06-697-001� t C� w >„IF '9 '9 v1 t Q �oeeY �;1r u 1 A ! 1 / EXISTING "EST-2" FIRE ol/ ALARM CONTROL PANEL L�hF AREA OF WORK KEY PLAN N..s SEQUENCE OF OPERATION: 1. FIRE ALARM INI'iTIATTON DEVICES: A, -MANUAL FIRE ALARM PULL STA11ON ACTIVA1ION 0 ANY FIRE ALARM PULL STATION SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. - ACTIVATE THE ALARM LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL. - INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING IN ENGLISH THE ALARMED DEVICE ON TH� FACP ALPHANUMERIC DISPLAY. ;. - TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED THIRD PARTY CENTRAL MONITORING STATION BY WO OF DIGITAL ALARM COMMUNICATOR. ti B.-AUTOMATIC FIRE DETECTORS ACTIVATION 0 ANY AUTOMATIC FIRE DETEC11ON DEVICE SHALL CAUSE THE FOLLOWING ACTIOK AND INDICATIONS: - ACTIVATE E AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. - ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL. - INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH,- TH&AkARMEG1 DEVICE ON THE FACP ALPHANUMERIC DISPLAY. - TRANS ITS A FIRE ALARM SIGNAL TO THE DESIGNATED THIRD PARTY CENTRAL MONITORING STATION BY WA OF DIGITAL ALARM COMMUNICATOR. 2.-SUPERVISORY ALARM INITIATION DEVICES. A. -DUCT DETECTORS ACTIVATION 01 ANY DUCT DETECTOR SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: — AC11VA E THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL. 4' — INDICATE THE LOCATION OF THE DUCT DETECTOR BY DISPLAYING IN ENGLISH THE ACTIVATED DEVICEI ON THE FACP AL,PHANUME IC DISPLAY. - TRANJITS.A SUPERVISORY ALAR SIGNAL TO THE DESIGNATED THIRD PARTY CENTRAL MONITORING STATION BY WAY OF DIGITAL ALA M COMMUNICATOR. * DEVICE MONITORED WITH SINGLE -INPUT MODULE, EST SIGA-CT1 N: DENOTES NEW DEVICE B.-SPRINKLER CONTROL VALVES E: DENOTES EXISTING [DEVICE ACTIVATION 0 ANY CONTROL VALVE SUP RVISORY SIGNAL INITIATING DEVICE (TAMPER SWTCHES AND BACK FLOW P,EVENTOR) SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: - ACTIVA�E THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL. ALARM NOTES - INDICATE THE LOCATION OF THE ACTIVATED DEVICE BY DISPLAYING IN ENGLISH THE ACTIVATED FIRE DEVICE) ON THE FACP ALPHANUMERIC DISPLAY. - TRANS ITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED THIRD PARTY CENTRAL MONITORING 1- FIRE ALARM SYSTEM SHALL BE U.L. LISTED AND NFPA 72 APROVED. STATIO� BY WAY OF DIGITAL ALARM COMMUNICATOR. 2- RISER INTERCONNECTIONS ARE DIAGRAMMATIC ONLY. 3- TOTAL ACTIVE AREA: 3,594 SQ. FT. NOTE: NOTIFICATION APPLIANCES WILL NOT BE ACTIVATED 4- FIRE ALARM SYSTEM TO BE "POWER LIMITED". ` 3.-TROUBLE SIGNALS. 5- THE INSTALLATION SHALL COMPLY WITH NFPA 70 CHAPTER 760 rdE OCCURREr;4CE OF ANY TROUBLE IN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTION AND 6- ALL WIRING AND CONDUIT SIZE SHALL BE IN ACCORDANCE WITH MANUFACTURER iNDICA11ONS: RECOMMENDATION, LOCAL CODES AND NFPA. •, - ACTIVATE THE TROUBLE LIGHT AND A DISTINCTIVE TROUBLE SOUND AT THE FIRE ALARM CONTROL 7_ ALL CONDUCT4�S SHALL BE SOLID COPPER. PANEL.; • - DISPLA� A TROUBLE DESCRIPTION ON THE FACP ALPHANUMERIC DISPLAY. 8- MAXIMUM CONDUIT FILLS TO BE 40%. MINIMUM RACEWAY SIZE •... - TRANSMITS A TROUBLE SIGNAL TO THE DESIGNATED THIRD PARTY CENTRAL MONITORING STATION 9- SYSTEM SHALL BE GROUNDED ACCORDING TO MANUFACTURER SPECIFICATION AND NEC • • BY WA, OF DIGITAL ALARM COMMUNICATOR. ARTICLE 250. .•• -•• NOTE: TR4�UBlE SIGNALS AND THEIR RESTORATION TO NORMAL SHALL BE INDICATED WITHIN 200 10-ALL WALL PENETRATION SHALL BE MADE WITH APPROVED (NEC) ELECTRICAL TUBING ` SECONDS.; AND SEALED WITH A U.L. LISTED FIRE STOPPER. (SEE FIRE STOP DETAIL). 11-THE 120V AC POWER FEED FOR THE FIRE PANE MUST BE FROM A DEDICATED CIRCUIT -'s 4.-FYRE SAFETY FUNCTIONS. AND THE BREAKER MUST BE IDENTIFIED THAT IS FOR THE FIRE ALARM CONTROL _`_` A.-AHU SHUTDOWN = - ACTIVA ON OF ANY AUTOMATIC DETECTOR (FLOW SWITCH SMOKE DETECTORS AND DUCT PANEL AND HAVE A LOCK ON IT. �yJ"• DETECIORS) SHALL AUTOMATICALLY SHUTDOWN ALL AIR HANDLER UNITS. " 12— VISUAL ALARM PER ANSI A117.1, 4.26, SFBC 513.3 AND ADA APPROVED. WALL - ACTIVATION OF ANY MANUALLY ACTUATED ALARM -INITIATING DEVICE (PULL STATION) SHALL MOUNTS 80" A.F.F. TO BUTTON OF STROBE LENS. AUTOM TICALLY SHUTDOWN ALL AIR HANDLER UNITS. 13-ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR B.-DOOR RELEASE SERVICE - ALL LOCKED EXIT DOORS IN THE BUILDING SHALL UNLOCK UPON RECEIPT OF ANY FIRE ALARM ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER NEC (NATIONAL ELECTRIC CODE) SIGNAL! BY MEANS OF "RELAY" CONTROLLED BY THE FIRE ALARM CONTROL PANEL. ARTICLE 760-61. 14—ALL N.A.C. WIRING SHALL BE CLASS "B" (STYLE "Y" ). INITIATING CIRCUIT WIRINGSHALL THE MAXIMU TIME PERIOD FROM ACTUATION OF THE INITIATING DEVICE UNTIL INITIATION OF ALL BE CLASS B SIGNALING LINE CIRCUIT WIRING SHALL BE CLASS B , (STYLE 4 ). RELATED FUNCTIONS AS LISTED ABOVE SHALL BE TEN SECONDS. , 15-HORN/STROBES SHALL BE LOCATED AS PER NFPA 72, CHAPTER 7. 16-STROBE LIGHT CIRCUITS SHALL BE SYNCHRONIZED AT 1HZ PER ADA AND NFPA 72. 17-THE SYSTEM SHALL HAVE BATTERY BACK UP FOR 24 HRS IN STANDBY MODE AND 5 I MINUTES IN ALARM. 18-EXISTING SYSTEM IS CLASSIFIED AS REMOTE SUPERVISING STATION FIRE ALARM SYSTEM'. 19-10 FEET CEILING HEIGHT MAXIMUM. 20-THE EST2 PANEL PROVIDE A CONTROL OF 96 DETECTORS AND 94 MODULES PER CIRCUIT AND PER LOOPS. S.W. 57TII COURT FIRE ALARM LEGEND SYMBOL DESCRIPTION MANUFACTURE MODEL FIRE ALARM CONTROL PANEL EST ES-T-2 FAC E IBM E BOOSTER POWER SUPPLY EST BP'S 1 CIA APS N AUXILIARY POWER SUPPLY SILENT KNIGHT 54195 ®E CONTROL RELAY EST SIG7"A-CR �M SINGLE INPUT MONITOR MODULE EST SIGA-CT1 © SIGNAL MODULE EST SIGA-CC 1 ©E ADDRESSABLE PULL STATION EST SIGA-270 ©WP ADDRESSABLE PULL STATION WEATHER PROOF EST SG­32 @D ADDRESSABLE SMOKE DETECTOR EST SI97A-PS 9` E ADDRESSABLE HEAT DETECTOR EST 'SIG�A-HRS t�*N DUCT DETECTOR SYSTEM SENSOR DH1100ACDCLP E DUCT DETECTOR EST SIGA-PS HQ HORN/STROBE (75cd) WHEELOCK NS.-24MCW-FR HQE HORN/STROBE (11Ocd) EST G1IF-HDVM H HORN/STROBE` WEATHER PROOF (1'10cd) STROBE LIGHT (75cd) EST WHEELOCK 757-8A-TW RS,S-24MCW-FR © ©E STROBE LIGHT WEATHER PROOF (110cd) EST CS405=-8A-TW EWL E ELEVATOR WARNING LIGHT LIGHT ENG.DISPLAY EL-1 TS E - MONITOR MODULE FOR TAMPER SWITCH EST SICA-WTM E E MONITOR MODULE FOR WATER FLOW SWITCH EST SIG.,A-WTM Dfl E MONITOR MODULE FOR BACK FLOW PREVENTO EST SIG.,A-WTM t ir PI, FIR61• is I •�, •• r rw% UA& as • . • Y Y . ♦ . r , • + • , • . , Y EXIT CORRIDORS AUbLIARY .... Y 9JMY W549s• REVISIONS .... AFIRE DEPARTMENT 03/22/06 THIS IS AN EXISTING 5 STORY FULLY SPRINKLED BUILDING SCOPE OF WORK: 1. FURNISH AND INSTALL NEW DEVICES TO EXISTING SYSTEM AS FOLLOW: QTY DESCRIPTION 1 NEW AUX. POWER SUPPLY (SK) 1 NEW SIGNAL MODULE (EST) 2 NEW DUCT DETECTOR (SYSTEM SENSOR) 2 NEW MONITOR MODULE (EST) 1 NEW SMOKE DETECTOR (EST) 3 NEW HORN/STROBE (WHEELOCK) 6 NEW STROBE LIGHT (WHEELOCK) \s FIRE ALARM _*--Z SCALE: 1/8 = 1'-•qn'' PLAN (SUITE t , MlAMl-DARE CO. FIRE DEPARTMENT APPLICATION #00��p— FIRE ALARM SYSTEM TO BE INSTALLED ED IN ACCORDANCE VVIIII NFPA 72; 70;101- APPROVEO MiAMI-DA.DE COUNTY FIRE DEPAR' ONT BLDG. PERMIT FIRE ALARM // FIRE SUPPRESSION�-1NJ1tER�. N w . . 4 `� ✓I tfJ N �oo� a U Q E­4 W � PROJECT NO.: DRAWING NO.: SCALE: 1/8" = V-0• DATE: 02/18/06 DRAWN BY: I.M. ISSUED: FOR PERMIT SHEET NO.: FA-01 01 OF 02