06-418-001I 1 0 BATTERY CALCULATIONS BPS-10 # 10 NE ITEM DESCRIPTION QTY STANDBY STANDBY ALARM ACTIVATED BOTH CURRENT CURRENT CURRENT CURRENT CURRENTS PER UNIT SUB -TOTAL PER UNIT SUB -TOTAL TOTAL (AMPS) (AMPS) (AMPS) (AMPS) 1 STROBE (75CD) 2 0 0 0.255 0.51 0.51 1 STROBE (11OCD) 0 0 0 0.311 0 t' 0 3 STROBE (110CD)WP 0 0 0 0.329 0 0 2 HORWSTROBE (75CD) 4 0 0 0.281 1.124 1.124 3 HORWSTROBE (110CD) 0 0 0 0.337 0 0 3 HORN/STROBE (110CD)WP 0 0 0 0.329 0 O' 4 BPS10 0 0.07 0 0.105 0 0 0 TOTAL 0 1.634 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 STANDBY 24 HOURS ALARM 5 MINUTES X 1/ 60 0.083 HOURS REQUIRED TOTAL SYSTEM REQ. STANDBY REQUIRED TOTAL SYSTEM REQUIRED ALARM STANDBY TIME TANDBY CURREIN CAPACITY ALARM TIME ALARM CIRCUIT CAPACITY (HOURS) (AMPS) (AMP -HOURS) (HOURS) (AMPS) (AMP -HOURS) 24 0 0 0.083333333 1.634 0.1362 REQ. STANDBY 1EQUIREDALAM TOTAL REQ. OPTIONAL REQ. BATTERY CAPACITY CAPACITY CAPACITY FACTOR OF CAPACITY (AMP -HOURS) (AMP -HOURS) (AMP -HOURS) SAFETY (AMP -HOURS) 0 0.1362 r 0.1362 1.2 0.1634 7.0 A/H Supplied NEW NNmlNIIIII cm BPS#IC nntmnnm it- F EST2 Cabinet Batte Calculation EXISTING Description Quantity Standby (ma) Alarm (ma) Total Alarm(ma) 2-MCM Main Controller/LCD 1 x 150 150 275 275 Front Panel LED Mcdules 1 x 5 5 16 16 DL2 Module 1 x 1 10 10 20 20 2-LSRA 0 x 80 0 80 0 Siga Smoke Detectors 32, x, , 0.000045 f 0.00144 0.000045 0.00144 Siga SD 2 x 0.000045 0.00009 0.000045 0.00009 Siga Single Stage Pull Stations 15 x 0.00025 0.00375 0.0004 0.006 Siga-CT1 6 x 0.00025 0.0015 0.0004 0.0024 Siga-CC1 7 x 0.00023 0.00161 0.0001 0.0007 Siga-CR 19 x 0.0001 0.0019 0.0001 1 0.0019 Siga-WTM 5 x 0.00025 0.00125 0.00025 0.00125 Siga-RM1 0 x 0.0002 0.0002 0.00025 0 Heat Detector 2 x 0.000045 0.00009 0.000045 0.00009 TOTAL (A) 165.01 TOTAL(B) 311.01 Battery Calculation , f Supervisory Hours (C)1 24 18attery Capacity (A.H) = 1.2j(AxC)+(0.0167xBxD)j/1000 Alarm Minutes (D) 1 5 1 Battery Capacity (A.H) = 3.986253578 jBatLCapacIty10A1H zzx_:9��� EOL �R%4�surm 430 S450-1 $450-2 S450-3 S450-4 S450-5 S450-6 PERMIT AREA ONLY .i�j�.+��f�Y�w�ii�iifJ���� �������;�./.li'//��/�i��r�������%�r>%����I.�:►/%/'l;�/''*,,,,,,,,,,,,,,,,,,,,,,, _ . EXISTING FIRE ALARM RISER: N.T.S 4 1 ,A System Na C-AJ-1149 r Rktkq - 2 w - r akdrq - 0 Hr L kuLv At An*.t -less Thml 1 crIvvq ft RstbV At 400 F - 4 Err/sq ft A 2 4 I3, A SECTIM A -A 1. "Or Or M how* - do 44/2 k Wd fdffaw{ 6#wI jA w wad W# (100-110 was lk Wd OW do be w WmW of Ai haw* � lei **Mr M I4Mww m%j y k www d aWa6. i w0b a rw4 qdm 1%w i W4 M M bow4a/M sepM w 1*6 a1M of ber w wd rw40.1M w..b Wo dd M 0 k 6 M 064 Y ww 1-1/4 k 1M 00" We of aiw of wddk � 'Ih k 0- � *VIM Sdeft a (w Mn4a) & "- No { k dw (w WAO *.I 4eibd fwtfra W, Gaff �l`4-Nfw{k4fp) dw(wWAIM1paL(wkw ahy,1.W Oh -New { k an (w ON" how (w 6WAO #w Sra1j'Nd"Y-163k1'1 dwi4Wm1widwdbd ewMkLWd w la,1►f.t eanNb w kbke0, w/ ph 4 h0: iwfldiw M Oqk Soww { k date Neely pdN Ita apdq w • pfwfwd Mw 1WIMM M be .wwwl bw 4 rlw. d Dew w kw bo 1, d wr w n0id k waw�eA•M No - OF Wdnw 4 M VW w tadf2 Ndmw -Smut -Ida 1,12 k I- d o -11" apOM .NiM M wm*% fide va 'q Seas d lbw, w wo whoa d wt N b pwM d W kaa4af Wee kh w{ wnadu, sob 1/2 k On bed d 9 fwM41 Ad be qM{ at Na aa�ada/IMa Merkeea w M i0 wlw d Nfw aa2 w IeOf wfawa d wl NJ comm1ept21 f2i1K'itl2, w or NU kIC - p`OOti, am w M-0 9 Swat (Ndc MIiFw wy dre m Q[ IMd Is wd} tlwio�Ow �"'� �' 1fa".wa 1r 1{7t is pnie f/ fwewow ^"°" *.oft 3166 00 C ® US I If rwaen� mmmmmmmmmommmmmmmmmmommmmmmmmmmmmmmmmmom mowmmmmmmw Mrd ■ ---- 1S i ■ ■ 1 ■ ■ 75cd ST ■ ■ _ - . S450-3 I ■ 7d COPY / SUPPLY ST CONFE CEn ` 1 I , I ■ f` f yy�� y� yy,�� G7 V V ■ ■ ■ is ------------------- ASSIST T1 ■ ■ ----- ■ ■ f'i 7 cd HALLWAY 1S RQOCATEO EOL S1R/450(1.E3IQ ■ r� -\ fi, e- --------------- F 75cd-------------- ■ ---- ---- ------------ ---- -�-e -------- ALEX TONY OFFICE 1 OFFICE 2 OFFICE 3 OFFICE 4 OFFICE 5 OFFICE 6 j ■ ■ - m 0 m m m m m 0 m m m m a m m 0 m m 0 m m m m m m m w 0 m 0 0 m m m m m ...... m 0 m 0 0 m 0 m 0 0 m a m m m w m 0 m 0 m m w m m w 0 m 0 0 m 0 m m m m w 0 m 0 m 0 m 0 m m m 0 go FIRE ALARM PLAN PERMIT AREA SCALE:1 /8"=1'-0" STROBE OUTPUT LOAD TABLE HORN/STR 75CD(ma) I HORN/STR 11OCD(ma) STR 75CD ma STR 110CD ma WP TOTAL Length Wire Size Vdrop Last Device Output Circuit QTY Sub -To QTY Sub -Tot I IQTYISub-Tot QTY Sub -Tot (mA) feet AWG V Volta e(V) STR. CIRC.#450 281 x 1 4 1 1124 1 337 1 x 1 0 1 0 255 1 x 1 2 1 510 329 IxI 0 1 0 1634 240 14 2.4079 17.9921376 SCOPE OF WORK: 1. THIS PROJECT IS A SUITE THAT SHALL BE ADDED TO PLAZA 57 BLDG. MAIN PANEL EXISTING, EDWARDS EST 2. 2. SUITE WILL BE PROVIDED WITH DETECTOR, STROBES, AND HORNS. PANEL IS EXISTING AS SHOWN AT RISER DIAGRAM. 3. CALCULATION WILL SHOW EFFECT ON EXISTIrG SYSTEM ONLY. SBOU R CE OIF OPERATION 1. SEQUENCE OF OPERATION SHALL AS FOLLOWS: A. OPERATION OF TAMPER SWITCH - SUPERVISORY INDICATION. 9. C. OPERATION OF PULL STATION- ALARM I(DICATIM, ACTIVATION OF AUDIOVISUAL AND VISUAL DEVICES. OPERATION OF SMOKE, HEAT, FLOW SWITCH - A•.ARM INDICATION. ACTIVATION OF AUDIOVISUAL AND VISUAL DEVICES, SHUTDOWN OF AIR HANDLING UNIT(S) IN THE AREA WHERE SIGNAL ORIGINATED. 0. DUCT MOUNTED DETECTOR PROVIDE ALARM INDICATION AT THE PANEL ONLY. 2. JURISDICTION: FINAL DECISION ON SYSTEM OPERATION DURING ALARM CONDITION AND LOCATION OF CENTRALIZED PERMANENTLY SUPERVISED LOCATION SHALL BE ESTABLISHED BY OWNER, FIRE MARSHALL AND RULING AUTHORITIES. CONTRACTOR SHALL COORDINATE OPERATION AND LOCATION OF DEVICES ACCORDINGLY BEFORE COMMENCING WORK. 3. TESTING: UPON COMPLETION OF THE INSTALLATION CONTRACTOR SHALL CONDUCT A COMPLETE TEST OF THE SYSTEM AREA AFFECTING THE TENANT SPACE IN QUESTION IN THE PRESENCE OF THE TENANT, LANDLORD AND FIRE DEPARTMENT'S REPRESENTATIVE(S). ANY CORRECTIONS TO THE SYSTEM REQUIRED FOR FINAL APPROVAL SHALL FIE DONE. FIRE ALARM NOTES 1. FIRE ALARM SYSTEM AND DEVICES TO BE UL USTED, POWER LIMITED AND COMPATIBLE. 2. VISUAL ALARM PER A.N.S.I. A 117.1.4.26 AND F.B.C. 3. FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED. 4. UPON ACTIVATION OF ANY MANUAL OR AUTOMATIC DEVICE A RED LED SHALL ILUMINATE ZONE IN ALARM AT F.A.C.P., IN ADDITION A LOCAL AUDIBLE ALARM SHALL SOUND THE GENERAL EVACUATION SIGNAL. IF AN INITIATION OR SIGNALING DEVICE IS DISCONNECTED OR WIRING TO THOSE DEVICES ARE CUT AN APPROPRIATE YELLOW TROUBLE LED SHALL ILUMINATE AND AN AUDIBLE SIGNAL SHALL SOUND AT THE F.A.C.P. 5. THE SYSTEM SHALL HAVE BATTERY BACK-UP FOR 60 HOURS IN THE SUPERVISORY MODE AND 5 MINUTES MINIMUM IN ALARM. 6. THE INSTALLATION SHALL COMPLY WITH N.E.C. CHAPTER 760 AND N.F.P.A. 72. 7. ALL CEILINGS ARE LESS 10' UNLESS OTHERWISE NOTICE. 8. ALL COMPONENTS ARE LISTED FOR FIRE SERVICE USE. 9. THE EST2 PANEL PROVIDE A GONIROL OF 96 DETECTORS AND 94 MODULES PER CIRCUIT AND PER LOOPS.(SEE CUT -SHEET) 10. HEAT DETECTOR IN ELEVATOR SHAFT SHALL BE FIXED TEMPERATURE. 1357. 24" MAXIMUM DISTANCE FROM SPRINKLER HEAD. PER FIRE DEPARMENT HEAT SENSOR SHALL BE PART OF THE FIRE ALARM SYSTEM, CORRELATE TO A SMART RELAY TO ACTIVATE THE SHUNT TRIP FOR ELEVATORS UPON ALARM ON THE HEAT DETECTOR. FIRE ALARM MUST PROVIDE SUPERVISION FOR POWER AT THE SHUNT TRIP SYSTEM. 11. PROVIDE RELAY FOR FIRE HAT ACTIVATION AT ELEVATOR CAR, UPON ALARM AT SMOKE DETECTORS AT THE MACHINE ROOM & ELEVATOR SHAFT. 12. FIRE ALARM SYSTEM IS A REMOTE MONITORING STATION WITH 2 LINES DIALER. 13. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS "B", STYLE "Y" WITH AN AVERAGE OUTPUT OF 2 AMPS. 14. SEQUENCE OF ELEVETOR CAPTURE: A. INITIATION OF SMOKE DETECTOR AT MACHINE ROOM SHALL CAPTURE THE ELEVATOR TO THE FIRST FL. IN ADDITION FIRE HAT AND ELEVATOR WARNING LIGHT AT ELEVATOR CAR SHALL BE ACTIVATED. B. INITIATION OF SMOKE DETECTOR A'F FIRST FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE SECOND FLOOR. C. INITIATION OF HEAT DETECTOR (OPEN AREA) AT SECOND AND THIRD FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE FIRST FLOOR. D. INITIATION OF SMOKE DETECTOR FROM FOUTII AND FIFTH FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE FIRST FLOOR. -CEILING 3'-2" MIN. SMOKE - DETECTOR A/C DIFFUSER AND /OR FLUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL N.T.S SCAT FcRTS EXISTING FIRE ALARM DEVICE LEGEND SYMBOL DESCRIPTION CATALOG NUMBER MOUNTING HEIGHT @OR®E SMOKE DETECTOR SIGH -PS / SIGA-SB ® HEAT DETECTOR SIGA-HRS 0- DUCT DETECTOR SIGA-SD ® CONTROL RELAY SIGA-CR MR MULTI -VOLTAGE CONTROL RELAYS Mk-101 75M STROBE (75CD) # G 1 F -VM 80" AFF TO BOTTOM 750 HORN/STROBE (75CD) G1F-HDVM 80" AFF TO BOTTOM LtJ 11ocD HORN/STROBE (11OCD) 757-8A-T 80" AFF TO BOTTOM ® tco wpp STROBE (110CD)(WEATHERPROOF) CS405-8A-TW/LKW-1/449 80" AFF TO BOTTOM (J t wD HORN/STROBE(110CD)(WEATHERPROOF) 757-8A-TW/757A-WBW 80" AFF TO BOTTOM O WP PULL STATION (WEATHERPROOF) SG-32 48" AFF TO CENTER 10 MANUALL PULL STATION SICA-270 48" AFF TO CENTER ® FIRE ALARM JUNCTIONBOX SIZE AS NEEDED ® BOOSTER POWER SUPPLY BPS-10 ® FIRE ALARM CONTROL PANEL EST-2 (ANALOG CONTROLPANEL) Q ELEVATOR WARNING LIGHT EL•-1 72" AFF TO CENTER AP ® WATERFLOW/TAMPER MODULE SIG4-WTM ® TAMPER SWITCH BY OTHERS ® FLOW SWITCH BY OTHERS IN ® CONTROL MODULE SIGA-CT1 Aqk ® SIGNAL MODULE SIGA-CC1 ® CONTROL MODULE SICA-CT2 BLOG. PERMI PLANS ARE BASED ON CONTRACT DRAWINGS PROVIDED BY ENGINEER ON RECORD. TO THE BEST OF MY KNOWLEDGE. I'M PROVIDING THE DESIGN OF CONNECTIONS TO MAIN FIRE ALARM SYSTEM AND PERIPHERAL DEVICES PER MANUFACTURER RECOMMENDATION, INCLUDING DROP OF VOLTAGE AND BATTERY CALCULATIONS 1 9E91 13PrS#2 am tTEVA Rem JIMA tT= REM BEM 1 BPSiIO EOL ST#1 EOL ST#3 EOL ST#8 EOL Sr#9 EOL ST#11 EOL STR#12 EOL STR#16 NAC#1 USED EOL STR #11C I EOL STR# 450 NEW EOL ST#2 EOL ST#4 EOL ST#7 EOL ST#10 EOL ST#12 EOL HORN#5 EOL STR#410 EOL STR #17 EOL STR #15 NAC#2 SPARE I EOL ST#2A EOL ST#5 EOL ST#8 EOL Sri10A EOL ST#11C EOL STR#13 EOL STR 018 NAC#3 SPARE EOL STR #13 NAC#3 SPARE EOL HORN01 EOL HORN#2 EOL HORN#3 EOL-MORN#4 EOL HORN#5 EOL STR#14 NAC#4 SPARE NAC#4 SPARE EOL STR 014 I NAC#4 SPARE W-DADE CO. FIRE DEPARTMENT UCATION #Q62lo-101 ALARM SYSTEM TO BE LED IN ACCORDANCE WITH NFPA 72; 70;101- p5p."ift0Vr=® ; OUNTY FIRE DEPARTNMNT FIRE ALARM FIRE SUPPRESSION W e MAIN EXT,�� LOCATED AT ELECT. RM. ® BPSJ10 I I I I I �III��I ■�I���I���I�■ � I�k� � KEY PLAN PERMIT AREA ••��Ifltltt _ m LL - '^C43 U .uJ QI Q. D U vw , O w ffw ,^ V , w F_ LEA/ sees Lr) O g Q V � g N �^ Q W CL O O nn Z. Of 0- cy- .(U LLJ 0 Lei Q• 0 V al O O O1 V3 cu t0 Ln r-• Ln rrn ~ L N fn M rd N 00 a1 mot' a_j 00 00 Ln Ln m O O >i A I Qj v v b v) � o I- u- � O •L N Q� Lu E. BORJA P.E.# 36040 ELECTRICAL CAD DATE: 02/02/06 SCALE: AS SHOWN EB# 000 7048 SHEET: FA-1 i OF 1