06-2099-003EST2 Cabinet Battery Calculation (EXISTING)
Description
Quantity
Standby (ma)
Alarm (ma)
Total Alan-n(ma)
2-MCM Main Controller/LCD
1
x
150
150
275
275
Front Panel LED Modules
1
x
5
5
16
.16
DL2 Module
1
x
10
10
20
20
2 ti S RA
0
x
80
0
80
0
Siga Smoke Detectors
36
x
0.000045,
0.00162
0.000045
0.00162
Siga Single Stage Pull Stations
14
x
0.00025
0.0035
0.0004
0.0656
Sl+ a-CT1
6
x
0.00025
0.0015
0.0004
0.0024
Siga-CC1
7
x
0.00023
0.00161
0.0001
0.0007
Siga-CR
17
x
0.0001
0.0017
0.0001
0.0017
Siga-WTM
5
x
0.00025
0.00125
0.00025
0,00126
Siga-RM1
0
x
0.0002
0.0002
0,00025
0
Heat Detector
3
x
0.000045
0.000135
0.000045
0.000135
TOTAL (A)
165.01
TOTAL(B)
311.01
Battery Calculation
Supervisory Hours
(C)
24
Battery Capacity (A.H) =
1.2((AxC)+(0.0167xBxD))/1000
Alarm Minutes
(0)
51
Battery Capacity (A.H) =
3.986245979 BattCapacitylO A/H
BATTERY
CALCULATIONS BPS-10 # 12(NEW)
ITEM
E ESCRIPTiON
CITY
STANDBY
STANDBY
ALARM
ACTIVATED
BOTH
CURRENT
CURRENT
CURRENT
CURRENT
CURRENTS
PER UNIT
SUB -TOTAL
PER UNIT
SUBTOTAL
TOTAL
(AMPS)
(AMPS)
(AMPS)
(AMPS)
1
STROBE (75CD)
2
0
0
0.255
0.51
0.51
2
HORN/STROBE (75CD)
3
0
0
0.281
0.843
0.843
3
HORN/STROBE (11000)
0
0
0
0.337
0
0
4
BPS10
1
0.07
0.07
0.105
0.105
0.175
0
TOTAL
0.07
1.458
REQUIRED OPERATING
TIME OF SECONDARY POWER
SOURCE FROM NFPA 72
STANDBY
24
HOURS ALARM
5
MINUTES X 1/
60
0. 883
HOURS
REQUIRED
TOTAL SYSTEM
REQ. STANDBY
REQUIRED
TOTAL SYSTEM
REQUIRED ALARM
STANDBY TIME
STANDBY CURRENT
CAPACITY
ALARM TIME
ALARM CIRCUIT
CAPACITY
(HOURS)
(AMPS)
(AMP -HOURS)
(HOURS)
(AMPS)
(AMP -HOURS)
24
0.07
1.68
0.083333333
1.458
0.1215
REQ. STANDBY
REQUIRED ALARM
TOTAL REQ,
OPTIONAL
REQ. BATTERY
CAPACITY
CAPACITY
CAPACITY
FACTOR OF
CAPACITY
(,',MP -HOURS)
(AMP -HOURS)
(AMP -HOURS)
SAFETY
(AMP -HOURS)
1.68
0.1215
1,8015
1.2
2.1618
TO A/H Supplied
STROBE OUTPUT LOAD TABLE
HORNI$TR 75CD(ma)
HORNISTR 110CD(ma)
STR 75CD(ma)
HORN1t3TR 11OCD(ma)WP
TOTAL
Length
Wire Size
Vdrop
Last Devtce
Output Circuit
QT
Sub -Tot
QTY
Sub -Tot
QTY
Sub -Tot
1
QTY
Sub -Tot
(mA)
(feet)
AWG
V
Voltage(V)
STR. CIRC.#18
281
x
3
843
337
x
0
0
9 A A
x
2
1 510
329
1 x
1 0
1 0
1353
300
14
2.4922
17,907774
System No, C-AJ-1149
FP.almq-2Ih
T P,atirg - 0 Ilr
L Ratkg At t4lent - Less Than 1 CFM/sq Ft
L P,ati j At 400 F- 4 CI N/sq f t
SLCTI(1M A -A
1. rkex or NA tl,%m?-1y - Wo 4-1/2 rn. Duck reinraced rqM" or
mrmd wrgM (100;-150 pcQ comete. tat may aho be constructed of
arty UL C miroord C-,:xre'.e i oc+-s r. Nat dam of opening is 12 h
See Coxrr'.e Vfk."_s (C" cate9orp in fhe Fin Resiatonce 0lred"
fa names of manufadurom
2. nvau* ra-4vta - One meldk pipk condul or luting to be iatdw
within 114 fuestop u)ilem. Pips, corIM or Nbirg to be rV supported
on both side* of Rwa a rat ossernby. Ru amuhr space d 6� 0 h
p�ipea, coed a b*g mco*4 to Pat ay be used 4 h the oAosnnp typo and sie* of matalFe
A. Sled Pie - Wave 10 h dam (er smarter) Scbedute 10 (at hoarier)
sled pps.
0, Cc qdl - Norm 4 in. dram (or smeller) sled efeMod meta16e tubing
or steel conduL'
C. C:,ppar lutirl - Have 4 k Gam (or sm ter) Typo L (or t*Vw)
capper twrs
0. C"Pper r;e - Nan 4 in, dram (or xr4kr) Reg" (or heavier) copper
3, roto vale,KA - i in 0 in. Nci nen of min 4 pd mineral roar bA
ind6on for we 4 ln, dam (and snaAw) pqm conduits or tubing* and
o nun 4 hthiidav es of m n 4 pd ftim d rod ball iuuhUoa for ppo
aer than non I rn. dam, fumy pocrrd into opening as o pmnaned
FPocking mAmal to bo rec.4 1.tooyp eurface of Roar or rran
both surfaa of MA as regdred to aaormr do ON repdred Nakm"
of fil materiel.
4. F 1, W d x Cm,,y 11claW - Szd-0 - Nib 1/2 w W*Ie s of ti
materhl opprad WViw the omdue, hush WO fM top sudoa Of Boar or
both surfaces of MCI, NR the point of contact locot7on between ppo and
wnaeta o mb 1/12 h dam bend of fA mots" "lot opprW at the
corwets/* wi sfoce on IM top surface of floor and on both surfaces
of Ira
t*09 CIUMIRUCdW81 CFirA . S UIV OF
IM,GC - CF.i01% CP800 or FS--ONE Sealmt
OMK l Ratings q,Py any when FS-ONE Seohrt ie used}
the tti Close iricaGae N
of
,� • @us
racafov s.srEes Dwerber 2a mooC
SEQUETICB OF OPFdt�'t,Ti
1. SEQUENCE OF OPERATION SIHALL AS FOLLOWS:
A. OPERATION OF TAMPER SYATCII4 - SUPERVISORY INDICATION.
C. OPERATION OF PULL STATION - ALARM INDICATION, ACTIVATION OF AVDIO/VISUAL AND VISUAL DEVICES.
OPERATION OF SMOKE, HEAT, FLOW SNATCH - ALARM INDICATION, ACTIVATION OF AUDIO/VISUAL AND VISUAL DEVICES, SHUTDOWN
OF AIR HANDLING UMT(S) IN IHE AREA WHERE SIGNAL ORIGINATED.
D. DUCT MOUNTED DETECTOR PRn)VIOE ALARM INDICATION AT THE PANEL ONLY.
2. AURISDICTiON: FINAL DECISUON ON SYSTEM OPERATION DURING ALARM CONDITION AND LOCATION OF
CENTRALIZED PERMANENTLY SUPERVISED LOCATION SHALL BE ESTABLISHED BY OWNER, FIRE MARSHALL
AND RULING AUTHORITIES. CONTRACTOR SHALL COORDINATE OPERATION AND LOCATION OF DEVICES
ACCORDINGLY BEFORE COMMENCING WORK.
3. TESTING: UPON COMPLETION OF THE INSTALLATION CONTRACTOR SHALL CONDUCT A COMPLETE TEST OF
THE SYSTEM AREA AFFECTING LANDLORD AND FIRE DEPARTMENTS RE RESNANT ENTATTIVE(SACE IN ). AN NCOR CORRECTIONS TO IN THE THE SYSTEOF THE M
TENANT,
REQUIRED FOR FINAL APPROVAL SHALL BE DONE.
OFFICE
M EOL STR/18(t.3A)
8-5
-DSD-2
AICAMA
FiRL ALARM NOTE•
1.
FIRE ALARM SYSTEM AMID DEVICES TO BE UL LISTED, POWER LIMITED
AND COMPATIBLE.
2.
VISUAL ALARM PER A.N .S.I. A 117.1.4.26 AND F.B.C.
"
3.
FIRE ALARM SYSTEM SHALL BE TOTALLY SUPERVISED.
•
4.
UPON ACTIVATION OF ANY MANUAL OR AUTOMATIC DEVICE A RED
LED SHALL ILUMINATE BONE IN ALARM AT F,A.C.P., IN ADDITION A
z.
LOCAL AUDIBLE ALARM, 2THALL SOUND-. THE. GENERAL FVAQJATION
SIGNAL. IF AN INITiAr,_K,;1 OR SIGNALING DEVICE iS DISCONNECTED
`
OR WIRING TO THOSE DEVICES ARE CUT AN APPROPRIATE YELLOW
TROUBLE LED SHALL ILILIMINATE AND AN AUDIBLE SIGNAL SHALL
SOUND AT THE F.A.C.P.,
5.
THE SYSTEM SHALL HAVE BATTERY BACK-UP FOR 60 HOURS IN THE
SUPERVISORY MODE AIND 5 MINUTES MINIMUM IN ALARM.
6.
THE INSTALLATION SHAD_ COMPLY WITH N.E.C. CHAPTER 760
AND N.F.P.A. 72.
7.
ALL CEILINGS ARE LESS 10' UNLESS OTHERWISE NOTICE.
PIKE ALARM SYSTEM TO BE
8.
ALL COMPONENTS ARE ILiS1 ED FOR FIRE SERVICE USE.
9.
THE EST2 PANEL PROVIDE A CONTROL OF 96 DETECTORS
INSTAUM IN ACCORDANCE VM
AND 94 MODULES PER CIRCUIT AND PER LOOPS.(SEE CUT -SHEET)
NEPA72; 70;101•
10.
HEAT DETECTOR IN ELEVATOR SHAFT SHALL BE FIXED TEMPERATURE. 1357.
24" MAXIMUM DISTANCE FROM SPRINKLER HEAD. PER FIRE DEPARMENT
HEAT SENSOR SHALL BE PART OF THE FIRE ALARM SYSTEM,
APPROVED
CORRELATE TO A SMART RELAY TO ACTIVATE THE SHUNT TRIP FOR ELEVATORS
UPON ALARM ON THE (HEAT DETECTOR.
IVitAMi-UADE COUNTY FIRE DEP"TIYiENT
FIRE ALARM MUST PROVIDE SUPERVISION FOR POWER AT THE SHUNT TRIP SYSTEM.
8100. PEAMIt FIRE ALA.Rti-t-1
11.
PROVIDE RELAY FOR FIRE HAT ACTIVATION AT ELEVATOR CAR, UPON ALARM
FIRE SUPPRESSION-. WATEA MXN EXT.
AT SMOKE DETECTORS AT THE MACHINE ROOM & ELEVATOR SHAFT.
QATC
12.
FIRE ALARM SYSTEM IS rA REMOTE MONITORING STATION WITH 2 LINES DIALER.
-
13.
NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE CLASS "B", STYLE "Y"
MIA 11-DADECO. RkE DEPr�l> ARTNIEN'�'
WITH AN AVERAGE OUTPUT OF 2 AMPS.
APPLICATION # 5, " ``DPL7 y
14.
SEQUENCE OF ELEVETOIR CAPTURE:
A.
INITIATION OF SMOKE DETECTOR AT MACHINE ROOM SHALL CAPTURE THE ELEVATOR TO THE FIRST FL.
IN ADDITION FIRE HAT AND ELEVATOR WARNING LIGHT AT ELEVATOR CAR SHALL BE
ACTIVATED.
B.
INITIATION OF SMOKE DETECTOR AT FIRST FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE
SECOND FLOOR.
C.
INITIATION OF HEAT DETECTOR (OPEN AREA) AT SECOND AND THIRD FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE
FIRST FLOOR.
D.
INITIATION OF SMOKE DETECiOR FROM FOUTH AND FIFTH FLOOR ELEVATOR LOBBY SHALL CAPTURE THE ELEVATOR TO THE FIRST FLOOR.
SCOPE OF WORK:
1. THIS PROJECT iS A SUITE THAT SHALL BE ADDED TO PLAZA 57
BI-DG. MAIN PANEL EXISTING, EDWARDS EST 2.
2. SUITE WILL BE PROVIDED WITH SMOKE DECT, DUCT DECT, STROBES, AND HORN/STB
PANEL IS EXISTING AS SHOWN AT RISER DIAGRAM.
3. CALCULATION WILL SHOW EFFECT ON EXISTING SYSTEM ONLY.
WIRE
LEGEND:
A = 2#18,
FPL (DATA)(UNSHIELDED)(BLUE)
B = 2#14
FPL (HORN)(UNSHIELDED)(RED)
S = 2#14
FPL (STROBE)(UNSHIELDED)(RED)
MINIMUM COUINDUIT ALLOW IS 1/2" EMT MINIMUM 40%
1 FILLED MAX.
tf_.____-__
SMOKE
OFFICE
CONFERENCE
ROOM L
Si
OFFICE
J _
w
a
i
OfFlCE
OFFICE
OFFICE
$I
^Si
S18-3100
PANTRY -�
CD
0 LOBBY
AREA L 518-1 IID r ;�
HD -I I r
1
1
1
I
TO EXISTING
FACP
(: �So-
ELECTRICALlit
YLOO _ _.ROOiA�_
CORRIDOR
FIRE ALARM PLAN -
KEY -PLAN
+ N.T.S
EXISTING FIRE ALARM DEVICE LEGEND
SYMBOL
DE:.':RIPTION
CATALOG NUMBER
MOUNTING HEIGHT
SD OR(JE
SMOKI: DETECTOR
SIGA-PS / SIGA-SB
HEAT DETECTOR
SIGA-HRS
g--OR Do
DUCT (DETECTOR
SIGA-SD
of
CONTROL RELAY
SIGA-CR
RJR
MULTI. -VOLTAGE CONTROL RELAYS
MR-101
7SCO
� OR 7gj
STROBE (75CD)
G1F-VM
80" AFF TO 80TTOM
7
Iyj OR
HORtJ/ ;TR08E (75CD)
G1 F-HDVM
80" AFF TO BOTTOM
lY 110CD
HORN/:.STROBE (11OCD)
757-8A-T
80" AFF TO BOTTOM
5i 1WP D
STROBIw; (110CD)(WEATHERPROOF)
CS405-8A-TW/LKW-1/449
80" AFF TO BOTTOM
yy
UY 1 WP
HORN/ -I ROBE(110C0)(WEATHERPROOF)
757-8A-TW/757A-WBW
80" AFF TO BOTTOM
CFO WP
PULL .'PTATION (WEATHERPROOF)
SG-32
48" AFF TO CENTER
U
MANUALL PULL STATION
SIGA-270
48" AFF TO CENTER
®
FIRE ALARM JUNCTIONBOX
SiZE AS NEEDED
BOOSTER POWER SUPPLY
BPS-10
FIRE ALARM CONTROL PANEL
EST-2 (ANALOG CONTROLPANEL)
LFW
ELEVA'(OR WARNING LIGHT
EL-1
72" AFF TO CENTER
®
WATERi'1-OW/TAMPER MODULE
SIGA-WTM
TAMPEII SWITCH
BY OTHERS
WSJ
FLOW ''SWITCH
BY OTHERS
CONTROL MODULE
SIGA-CT1
SIGI'VA. MODULE
SIGA-CC i
CONTROL MODULE
SIGA-CT2
DETECTOR A/C
DIFFUSER AND /OR
FLUORECENT LIGHT
SMOKE DETECTOR MOUNTING DETAIL
awl",
PLANS ARE BASED ON CONTRACT DRAWINGS
PROVIDED BY ENGINEER ON RECORD. TO
THE BEST OF MY KNOWLEDGE. I'M PROVIDII,
THE DESIC14 OF CONNECTIONS TO MAIN FIRE
ALARM SYSTEtA AND PERIPHERAL DEVICES PE
MANUFACTURER PECOMMENDATION, INCLUDING
DROP OF VOLTAGE AND BATTERY CALCULATiO'
}
el