Loading...
06-2099-002Miami -Dade Fire Rescue Fire Alarm Pre -Submittal Checklist a i? el{ - A, YES NO NIA The FACP and all sub panels in unoccupied rooms are protected with a smoke &15rlA) & 28 detector. If a complete automatically activated system, there is at least 1 pull station each floor 29 or 2 for large buildings. If a manually activated system, the travel distance to reach a pull station is less than 30 200' and near all exits. All automatic initiating devices are shown and are located in accordance with NFPA GOO 31 72, the manufacturer's specifications, and accepted engineering ractices. All visible devices are placed per the tables in NFPA 72 and each strobe has it's 32 candela rating listed on the floor plan and riser. All corridor spaced strobes are placed a maximum of 100' apart and wvithin 15' from !! ST! ►V 33 ends of the corridor. /'/ 34 All spaces meet the audible characteristics of NFPA 72 and NFPA 101. Walls, partition, racks, shelves and equipment which may block deviices are shown 35 with their height indicated. Duct detectors or relays for duct detectors are shown on the floor plan and riser for all 36 systems over 2000 cfm. The fire pump is monitored for run, phase reversal & phase loss to _ a continuously 37 manned location, or the supervised fire alarms stem. 38 Elevator recall is connected to the fire alarms stem. All interconnected fire alarm control panels are arranged to function ias a single 39 system and monitored for integrity er NFPA 72. All relays for automatic extinguishing systems are shown on the floor plan and riser. 40 Hood, sprinkler, FM200, etc. The class and/or style are shown for all initiating device circuits, signal line circuits 41 and notification appliance circuits. The maximum number of each device type is provided for each IDC biased on device load or each SLC, based on class and style, per NFPA 72 and the manufacturer's 42 specifications. The capacity of each power supply and circuits complete with individlual device 43 current is specified for each fire alarm control panel and NAG panel The total footage to the last device including voltage drop calculations are provided 44 for each notification appliance circuit for each power supply. 45 The wattage tap is Indicated for all speakers, 46 The wattage capacity and load is provided for each amplifier. All lodd and draw calculations correlate with the provided spec sheets and the device 47 draw or available power is highlighted on the specification sheets. This system is a Local Fire Alarm System or a Proprietary Supervising Station Fire 48 Alarm System and is stated as such on the plan. 24 hours secondspower) This system will be certificated or placarded as a Central Station Service Fire Alarm 49 System and is stated as such on the plans. 24 hours secondspower) This system is an "Existing Remote Supervising Station Fire Alarm System" as stated 50 on the plan and will be provided with 24 hours of seconds power). This system includes Emergency Voice Evacuation and is provided writh 15 minutes of 51 secondary alarm power. This system is being provided back up power by an emergency geneirator and will 52 provide 4 hours of standby power plus the appropriate secondary alarm power. Battery calculations, detailed in chart form, showing all information required per NFPA 53 72 4.4.1.5.3.1 are provided for each back-up power supply. Instructions are available on request. Refer to the instructions for a tune by line '• clarification of the above items. Designe Signatur (,vt<< Phone #: 2 7 d by: � _