06-138-012STRAPS ANCHORED TO SLAB
W/ 1/4'xl' TAPCONS W/ WASHER5,
yy,.Y
J+ i
11/2' GALV, x 22 Ga.
METAL 5TRAP5.
LOW VELOCITY
FLEXIBLE DUCT
1/2' PER FT.
MAXIMUM 5AG,
(2.5' FOR 5 FT. SPACING)
FLEXIBLE DUCT HANGING DETAIL
NTS
LOW VELOCITY r <= FLOW
SHEET METAL DUCT
INSULATED AND SEALED
AGAINST DUCT INSTALLATION.
MANUAL VOLUME - SPIN -IN TAKE -OFF
CONTROL DAMPER FLEXMASTER
SERIES 3000S FOR
SHEETMETAL
— �- LOW VELOCITY
FLEXIBLE DUCT
......... TO DIFFUSER, MANUF. BY
FLEXMASTER TYPE 4M
(UL-181) OR EQUAL
SQUARE ELBOW DETAIL
N.T.5.
NVAC LEGEND t SYM501-8
F—
VOLUME DAMPER
Q
THERM05TAT
®
DUCT SMOKE DETECTOR
LOCAL AUDIOVISUAL ALAF41 W/
TROUBLE INDICATOR LIGHT
FOR DUCT SMOKE DETECTOR
MODULAR R/A GRILLE
h -)MODULAR
DIFFUSER (SUPPLY AIR)
Lu J
R/A TRHU V CLEAR UNDERCUT
C 1[] 1x12 DENOTES CLG DIFFUSER,
100
NECK SIZE AND CFM
NVAC PLAN NOTES
I. FINAL LOCATIONS OF THERMOSTATS
SHALL BE COORDINATED WITH ARCHITECT
AND ENGINEER
ENGINEER SHALL BE CONSULTED ON ANY
CHANGES IN THERMOSTAT LOCATIONS.
2. PROVIDE I' MN. DOOR UNDERCUT FOR RETURsl AIR
WHERE SHOWN. MEASURE UNDERCUT SIZE
FROM FINAL FINISHED LEVEL. (ABOVE CARPET
OR OTHER FINISH.)
3. COM HATE EXK FAN AND A/C UNITS ROOF
OPENNMS W/ STRUCTURAL DWGS. AND MME.
SPECIF. t RECO lWATIONS.
4. ALL SANITARY AND EXN. VENT SHALL BE 10'
MIN. AWAY FROM ANY AIR COND. O/A NTAKE.
5. ALL MECR EQUIP. ON ROOF SHALL BE
N5TALLED A MNIMUM OF 10' FROM PARAPET.
x 22 CAA. HANGER STRAP
)T INTO CONCRETE 5LAE3 W1 WASHER
MAX. (TYPICAL)
LOW VELOCITY
GLA35 FIE3ER DUCT
K11/2°x22GA,
4NNEL
PI=R 5MACNA FIBROUS GLA55
DUCT CONSTRUCTION 5TANDARD8
RIGID FIBERGLASS DUCT HANGING DETAIL
N TIST S
JENNA WHITE
RETAIL BUILDOUT
SUITE 120, FIRST FLOOR, PLAZA 57
7300 S.W. 57TH COURT
CITY OF SOUTH MIAMI
SOUTH MIAMI, FLORIDA 33143
H,V.A,C, OFFIC
SCALE: 1/4' a l'-O'
To
X />
<,
AN - SUITE 120
AN (C N, o r ZANY E
VECH
VIV'ANA FRAW
P
E 143:iCj3 fv'C
( fi .i3 of
to
WV 2I SlrccJ�rri r E_ .331 2
1 g I n f: e Y' a. c C x i I
G 113;C s, s ry�i CIATE
ur:�� I�I�I��,F s� •�,
TYPICAL TOILET EXHAUST FAN
w CHI ® 0.125 S.P.
CONNECTED TO LIGHT SWITCH
110-1-60
O/A CALCULATION
510 *x30P/10004 ■ 11 P x 20 CFMI / P - 340CFM
�r�x� r r w1■ r■■: ■■■
AIR CONDITIONING SCHEDULE
UNIT DESIGNATION
__ AC -I
SUITE 120
_
AREA OR UNIT SERVED
.
UNIT TYPE
0):5FLIT
MANUFACTURER
RHEEM
AIR H DU G UNIT ODEL
RBHK-17
CONDENSING UNIT MODEL
RCN-36A1
,
COOLING COIL MODEL
RPMC-030,JA
�`
CU UNIT WEIGHT, LBS
225
•lit
•_ ..,-.�.
AHU UNIT WEIGHT, LBS
78
.,
ELECTRICAL SERVICE AVAILABLE (1)
208-140
SYSTEM AMPS. (COMPRESSOR)
13.5
7
MIN. CIRCUIT AMPACITY, COND. UNIT
11
MAXIMUM FUSE SIZE OR HACR
25
SYSTEM SEER
13.15
TOTAL SENSIBLE CAPACITY BTU H ARI
20,000
TOTAL COOLING CAPACITY, BTU H (ARI)
21,400
SUPPLY AIR CFM)/STATIC PRESS. H 0
1000
EXTERNAL STATIC PRESSURE, " WG (W/O FILTERS
0.36
FAN MOTOR H.P.
HEATING SYSTEM TYPE 1
ELECT.
,
TOTAL HEATING CAPACITY, BTU H
11,000 .
HEATER RATING
5 KW
GENERAL
REFRIGERANT PIPE LENGTH
SEE PLANS
REFR. LINE SIZES O.D. SUCTION LIQUID
(3)
'
ACCESSORIES: (U PROVIDE VWSLE POINT ELECTRICAL CONNECTION WITH FACTORY -WIRED ELECTRIC HEATER
(2) PROVIDE AIR HANDLING UNIT WITH FACTORY INSTALL D° CIRCUIT BREAKER
(3) INSTALL RFfR1C,ERANT PIPING SIRE AND ACCESSORIES PER FACTORY SPECS. FOO VaO SUCTION LIFT REQUIRE eT
DESIGN CRITERIA
COOLING & HEATING LOAD METHOD ASHRAE
CHAPTER 26i
INSIDE & OUTSIDE DESIGN TEMPERATURES
INSIDE
SUMMER 75'F
OUTSIDE
SUMMER 510F ,.
WINTER 45°F
WINTER 12'F
OTHER DESIGN PARAMETERS (SEE ENERGY CALCULATIONS). -
GLASS TYPE SINGLE CLEAR SINGLE TINTED
GLASS INTERIOR SHADING VENETIAN BLINDS
1___HOTWATER
WALL INSULATION R - 3
ROOF INSULATION R -19
HEAT RECLAIM UNIT - N/R
GROUND LEVEL
BUILDING PLAN,
SCALE: iz3V-0'
f
yam.,
__
— _ q
THESE PLANS ARE FOR BUILDING DEPARTMENT tifVIEW. THEY ARE
NOT TO BE CONSTRUED AS FINAL CONSTRUCTION DOCUMENTS
UNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED AND
COMMENTS INCORPORATED INTO THESE D S. DUE TO THE
VARIATIONS IN INTERPRETATIONS OF THE COPE THAT OCCUR IN
DIFFERENT MUNICIPALITIES FINAL APPROVAL D REVIEW IS NEEDED
TO ASSURE COMPLIANCE WITH THE APPLICABLE CODES AND
STANDARDS.
a I I?MVVM TTRZ—
FEVOCIN
V .A.C■ t
PARTIAL ONCE PLAN
�•wti, ....... SUITE 120
' SCALE:
`\I DATE- SOY. CD 12-08-05
PROJECT NO 2004.23 J
WWING NO
�N M.1
2