06-138-01024" MAX. ARM OVER 24" MAX. ARM OVER
LENTH PER NFPA 13 LENTH PER NFPA 13
1996 4-14.2.3.4 1996 4-14.2.3.4
1 1 (TYPICAL) I _
NEW NEW
1" TEE (MWk I I I I 11 /- 1 /4" TEE (MIN)
1" DROP "I I I I 11-- 1" DROP I 1 1" DROP
EXISTING) L-- EXISTING
SPRINKLER I SPRINKLER SUPPLY
SUPPLY BRANCH BRANCH
CEILING 1 I T CEILING
NEW SEMI -RECESSED
PENDANT SPRINKLER HEAD
CENTERED IN CEILING TILE
`ANEW SEMI -RECESSED
PENDANT SPRINKLER HEAD
CENTERED IN CEILING TILE
NEW HEAD INSTALLATION DETAIL
NO SCALE
PHILLIPS CONCRETE
FASTENER OR EQUAL
...................�
_ ..... . _...... ..... _ _._...... _..
L.
r / 00 MINIMUM DISTANCE
..... .... ...... ..... .
_ ........... ........._ ... ................. .............. .........
=
- _......, ..../
CONCRETE
= CONSTRUCTION
Q
ALL THREAD
ROD -
o_
SWIVEL RING
SWIVEL RING
TAKE-OUT U
PIPE
HANGER
DETAIL - DROP -IN ANCHOR
N.T.S.
PIPE
ROD
TYPE OF
MIN "C"
MAX "D"
SIZE
SIZE
FASTENER
DIM.
DIM.
3/4
3/4�
3/$ r
1-3i8' x l 11/32'
DROP -IN ANCHOR
114 �
13/16"
II/�
2"
2 +
r
1 3/16'
2 3/8'
21/a"
11/ "
1- I/2' x 1 15/32"
1 1/1(0"
2 3/41
31
1 3/ "
4
3 1/4 "
2
DROP- IN ANCHOR
31/2'
2"
3 �/$"
4"
5/6
1-6/a' x 2 15/32'
DROP- IN ANCHOR
2 1/4 "
3 8
2 3/4'
4 3/4'
"
3/4'
1-3/4'x3 1/4' DROP -IN ANCH.
3 5/16"
5 1/2'
'
N/A
N/A
N/A
N/A
FIRE
SCALE: 1/4' 21'_0'
SUITE 120' FIRST FLOOR, PLAZA 57
7300 S.W�OUTH
b7TH COURT
CITY OF MIAMI
SOUTH MIQ MI, FLORIDA 33143
� \' / \' \ x/ I
07EGTION OFFIG
EXISTING FIRE
SPRINKLER LAYOUT.
SEE SHELL PERMIT
SET
AN - SUITE 120
R BUILDING
PERAII'l T'It G PURPOSES 13Y
INMALI-DADS CO(JN'1"Y F111,H
DEPAR'!'mRNC
FIRE PAOfECTION ,AN4/Oil FIRE ALARM
WORKING PLAINS SMALL. 111E 3USPAI fi) FOIL
APPHOVAL TO MIAMI•OAOA. FIRE 0EPAnTmE)Ir
OF -FORE, 'IFINE PAO)IE(:tlOMFIRE ALARM
11UY INSTALI.EO oil Hell,00ELF.O.
PLAN KEYED NOTES
1D CONNECT NEW SEMIRECESSED SPRINKLER HEAD TO
EXISTING FIRE PROTECTION WATER PIPE SYSTEM.
FIRE SPRINKLER EGEND:
2'
_ EXIST. FIRES S INKL LRMAIN A5 PER
REFERENCr----�
NEW FIRE SPRINKLER BRANCH
ON DENOTES NEW PENDANT SPRINKLER HEAD
LOCATE IN CENTER OF TILE
DENOTES RELOCATED PENDANT HEAD LOCATE
R AT CENTER OF TILE. ROVIDE I' DROP MIN.
0 DENOTES EXIST. PENDANT t0 REMAIN
TOTAL NO. OF HEADS
NEW
RELOCATED
REMAIN
REMOVr [)
PENDANTS
,.
,.
,.
,•
TOTAL NO. OF HEADS ,•
AVERAGE COVERAGE PROVIDED 11 Sa Ft. PER HEAD
ORIGINAL DESIGN CRITERIA
I. HYDRAULIC DESIGN CRITERIA:
C. OFFICES t GENERAL CORRIDOR t TOILET AREAS
NFPA HAZARD CLASSIFICATION---- OH - 2
DESIGN AREA OF APPLICATION---- 1,500 SF.
DESIGN DENSITY ---------------- 0.10 GPM/SF
DESIGN COVERAGE PER HEAD---- 130 SF. MAXIMUM.
MAXIMUM HEAD SPACING --------- 15 Ft.
FIRE SPRINKLER LEGEND
OFFICES AREAS
COMMON AREAS, OFFICES, ETC,
UPRIGHT OR PENDANT SPRINKLER HEAD.
CENTRAL MODEL TY-B (QUICK RESPONSE)
I(o5°F - K--5.(o 1/2' ORIFICE,
PROVIDE CLEVIS TYPE HANGER APPROVED BY
UPRIGHT OR PENDANT SPRINKLER HEAD.
FIME SPRINKLER CONSTRUCTION NOTES
CONTRACTOR SHALL NOTIFY MOAD 1 WORKING DAYS BEFORE
A SHUT DOWN WILL OCCUR FOR INSTALLATION OF NEW HEADS OR LINES.
CHANDLER AND ASSOCIATES
ARClirrECTURK PA
AA 0003M
JASON R CHANDLER. ALA. AR NO. MW
SOUTH MIAW FLORIDA 33143
TEL M 669-7992
FAX (M 669-7993
YAW.CHANDLERARCBTrECTURECOM
corkmaHT 3m
GENERAL:
A) THE FIRE SPRINKLER SYSTEM FOR 714I3 PROJECT 15 TO 8E FRCCl:RED ON A DE81GN BUILD
BASIS WITH THE SPRINKLER CONTRACTOR FULLY RESPONSIBLE FOR THE DETAILED DE81GN OF
AND $HALL CONFORM TO LOCAL CODE, DEVELOPER INSURANCE UNDERWRITER AND ALL PERTINENT
STANDARDS OF NFPA.
B) ORDER NEW WATER FLOW TEST FF Fl)M '114E FIRE DEPARTMENT TV USE AS BA615 FOR DESIGN
C) COORDINATE WITH ALL OTHER TRAPF-a REFURE PREr'ARfiTION OF rGE••316N DOCUMENTS.
FOR SUBMITTAL AND PERMIT PURPOSES.
U THE PROPOSED BUILDING SHALL BE FULLY SPRINKLERED IN COMPLIANCE
WITH THE FOLLOWING:
a. LOCAL AUTHORITY HAVING JURISDICTION.
b. NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS
c. NFPA 14 - NOT USED
d. NFPA 20 - NOT USED
e. NFPA 24 - PRIVATE FIRE SERVICE MAINS
F. NFPA 101- LIFE SAFETY CODE
g. THE FLORIDA BUILDING CODE - 2000
h THE FLORIDA FIRE PREVENTION CODE
I. ALL OTHER APPLICABLE CODES AND STANDARDS.
2) PROVIDE A WET PIPE SPRINKLER SYSTEM, ALTERNATIVELY FED FROM
THE FIRE 6TANDFIFE5 AND PUMP SYSTEM.
3) PREPARE FULLY DIMENSIONED AND COORDINATED SPRINKLER AND FIRE
STANDPIPE SHOP DRAWINGS IN ACCORDANCE WITH THE REQUIREMENT OF
THIS BUILDING AND ALL APPLICABLE CODES AND STANDARDS. SHOP
DRAWINGS SHALL BE PREPARED BY A LICENSED SPRINKLER CONTRACTOR
AND SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
ENGINEER, TOGETHER WITH THE HYDRAULIC CALCULATIONS.
4) SPRINKLER SYSTEM LAYOUT, AND HYDRAULIC CALCULATIONS
SHALL BE PREPARED IN ACCORDANCE WITH THE FOLLOWING NFPA 13
HAZARD CLASSIFICATIONS:
a. CORRIDORS t TOILET AREAS - ORDINARY HAZARD GROUP 2.11-4.1.2)
b. OFFICE SPACES - LIGHT HAZARD (1-4.1.2)
c. LOBBY AREAS - ORDINARY HAZARD (1-13.1)
d) ALL EXPOSED PIPING SHALL BE SCH. 40 -GALVANIZED STEELSTEEL.
e) PROVIDE CORROSION RESISTANCE TREATMENT TO SPRINKLER HEADS
EXPOSED TO WEATHER ALL NON AIR CONDITIONED AREAS ARE t0 BE
CONSIDERED EXPOSED t0 WEATHER
5) PIPING SHALL BE IN ACCORDANCE WITH SECTION 2-3, NFPA 13, 1999
EDITION. AND AS FOLLOWS.
a) GENERAL DISTRIBUTION -SCH. 40 -BLACK STEEL.
W/THREADED JOINTS.
b) UNDERGROUND SERVICE PIPE FROM MAIN t0 RI6ER-4' D.I.P.
c) RISER - SCH. 10 - 4' BLACK STEEL W/ VICTAULIC FITTINGS.
GENERAL DISTRIBUTION -
d) FIRE SPRINKLER CONTROL VALVES TO BE OF THE PRESSURE
RESTRICTIVE TYPE WHERE PRESSURE EXCEEDS 115 P.S.I.G.
(o) INSTALL HANGERS IN ACCORDANCE WITH CHAPTER (o, NFPA 13, 1999
EDITION. HANGER TO BE MANUFATURED BY ERICO CO.
1) PROTECT ELEVATORS IN ACCORDANCE WITH STATE FIRE MAR6HALL'5
UNIFORM SAFETY RULES, CHAPTER 4A-41. ELECTRICAL AND ELEVATOR
CONTRACTORS MUST COMPLY WITH THESE REQUIREMENTS.
8) PROVIDE SPARE SPRINKLER CABINET IN ACCORD WITH NFPA 13
PROVIDE A MINIMUM OF (o SPARE HEADS OF EACH TYPE, SIZE AND
pR��ATINyyG USED. (NOT LESS THAN 24 TOTAL)
LOCATE CABINETLIN APPPRROVED LONCATIONN THE CABINET.
9) INSTALL FIRE SPRINKLER HEADS IN
THE CENTER OF THE CEILING TILES.
10) THE INSTALLATION OF H.VAC. AND PLUMBING HAS PRECEDENCE OVER
FIRE PROTECTION. THE FIRE SPRINKLER CONTRACTOR SHALL
COORDINATE WITH THE MECHANICAL CONTRACTOR TO ALLOW ALL
DUCTWORK TO BE INSTALLED AS HIGH AS POSSIBLE.
11) COORDINATE WITH ELECTRICAL CONTRACTOR FOR ANY CONFLICTS OF
SPRINKLER HEADS AND LIGHT FIXTURES, SEE ELECTRICAL PLANS
GROUND LEVEL
UILDING PLAN THESE PLANS ARE FOR BUILDING DEPARTMENT REVIEW. THEY ARE
NOT TO BE CONSTRUED AS FINAL CONSTRUCTION DOCUMENTS
BUNTIL ALL BUILDING DEPARTMENT APPROVALS ARE OBTAINED AND
COMMENTS INTO THESE DWGS. DUE TO TH
SCALE: Y=30'-O' VARIA NS INrCORPORATED INTERPRETATIONS OF THE CODE THAT OCCUR EN
NO• DATE Fevom
DIFFERENT MUNICIPALITIES FINAL APPROVAL AND REVIEW IS NEEDED
TO ASSURE COMPLIANCE WITH THE APPLICABLE CODES AND
STANDARDS.
DRAWING TITLE'
NO. DATE FE'YISION
IRE PROTEC11ON
PARTIAL. OFFICE PLAN
�SUITE 120
' SCALE:
' DATE- 50% C.D 12-08-05
j PROJECT NO 2004.23
DRAWING NO
' FPANI
�-1
i 1
I
I