Loading...
06-1147-010FIRIE- -ALARLU OPERATION - UPON THE ACTIVATION OF AN AUTOMATIC DEVICE (DUCT DETECTOR, SMOKE _-DETE=R�OR MX-4UAL DUKE = TtlE.FIk?,-- ALARN. SYSTEM AHALL TRANSMIT THE ALARM VIA CENTRAL STATION MONITORING. -ALL STROBES WILL FLASH UNTIL RESET. -ALL HORNS WILL SOUND UNTIL RESET. -ALL AHU'S SHALL SHUT -DOWN UNTIL RESET. NOTE& 1 -CONDUCTOR TYPES: THHN-STRANDED. 2 -CONDUCTOR SIZES: #14 MINIM. 3 -RACEWAY AND SIZE: EMT 1/2" MINIM. 4 -ALL COMPONENTS SHALL BE UL LISTED FOR FIRE SERVICE.. 5 -POWER LIMITED 24 VOLTS. 6 -SYSTEM SHALL CONFORM TO ALL REQUIREMENTS OF NFPA, AND STATE AND LOCAL CODES 7 -ALL PULL STATIONS WILL BE MOUNTED AT 48" A.F.F. TO THE TOP OF THE DEVICE. 8 -ALL WALL MOUNTED SIGNAL DEVICES WILL BE MOUNTED AT 80" A.F.F. MEASURED FROM THE BOTOM OF THE LIGHT SOURCE. 9 -THE COMPLETE INSTALLATION SHALL CONFORM TO THE APPLICABLE SECTIONS OF NFPA-72, LOCAL CODE REQUIREMENTS NATIONAL ELECTRICAL CODE. ELECTRICAL LEGEND 120V, DUPLEX RECEPTACLE �GI 120V, ISOLATED GROUND DUPLEX RECEPTACLE G FI 120V, GROUND FAULT, DUPLEX RECEPTACLE 220 220V, DEDICATED RECEPTACLE 120V, ABOVE COUNTER, DUPLEX RECEPTACLE ® 120V, FLOOR DUPLEX RECEPTACLE EXHAUST FAN I' � I TELEVISION OUTLET Li-1 TOGGLE SWITCH L 3 WAY TOGGLE SWITCH O CEILING OUTLET PO WALL MOUNTED OUTLET WALL MOUNTED JUNCTION BOX 1'X4' PENDENT FLUORESCENT FIXTURE ® 1'X4' PENDENT FLUORESCENT FIXTURE W/2 LAMPS ON BATTERY BACK UP O CEILING MOUNTED JUNCTION BOX 4 DISCONNECT SWITCH ® ELECTRICAL PANEL —� TELEPHONE COMPUTER NETWORK OUTLET DOOR OPENER �] EXIT SIGN ABOVE DOOR W/ BATTERY BACK UP C7 CONNECTED AHEAD OF SWITCH l�J COMBINATION HORNISTROBE LIGHT - FIRE ALARM s� STROBE LIGHT - FIRE ALARM FACP FIRE ALARM PANEL p�p DUCT DETECTOR - FIRE ALARM FA_N_N_j FIRE ALARM ANNUNCIATOR GENERAL NOTESi 1. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CODES AND STANDARDS. 2. THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING THE SITE PRIOR TO COMMENCING/BIDDING WORK. 3. THE CONTRACTOR SHALL SATISFACTORILY REPAIR/REPLACE EQUIPMENT OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS. 4. APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER. 5. ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/NOTED OTHERWISE. 6. WIRE SIZE SHALL BE #12 THHN/THWN STRANDED MINIMUM UNLESS OTHERWISE NOTED ON PLANS, 7. ALL CONDUCTORS SHALL BE COPPER. 8. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250-95 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED. 9. ALL MATERIAL MUST BE U.L. APPROVED. 10. ALL BRANCH CIRCUITS MUST BE PROPERLY PHASE BALANCED. 11. CONTRACTOR SHALL SEAL ALL FLOOR OPENINGS WITH AFIRE SEAL SIMILAR TO 3M FIRE DAM 150. 12. ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS. 13. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED. NOTE: ELECTRICAL CONTRACTOR SHALL VERIFY AT FIELD THE 14. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS. 15. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. 16. THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM. 17. ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED. 18. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES. 19. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD. 20. ALL WORK SHALL BE DONE IN A NEAT WORKMANLIKE MANNER. 21. BRANCH CIRCUIT BREAKERS SHALL BE OF THE BOLT -ON TYPE. PLUG-IN CIRCUIT BREAKERS WILL NOT BE ACCEPTED. 22. ALL ROOF PENETRATIONS TO BE PROVIDED WITH PITCH PANS. 23. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZE ARE BASED ON A/C EQUIPMENT SPECIFIED ON CONTRACT DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. 24. CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL CIRCUITS WIRING AND RACEWAYS, AS SHOWN ON THE AIR CONDITIONING DRAWINGS OR SPECIFICATIONS. IF AIR CONDITIONING DRAWINGS REFER TO MANUFACTURER'S WIRING DIAGRAMS. INFORMATION PROVIDED ON THESE PLANS AND RETURN ANY DISCREPANCIES TO THE THE ENGINEER BEFORE COMMENCEMENT OF WORK. EXISTING 3P 1200A, 120/208V, 3P, 4W, E.C.B NEW 4#3/0 & 1#6(G) THWN CU IN NEW 2" EMT. i EXISTING METER MAIN ` EXISTING METER TO BE CENTER 41 OF '`�,r ',' USED FOR NEW TENANT SPACE 4 -�'�-�`•--- EXISTING EXISTING EXISTING 3P, 200 AMPS, ELECT ROOM CORRIDOR M.C.B 42KA.I.C. '9 - FOR NEW TENANT SPACE. I ` EXISTING 4 SETS OF 4#400 MCM CU IN 3" CONDUIT EACH SET EXUTIl4G CIKXM Sn TO FP&L TRANSFORMER Iy v ELECTRICAL RISER DIAGRAM NTS NEW I NEW A TENANT PNL SPACE ROOF LEVEL 5 LEVEL 4 LEVEL 3 LEVEL 2 GROUND LEVEL 1 TYPE: LOAD CENTER PANEL " A " VOLTS: 120/208 V, 30, 4W MTG: SURF BUS: 200 A MAIN: 313-100 AMPS (E)aSITING) LOAD: LOAD COND. WIRE TRIP POLES DESCRIPTION KT. KT. DESCRIPTION POLESF60 WIRE OND. LOAD 1200 1/2 12 20 i LIGHTING 1 2 FCU-1 2 4 1 1/4 10,800 1200 1 2 12 20 1 LIGHTING 3 4 1200 1/2 12 20 1 LIGHTING 5 6 CU-1 2 60 6 1 7,200 1200 1/2 12 20 1 LIGHTING 7 8 1200 1/2 12 20 1 LIGHTING 9 10 RECEPTACLES 1 20 12 1/2 1080 1080 1/2 12 20 1 RECEPTACLES 11 12 RECEPTACLES 1 20 12 1/2 1080 1080 1/2 12 20 1 RECEPTACLES 13 14 RECEPTACLES 1 20 12 1/2 1080 1080 1/2 12 20 1 RECEPTACLES 15 16 SPACE SPACE 17 18 19 20 21 22 23 24 25 126 27 128 29 1.30 31 132 33 134 35 36 37 38 39 40 9,240 41 42 21.240 TOTAL CONNECTED LOAD: 30.5 KVA KITCHEN EQUIPMENT LOAD: 84.6 AMPS ROOF LEVEL 5 LEVEL 4 LEVEL 3 EXISTING FLOOR EXISTING 2 SETS TEL BOARD LEVEL 2 OF (2) 4" COND NEW VC EXISTING MAIN TEL BOARD ---■--` NEW L_ _J TENANT SPACE GROUND LEVEL 1 'L EXISTING GROUND —O SEE FLOOR PLAN FOR EXACT EXISTING 2-3" LOCATION AND QUANTITIES — CONDUITS TO TEL CO. TEL RISER DIAGRAM NTS -AL !l f •y�!�J� ALARM i'1rL `i�s �,"i a�i..� y 4• !--`y��_'t � •f .���'/� A,J y i.S J-- ir.rr p , .. - « �•iJi.,°:�:� iam shah to 114iami- T .-' e � is �t.'.-. • � } .� l.,Dote l L only! NOTE: CONTRACTOR TO SUBMIT A COMPLETE SHOP DRAWING IN ORDER TO PULL A PERMIT SEE FLOOR PLAN FOR EXACT LOCATION AND QUANTUTIES EXISTING FIRE ALARM PANEL (BATTERY BACKUP) L NEW FACP TENANT SPACE EXISTING DIAL TONE —��'v (1ST FLOOR FAP ROOM) FIRE ALARM RISER DIAGRAM N.T.S. O� J ' Z > w m 4 w w Q w w > > m U) CO m ❑ Ci H Z z 2 z w Q n O 0r w d U ❑ CO m d� C6 zo 0 0 ;y ' Cn w ,L "jo z �0 LU w Z z . � Uj z J z �'� • M w� M a (L � t z O4p ILM UP li J �• eta C0 0 6 A D v O� Ww w ..a� ti Q z v 0 a Q � 's N LIC. AA 26000897 _W4,a ROOFwa Q M LEVEL 5 Raw M Wo W ZZ a U 0 LEVEL 4 U. Z3Z Q � � LEVEL'3' ` p •!t>..,s. R.i a a�. - z LEVEL 2 0 a w = Iaa. w a man °'- 00 f ` Nf z Q refit,. D' Q :��- , ,�-i..h � i r mks• GROUND LEfft7f, Vd, _ -� - s1or8Se' ifUeti�e e• w �vs• o: Date 4. w TF Consulting Engineers Inc. MECHANICAL - PLUMBING - ELECTRICAL 9520 S.W. 40 St. Sult9 # 207 - MIAMI FLORIDA 33165 OFFICE (305) 225-8377 - FAX 305-225-8378 SHEET NO.: E-2