06-1147-007GENERAL NOTES 1. GENERAL A. ALL WORK SHALL be done in accordance with the Florida Building Code and with all applicable regulations. B. DRAWINGS: Refer to all drawings for coordination of the HVAC work. C. ARRANGE AND PAY for all permits licenses, inspections and tests. Obtain the required certificates and present to owner. D. GUARANTEE: The completed installation shall be fully guaranteed against defective materials and/or improper workmanship for a minimum of one year for material and labor. Compressors shall be guaranteed for a period of five years. 2. SHOP DRAWINGS: Contractors shall submit for approval, within 30 days after signing contract, a minimum of five copies of fully descriptive literature, including but not limited to: air conditioning units, air outlets, controls and fans. No work shall proceed without approval of these submittals. 3. DESIGN PARAMETERS: A. Outdoor design temperature (Summer): 917 DB and 797 WB B. Outdoor design temperature (Winter): 457 C. Indoor design temperature (Summer): 78T DB D. Indoor design temperature (Winter): 727 DB 4. ALL THERMOSTATS shall have heating mode maximum setting of 757, and cooling mode minimum setting of 707. The thermostat shall be arranged to prevent the simultaneous operation of heating and cooling. 5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract. 6. EOUIPMENT SPECIFIED BY manufacturer's number shall include all accessories, controls, etc., listed in the catalog as standard with the equipment. Optional or additional accessories shall be furnished as specified. 7. MATERIALS: A. Ductwork: a. All supply, return and exhaust air ductwork shall be of galvanized sheet metal construction, fabricated and installed as per lolest edition of SMAGNA "low pressure duct manual" Insulate supply air ductwork in concealed spaces with 1 1/2 in. thick fiberglass blanket insulation with foil vapor barrier (R-6.0 MIN.) b. All exposed round supply air ducts shall be galvanized sheet metal factory fabricated spiral type as manufactured by United Sheet Metal or approved equal. Ductwork shall be fabricated and installed as per lates edition of SMACNA 'Low Pressure Duct Manual'. c. All duct dimensions are clear inside dimensions. d. Flexible insulated ductwork with 1-1/2" thick fiberglass insulation with FRK vapor barrier R-6.0 Min. 8. TEST AND BALANCE: Contractor shall test and balance all ventilation and air conditioning systems. Submit four (4) copies of Test and Balance Report to Owner for approval. 9. CONTROLS: Roof top Air Conditioning System shall be started and stopped thru individual thermostats located in corridor. Individual thermostat shall start/stop supply fans and activate cooling/heating systems as selected. 10. COORDINATE all required roof openings with general contractor. 11. PROVIDE U.L. LISTED Volume damper where indicated on drawings. Provide duct access doors to access damper blades. Access doors shall be insulated when located in supply ducts. 12. PROVIDE CEILING/WALL ACCESS DOORS where indicated on drawings and where required to access mechanical equipment. Doors shall be recessed type. fire rated if in fire rated wall or ceiling. As manufactured by Karp model RDW and KATR. 13. CONTRACTOR: to fire protect and seal all openings and pipe penetrations thru fire rated walls and ceiling. Material and methods of fire rating shall be approved by City Code Product Control. SPLIT A/C UNIT SCHEDULE UNIT DESIGNATION FCU-1 AREA SERVED OFFICE LOCATION CEILING SPACE OPERATING WEIGHT 195 DESIGN MANUFACTURER RHEEM MODEL NO. RBHK25J (HORIZONTAL) SEER, MIN, 13 TOTAL AIR, CFM 2000 VENT AIR, CFM --- Z " EXT. STATIC PRESS., INCHES OF H2O 0.5 FAN MOTOR H.P. (NON -OVERLOAD) 3/4 ELECTRICAL SERVICE AVAILABLE 208/1/60 MIN. CIRC. AMPACITY 59.6 MAX. CIRC. PROT. 60 FACE VELOCITY, FPM --- z o DESIGN AIR ACROSS COIL, CFM 2000 0 Z GRAND TOTAL CAPACITY, BTUH 55.5 Z a TOTAL SENSIBLE CAPACITY, BTUH 37.6 U- 0 ENTERING AIR TEMP. °F DB/WB 80/67 COIL MODEL NO. RCGJ6041 FILTER TYPE & THICKNESS CLEANABLE 1" QUANTITY AND SIZE 1-23.25X21 a FACE VELOCITY FPM. MAX. --- HEAT/REHEAT COIL TYPE ELECTRIC o: ELECTRICAL SERVICE AVAILABLE 208/1/60 Q = AUXILIARY ELECTRIC HEAT, KW 10 STAGES AND KW/STAGE 1 / 10 KW UNIT DESIGNATION CU-1 TYPE OF FAN PROPELLER z NO. OF FANS AND AMPS 1 - 1.2 AMBIENT AIR TEMP., °DB 95 Z z NO. OF COMPRESSORS / TYPE 1 / SCROLL w 0 COMPRESSORS F.L.A. / L.R.A. 25.3/141.0 0 CAPACITY REDUCTION 0-100% a ui MIN. CIRC. AMPACITY 33 0 0 0 MAX. CIRC. PROT. 50 a ELECTRICAL SERVICE AVAILABLE 208/1/60 OPERATING WEIGHT,LBS. 230 DESIGN MANUFACTURER RHEEM MODEL NO. RAND060J REFRIGERANT LINE SUCTION & LIQUID 1 1/8" — 1/2" NOTE: 1) VERIFY LINE SIZE AS PER MANUFACTURER RECOMENDATIONS 2) PROGRAMMABLE THERMOSTAT 3) FAN COIL UNITS SHALL BE PROVIDED WITH FACTORY INSTALLED CIRCUIT BREAKER. 4) HORIZONTAL FAN COIL UNIT. VENTILATION FAN SCHEDULE UNIT DESIGNATION EF-1 AREA SERVED TOILET'S UNIT OPERATING WEIGHT LBS. 13 LOCATION CEILING FAN TYPE IN—UNE BLOWER TOTAL AIR CFM 80 DRIVE TYPE DIRECT FAN WHEEL TYPE CENTRIFUGAL FAN TIP SPEED RPM MAX --- FAN SPEED, RPM 900 TOTAL STATIC PRESSURE, IN. OF H2O 0.100 FAN MOTOR HP NON OVERLOAD 64 WATTS Z < FAN MOTOR STARTER TYPE WALL SWITCH STARTER FURNISHED BY MC ELECTRICAL SERVICE AVAILABLE 115-1-60 MASONARY OPENING REQUIRED NO CONNECTED TO EMERGENCY POWER NO DESIGN MANUFACTURER GEMINI MODEL NUMBER GC-124 SERVICE -SWITCH YES SMOKE DETECTORS U.L. APPROVED NO FIRE DAMPER NO vn CONSTRUCTION ALUM/PLAST iR MULTTBLADE BACKDRAFT DAMPER YES BIRDSCREEN NO 1� SOLID STATE SPEED CONTROL NO a THERMOSTAT CONTROL NO FACTORY FABRICATED CURB NO FILTER AND FILTER FRAME NO MANUALLY AJUSTABLE PITCH BLADES NO HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR )( — FIRE DAMPER(S) — X SMOKE DAMPER(S) — X FIRE RATED ENCLOSURE -- X FIRE RATED ROOF/FLOOR ASSEMBLY — XCEILING FIRE STOPPING X — SMOKE CONTROL — )( AIR DISTRIBUTION SCHEDULE SYMBOL USE TYPE ACCESORIES DESIGN MANUFACTURER & MODEL Mo. UA SUPPLY AIR ROUND CEILING DIFFUSER O.B.D. TITUS TMR—AA �B SUPPLY AIR CEILING DIFFUSER O.B.D. TITUS 250—AA OC RETURN AIR CEILING GRILLE — — — TITUS 4FL NOTE: 1. ALL AIR DISTRIBUTION DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION. 2. COORDINATE COLOR FINISH WITH ARCHITECT, WHITE BAKED ENAMEL STANDARD. 3. ARROWS INDICATE DIRECTION OF AIR DISTRIBUTION. AS PER FLORIDA OUTDOOR AIR CALCULATIONS BUILDING CODE 2001 TABLE 403.3 AREA DESIGNATION FLOOR AREA PERSONS/ 1000/FT2 TOTAL PERSONS CFM / PERSONS CFM / FT2 CFM REQUIRED CFM PROVIDED SYSTEM DESIGNATION RETAIL STORAGE 595 --- --- --- 0.15 90 90 SALES AREAS RETAIL 1050 --- --- --- 0.20 210 210 300 300 FCU-1 HVAC SYMBOL LEGEND Sao SMOKE DETECTOR UT THERMOSTAT CFM CUBIC FEET PER MINUTE RTU ROOF TOP UNIT AFF ABOVE FINISH FLOOR a w w 0 0 w w N m co co m H Z Z m w 0 0� w N 1 to 1 1 CJD LO 1 • . / w • 0 .. CC) F- Q C) LIC. AA :M: . ®� M r M M .a Wo Im C9 a y2* I cn 0 Z V h to � , •a= •gN Vf = 00 N z ary el ior`-i — .Cifuenti s . P--1 u� . sqnstum �a W��, 7' Consulting Engineers Inc. MECHANICAL - PLUMBING - ELECTRICAL 9520 S.W. 40 St. Suite # 207 - MIAMI FLORIDA 33165 OFFICE (305) 225-8377 - FAX 305-225-8378 SHEET NO.: AC-3