06-1147-007GENERAL NOTES
1. GENERAL
A. ALL WORK SHALL be done in accordance with the Florida
Building Code and with all applicable regulations.
B. DRAWINGS: Refer to all drawings for coordination of the HVAC work.
C. ARRANGE AND PAY for all permits licenses, inspections and tests.
Obtain the required certificates and present to owner.
D. GUARANTEE: The completed installation shall be fully guaranteed
against defective materials and/or improper workmanship for a
minimum of one year for material and labor. Compressors shall be
guaranteed for a period of five years.
2. SHOP DRAWINGS: Contractors shall submit for approval, within 30 days
after signing contract, a minimum of five copies of fully descriptive
literature, including but not limited to: air conditioning units, air outlets,
controls and fans. No work shall proceed without approval of these submittals.
3. DESIGN PARAMETERS:
A. Outdoor design temperature (Summer): 917 DB and 797 WB
B. Outdoor design temperature (Winter): 457
C. Indoor design temperature (Summer): 78T DB
D. Indoor design temperature (Winter): 727 DB
4. ALL THERMOSTATS shall have heating mode maximum setting of 757, and
cooling mode minimum setting of 707. The thermostat shall be arranged
to prevent the simultaneous operation of heating and cooling.
5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract.
6. EOUIPMENT SPECIFIED BY manufacturer's number shall include all
accessories, controls, etc., listed in the catalog as standard with the
equipment. Optional or additional accessories shall be furnished as
specified.
7. MATERIALS:
A. Ductwork:
a. All supply, return and exhaust air ductwork shall be of
galvanized sheet metal construction, fabricated and installed
as per lolest edition of SMAGNA "low pressure duct manual"
Insulate supply air ductwork in concealed spaces with 1 1/2 in.
thick fiberglass blanket insulation with foil vapor barrier (R-6.0 MIN.)
b. All exposed round supply air ducts shall be galvanized sheet metal
factory fabricated spiral type as manufactured by United Sheet Metal
or approved equal. Ductwork shall be fabricated and installed as
per lates edition of SMACNA 'Low Pressure Duct Manual'.
c. All duct dimensions are clear inside dimensions.
d. Flexible insulated ductwork with 1-1/2" thick fiberglass
insulation with FRK vapor barrier R-6.0 Min.
8. TEST AND BALANCE: Contractor shall test and balance all ventilation
and air conditioning systems. Submit four (4) copies of Test and Balance
Report to Owner for approval.
9. CONTROLS: Roof top Air Conditioning System shall be started and
stopped thru individual thermostats located in corridor. Individual
thermostat shall start/stop supply fans and activate cooling/heating
systems as selected.
10. COORDINATE all required roof openings with general contractor.
11. PROVIDE U.L. LISTED Volume damper where indicated on
drawings. Provide duct access doors to access damper blades. Access
doors shall be insulated when located in supply ducts.
12. PROVIDE CEILING/WALL ACCESS DOORS where indicated on drawings and where
required to access mechanical equipment. Doors shall be recessed type.
fire rated if in fire rated wall or ceiling. As manufactured by Karp
model RDW and KATR.
13. CONTRACTOR: to fire protect and seal all openings and pipe penetrations
thru fire rated walls and ceiling. Material and methods of fire rating
shall be approved by City Code Product Control.
SPLIT A/C UNIT SCHEDULE
UNIT DESIGNATION
FCU-1
AREA SERVED
OFFICE
LOCATION
CEILING SPACE
OPERATING WEIGHT
195
DESIGN MANUFACTURER
RHEEM
MODEL NO.
RBHK25J (HORIZONTAL)
SEER, MIN,
13
TOTAL AIR, CFM
2000
VENT AIR, CFM
---
Z
"
EXT. STATIC PRESS., INCHES OF H2O
0.5
FAN MOTOR H.P. (NON -OVERLOAD)
3/4
ELECTRICAL SERVICE AVAILABLE
208/1/60
MIN. CIRC. AMPACITY
59.6
MAX. CIRC. PROT.
60
FACE VELOCITY, FPM
---
z
o
DESIGN AIR ACROSS COIL, CFM
2000
0
Z
GRAND TOTAL CAPACITY, BTUH
55.5
Z
a
TOTAL SENSIBLE CAPACITY, BTUH
37.6
U-
0
ENTERING AIR TEMP. °F DB/WB
80/67
COIL MODEL NO.
RCGJ6041
FILTER TYPE & THICKNESS
CLEANABLE 1"
QUANTITY AND SIZE
1-23.25X21
a
FACE VELOCITY FPM. MAX.
---
HEAT/REHEAT COIL TYPE
ELECTRIC
o:
ELECTRICAL SERVICE AVAILABLE
208/1/60
Q
=
AUXILIARY ELECTRIC HEAT, KW
10
STAGES AND KW/STAGE
1 / 10 KW
UNIT DESIGNATION
CU-1
TYPE OF FAN
PROPELLER
z
NO. OF FANS AND AMPS
1 - 1.2
AMBIENT AIR TEMP., °DB
95
Z
z
NO. OF COMPRESSORS / TYPE
1 / SCROLL
w
0
COMPRESSORS F.L.A. / L.R.A.
25.3/141.0
0
CAPACITY REDUCTION
0-100%
a
ui
MIN. CIRC. AMPACITY
33
0
0
0
MAX. CIRC. PROT.
50
a
ELECTRICAL SERVICE AVAILABLE
208/1/60
OPERATING WEIGHT,LBS.
230
DESIGN MANUFACTURER
RHEEM
MODEL NO.
RAND060J
REFRIGERANT LINE SUCTION & LIQUID
1 1/8" — 1/2"
NOTE: 1) VERIFY LINE SIZE AS PER MANUFACTURER RECOMENDATIONS
2) PROGRAMMABLE THERMOSTAT
3) FAN COIL UNITS SHALL BE PROVIDED WITH FACTORY
INSTALLED CIRCUIT BREAKER.
4) HORIZONTAL FAN COIL UNIT.
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF-1
AREA SERVED
TOILET'S UNIT
OPERATING WEIGHT LBS.
13
LOCATION
CEILING
FAN TYPE
IN—UNE BLOWER
TOTAL AIR CFM
80
DRIVE TYPE
DIRECT
FAN WHEEL TYPE
CENTRIFUGAL
FAN TIP SPEED RPM MAX
---
FAN SPEED, RPM
900
TOTAL STATIC PRESSURE, IN. OF H2O
0.100
FAN MOTOR HP NON OVERLOAD
64 WATTS
Z
<
FAN MOTOR STARTER TYPE
WALL SWITCH
STARTER FURNISHED BY
MC
ELECTRICAL SERVICE AVAILABLE
115-1-60
MASONARY OPENING REQUIRED
NO
CONNECTED TO EMERGENCY POWER
NO
DESIGN MANUFACTURER
GEMINI
MODEL NUMBER
GC-124
SERVICE -SWITCH
YES
SMOKE DETECTORS U.L. APPROVED
NO
FIRE DAMPER
NO
vn
CONSTRUCTION
ALUM/PLAST
iR
MULTTBLADE BACKDRAFT DAMPER
YES
BIRDSCREEN
NO
1�
SOLID STATE SPEED CONTROL
NO
a
THERMOSTAT CONTROL
NO
FACTORY FABRICATED CURB
NO
FILTER AND FILTER FRAME
NO
MANUALLY AJUSTABLE PITCH BLADES
NO
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
)(
—
FIRE DAMPER(S)
—
X
SMOKE DAMPER(S)
—
X
FIRE RATED ENCLOSURE
--
X
FIRE RATED ROOF/FLOOR
ASSEMBLY
—
XCEILING
FIRE STOPPING
X
—
SMOKE CONTROL
—
)(
AIR DISTRIBUTION SCHEDULE
SYMBOL
USE
TYPE
ACCESORIES
DESIGN MANUFACTURER & MODEL Mo.
UA
SUPPLY AIR
ROUND CEILING DIFFUSER
O.B.D.
TITUS TMR—AA
�B
SUPPLY AIR
CEILING DIFFUSER
O.B.D.
TITUS 250—AA
OC
RETURN AIR
CEILING GRILLE
— — —
TITUS 4FL
NOTE: 1. ALL AIR DISTRIBUTION DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION.
2. COORDINATE COLOR FINISH WITH ARCHITECT, WHITE BAKED ENAMEL STANDARD.
3. ARROWS INDICATE DIRECTION OF AIR DISTRIBUTION.
AS PER FLORIDA
OUTDOOR AIR CALCULATIONS BUILDING CODE 2001
TABLE 403.3
AREA
DESIGNATION
FLOOR
AREA
PERSONS/
1000/FT2
TOTAL
PERSONS
CFM /
PERSONS
CFM /
FT2
CFM
REQUIRED
CFM
PROVIDED
SYSTEM
DESIGNATION
RETAIL STORAGE
595
---
---
---
0.15
90
90
SALES AREAS
RETAIL
1050
---
---
---
0.20
210
210
300
300
FCU-1
HVAC
SYMBOL LEGEND
Sao
SMOKE DETECTOR
UT
THERMOSTAT
CFM
CUBIC FEET PER MINUTE
RTU
ROOF TOP UNIT
AFF
ABOVE FINISH FLOOR
a
w
w
0
0
w
w
N
m
co
co
m
H
Z
Z
m
w
0
0�
w
N
1
to
1
1
CJD
LO
1
•
.
/
w
•
0
..
CC)
F-
Q
C)
LIC. AA :M:
.
®� M
r M
M
.a
Wo
Im C9
a
y2*
I
cn
0
Z
V
h
to
�
,
•a=
•gN
Vf =
00
N
z
ary
el ior`-i — .Cifuenti s .
P--1 u� .
sqnstum
�a W��,
7' Consulting Engineers Inc.
MECHANICAL - PLUMBING - ELECTRICAL
9520 S.W. 40 St. Suite # 207 - MIAMI FLORIDA 33165
OFFICE (305) 225-8377 - FAX 305-225-8378
SHEET NO.:
AC-3