02-930-165.....................................................................................................................- ........................................................................... ................................................_................................................---............................................................. 1'E_C_ W/PULLWIRE TO ELECTRICALIALi�OM (TYPICAL) ROOF I i NORTH ELECTRICAL ROOM I I 4'xa'x3/4" I I SOUTH ELECTRICAL ROOM , T.TB. I I I 12' x 12' x 4' PULLBOX (TYPICAL) SEE FLOOR PLAN FOR NUMBER OF BOXEa REQUIRED At ELEVATOR COMTROLLER I qp I I 2-2' EPVC I I I 2-2' EPVC i I I I , 1=11"TH LEVEL NORTH ELECTRICAL ROOM SOUTH ELECTRICAL ROOM r ,G I r t t I 4'xa'x3/4' I T.T.B. I t I 4'xa'x3/4' T.TB. I BEE PNL SCHEDULE FOR CKT. NIM55R FOURTH LEVEL au TER CALCLXATKM RETAIL SPACES 7,806 SO. FT A 12 W./SO. Fr. 94 KW. RESTAURAUNT 57828 SO. FT % 20 W./SO. FT. 117 KW. FUTURE LOAD 150 KW. a-4' EPYC TOTAL LOAD 361 KW. •208/3 PHASE 1002 AMPS THIRD LEVEL GUTTER WILL BE SIZED AT 1200 AMPS W/ (3) 3-1/2ff C. EA. W/ 4 # 600 MCM G PAWING 1 6 Cu (G) l 6 CU (G) 10 BLOC. ACCESS P!JL (VERITY EXACT LOCATION) MAIN ELECTRICAL ROOM SECOND LEVE F.P.t L. TX. VAULT I � I 4 f 4'xa'x3/4' t T.TB. G I I G l AP C FIRST LEVEL * / L-4 34 "�.+ � -- ! O G.E.G. To GEC. = PARKING- TELEF HONE RISER DIAGRAM 2-4' E.PYC W/ PULLWIRE N.T.S. TO PROPERTY L NE TEL CamPOINT 0;= . (VERIFY EXACT LOCATION BEFORE COMMENCING WORK) ROOF