02-930-090CONCRETE DOUBLE TEE j aMINIMUM DISTANCE = 1" CONCRETE EXPANSION ALL THREAD ANCHOR DRILLED IN SLAB ROD i HANGER ROD. SIZE PER SPEC. SECTION 15050-3.03C STANDARD CLEVIS HANGER (MS SP-69.TYPE ) RO� LOCKING NUT a SwNSUFA? T UT :;4 TAKE-OUT , U PIPE SIZE AS I PIPE HANGER DET IL 3 NO Sri FP-9 PIPE ROD TYPE OF MIN "C" MAX "C' SIZE SIZE FASTENER DIM. DIM. 3/4 A 3/in I-V x 1 11/32' I/2 1 I 13/41 11/4 13/16" 1'/8' DROP- IN ANCHOR 11/21 15/l(0 2' 21 1 3/16" 2 3/81 2 1/2 " 1/2 x 1 15/32' 1 1 /16 1 2 3141 3• 1 3/4, 3 1/4 1 DROP- IN ANCHOR 31/2 Y 2' 3 Nt Y 41 5/61 I-V x 2 15/32' DROP- IN ANCHOR 2 1/4' .3. 146Y 5" 2 3/41 4 3/41 6' 3/4" 1-3i4'x3 1/4' DROP -IN ANCH. 3 5/16" C✓ I/Y" STEEL I —BEAM OR BAR JOIST TOP BEAM C—CLAMP WITH LOCK NUT ALL THREAD _ ROD - TOP OF BEAM o OR BAR JOIST TO CENTER LINE SWIVEL RING _ OF SIRE SWIVEL RING TAKE—OUT U ' PIPE HANGER DETAIL - TOP BEAM C-CLAMP N.T.S. PIPE ROD MIN "C' MAX "C" SIZE SIZE DIM. DIM, 3/4 3/8 Y It 5/i' 1 3/4 , 11/4 13/16° 17i8Y 1 12' Ib/16' 2' 2' 1 3/16" 2 3/8' 2 I/2 Y 1 T /1(01 2 3/4 1 31, 1 3/4 Y 3 1/4 Y 31/2' 2' 3 4' 2 1/4' 3" va' 5. I/21 I 2 3/41 4 3/41 6 " 6' I N/A N/A OWNER/DEVELOPER THE lgicpAltp- 3gAnD n COMPANY SUITE 400 4960 S.W. 72 AVENUE MIAMI, FLORIDA 33155 305.662.1421 it O, PLAZA 57 7300 S.W. 57 COURT . CITY OF SOUTH MIAMI SOUTH MIAMI, FLORIDA 33143 SUPPORT SLAB _ESS STEEL .VE BOX. BUTTERFLY VALVE WITH TAMPER SWITCH. w V) Of Z Of 0 NO SCALE STUDS WIELDED TO SLEEVE PROJECT SLEEVE 1" ABOVE SLAB INDICATING TYPE FLOOR CONTROL VALVE WITH SUPERVISORY SWITCH PRESSURE GAUGE AND GAUGE COCK. 1 r-WATERFLOW SWITCH SIGHT GLASS C� I /TESTSECTIONAL DRAIN VALVE VALVE TO DRAIN UNION W/CORROSION RESISTENT ORIFICE, GIVING FLOW EQUIVALENT TO THE SMALLEST SPRINKLER ORIFICE IN THE SYSTEM 4" FIRE SPRINKLER RISER N.F.P.A. 13-1996 FIG. A-4-15,4.2(b) INSPECTOR TEST ASSEMBLY N•T.S• FIRE SPRINKLER LEGEND --0-- 1/2' ROYAL FLUSH WHITE PENDANT HEAD ---33 TOTAL K-, 5161 --- T= 165' 0— 112' ORIFICE UPRIGHT SPRINKLER HEAD -BRONZE K= 5bl --- T- 165' ---0— 11/2' ORFICE PENDENT 5PRINKI_ER HEAD (200') 200 K� 5b7 --- t= 200' --0— 1/2' ORFICE PENDENT SPRINKLER HEAD CHROME RECESSED TYPE (155') �.-. 1/21 51DEWALL SPRINKLER HEAD CHROME RECESS (GBR) 0 112' ORIFICE UPRIGHT SPRINKLER HEAD (BRASS- 256') 286 I CONTROL VALVE WITH TAMPER SWITCH O FLOW SWITCH &4 FIRE DEPARTMENT VALVE IN STAIR - 21/2' (F.D.V.) .Mnyr 100 FEET HOSE ,AND REEL I" I S INKL NOTES: I. THE PROPOSED BUILDING SHALL BE FULLY SPRINKLERED IN COMPLIANCE WITH THE FOLLOWING: a. LOCAL AUTHORITY HAVING JURISDICTION. b. NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS a NFPA 20 - CENTRIFUGAL FIRE PUMPS d. NFPA 24 - PRIVATE FIRS= SERVICE MAINS e. NFPA 101- LIFE SAFETY CODE f. ALL OTHER APPLICABLE CODES ,AND STANDARDS. 2. PROVIDE A WET PIPE SPRINKLER SYSTEM, ALTERNATIVELY FED FROM THE FIRS STANDPIPES AND PUMP SYSTEM. 3. PREPARE FULLY DIMENSIONED AND COORDINATED SPRINKLER AND FIRE STANDPIPE SHOP DRAWINGS IN ACCORDANCE WITH THE REQUIREMENT OF THIS BUILDING AND ALL APPLICABLE CODES AND STANDARDS. SHOP DRAWINGS SHALL BE PREPARED BY A LICENSED SPRINKLER CONTRACTOR AND SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, TOGETHER WITH THE HYDRAULIC CALCULATIONS. 4. SPRINKLER SYSTEM SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL 15E PREPARED IN ACCORDANCE WITH THE CRITERIA SPECIFIED UNDER 'DESIGN CRITERIA' 5. INSTALL PIPING IN ACCORDANCE WITH SECTION 4-1, NFPA 13, 1994 EDITION, AND AS FOLLOWS: A- ALL PIPING EXPOSED TO THE WEATHER 5HALL BE SCH. 40 GALVANIZED. b. ALL EXP05ED AND CORE AREA PIPING 2-I12' AND LARGER SHALL BE SCH. 10 STEEL COMPLETE WITH GROOVED FITTINGS. c. ALL CONCEALED PIPING 2' AND SMALLER SHALL BE ALLIED XL, CENTURY LS OR CPVC. d. UNDEw_%ROUND PIPING SHALL BE CLA58 52 DUCTILE, C- 300 SDR 14 PVC OR EQUAL. (o. INSTALL HANGERS IN ACCORDANCE WITH SECTION 4-6, NFPA 13, 1994 EDITION. 1. PROTECT ELEVATORS IN ACCORDANCE WITH STATE FIRE MARSHALL'S UNIFORM SAFETY RULES, CHAPTER 4A-41. ELECTRICAL AND ELEVATOR CONTRACTORS MUST COMPLY WITH THESE REQUIREMENTS. 8. PROVIDE CORROSION RESISTANCE TREATMENT TO SPRINKLER HEADS EXPOSED TO WEATHER ALL NON AIR CONDITIONED AREAS ARE TO BE CONSIDERED EXPOSED TO WEATHER 9. PROVIDE SPARE HEAD AND TOOLS CABINET. 10. HYDROSTATICALLY TEST ENTIRE SYSTEM At 200 PSI FOR MIN. (2) HOURS MUST PROVIDE CERTIFIED TEST DATE. 11. COORDINATE WITH ELECTRICAL CONTRACTOR FOR ANY CONFLICTS OF SPRINKLER HEADS AND LIGHT FIXTURES, SEE ELECTRICAL PLANS 12. COORDINATE WITH STRUCTURE ALL OTHER TRADES FOR PLACEMENT OF PIPES / HEADS. DESIGN CRITERIA. 1. HYDRAULIC DESIGN CRITERIA: A. PARKING GARAGE NFPA HAZARD CLASSIFICATION---- OH-1 DESIGN AREA OF APPLICATION---- 1"0 SF. DESIGN DENSITY ---------------- 0.15 GPM/SF- MAXIMUM HEAD SPACING --------- 15 Ft. DESIGN COVERAGE PER HEAD---- 130 SF. MAXIMUM. B. OFFIGES NFPA HAZARD CLASSIFICATION---- LH DESIGN AREA OF APPLICATION---- 1,500 SF. DESIGN DENSITY ---------------- 0.10 GPM/SF MAXIMUM HEAD SPACING --------- 15 FT. DESIGN COVERAGE PER HEAD---- 225 SF. MAXIMUM. 2. SYSTEM REQUIREMENT PER HYDRAULIC CALCULATIONS GPM = 615 PRESSURE = 15 P51G 3. FIRE PUMP DATA: GPM = 500 PRESSURE DIFFERENTIAL= 6$ PSIG MIN. DICHARGE PRESSURE = 85 PSIG vok CA w F ..'ww J PERMIT SET DRAWING TITLE: NO. DATE REVISION NO, DATE REVISION NOTES URDATED REFUr Wr o 710-M t DETAIL �^' is •-t. ..-% PLAN . ' SCALE: DATE- JLM A 2003 113• -; --PROJECT NO. 9W22 DRAVANG NO: 2003 FS-'� - ..k. is I