02-930-0685 TON 5 TON
4 TON 5 TON 5.25 TON
VIBRATION ISOLATOR SCHEDULE
TYPE
DESCRIPTION
USE
MANUFACTURER
ISOLATING PAD, BONDED PERMANENTLY
I
TO 3/4" STEEL PLATE FOR EQUIPMENT
ROOF C.U.'S
KORFUND TYPE EU
MOUNTING
SPRING ISOLATOR, -FREE STANDING,
KORFUND SERIES
II
LATERALLY STABLE, UNHOUSED, WITH
NOT USED
WSC (MIN. 1/2"
LEVELING BOLTS AND 1/4" THICK
DEFLECTION)
ISOLATING PAD
SPRING ISOLATED INERTIA BASE:
REINFORCED CONCRETE POURED INTO
III
WELDED STEEL FRAME AND ISOLATED
NOT USED
BY TYPE II ISOLATOR
SPRING ISOLATED HANGERS:
IV
COMBINATION OF SPRING AND RUBBER
(LOBBY)
AHU-11 LOBBY
KORFUND TYPE VX
(MIN.1" DEFLECTION)
IN SHEAR IN SERIES, ALL ENCASED IN
WELDED STEEL BRACKETS
NOTES
1 • ALL SPRING ISOLATORS SHALL HAVE AN ADDITIONAL TRAVEL OF 50 %
BETWEEN DESIGN HEIGHT AND SOLID HEIGHT, SHALL HAVE THE SAME
DEFLECTION FOR EACH EQUIPMENT, AND THEIR OUTSIDE DIAMETER
SHALL NOT BE LESS THAN 80 % OF THEIR OPERATING HEIGHT.
2. DEFLECTION SHALL BE AS SHOWN ON CONTRACT DOCUMENTS.
AIR CONDITIONING LEGEND
A FD FIRE DAMPER MOUNTED VERTICALLY
FIRE DAMPER MOUNTED HORIZONTALLY
-� FD
FIRE AND SMOKE DAMPER MOUNTED VERTICALLY
FSD
TFSD FIRE AND SMOKE DAMPER MOUNTED HORIZONTALLY
CEILING RADIATION DAMPER
SMOKE DAMPER
WALL FIRE RATING LEGEND
NOT RATED
ONE HOUR FIRE RATED
TWO HOUR FIRE RATED
OWNER/DEVELOPER
THE PLAZ,
8000MPANY
7300 S.W. 57 COI
SUITE 400
4960 S.W. 72 AVENUE
MIAMI, FLORIDA 33155 CITY OF SOUTH I
305.662.1421 SOUTH MIAMI, FL
A/C SPLIT SYSTEM SCHEDULE
DESIGNATION
AHU-I (SUN M LOBBIES)
ANTI-2 (NORTH 141NCs LOBBIES)
AHU-3
AHU-4
AHU-5
AHU-6
AREA SERVED
COM40 LOBBIES
CM AO LOBBIES
OFFICES
OFFICES
OFFICES
OFFICES
TRANS
TRANE
TIRANE
TRANS
TRANS
TRANS
IMANUFACTURER
FAN COIL MODEL No.
TWE060
TWE060
TWE048
TWE060
TWE063
TWE062
CONDENSING UNIT MODEL No. I
2TTR2060
t 2TTR2060
2TTR2048
2TTR2060
2TTR20(-0
()) 2TTR2036
C O M 8 1 N E D R AT I N G S
TOTAL SENSIBLE CAPACITY BTU HR
60,500
60,500
49,500
60,500
61000
63,000
GRAND TOTAL CAPACITY BTU HR
43,800
43000
35,900
43000
45100
48,400
TOTAL HEATING CAPACITY BTU H R
25,500
25,500
25,500
25,500
25,500
25,500
ENERGY EFFICIENCY RATIO SEER (EER)
12.50
12.50
1225
12.50
12.0
10.4
COEFFICIENT OF PERFORMANCE COP
-
-
-
-
-
-
FAN COIL UNIT
TYPE
VERTICAL
VERTICAL
VERTICAL
VERTICAL
VERTICAL
VERTICAL
TOTAL AIR SUPPLY CFM
1)300
1)300
1,600
1)300
2,000
2,100
OUTSIDE AIR SUPPLY CFM
300
300
360
200
230
460
ENTERING AIR CONDITIONS FDB/FWB
60/61
80/61
50/61
80/61
80/61
80/61
EVAPORATOR COIL MIN. ROWS MAX. F.P.I.
-
-
-
-
-
-
EXTERNAL STATIC PRESSURE "H 20
0-5
05
05
05
0.5
05
FAN SPEED RPM
HIGH SPEED
HIGH SPEED
HIGH SPEED
HIGH SPEED
HIGH SPEED
HIGH SPEED
FAN MOTOR HP
11/2
1/2
1/2
1'/2
3/4
3/4
ELECTRICAL SERVICE AVAILABLE 1
208/1I60
208/1/60
208/1/60
208/1/60
208/1/60
208/1/60
RUNNING LOAD AMPS
3.1
3.1
4.2
3.1
3. 9
1.0 (EACH)
ELECTRIC RESISTANCE HEATER SIZE KW
1.5
1.5
1.5
1.5
1.5
1.5
UNIT WEIGHT
225
225
C O N D E N S I N G U N I T
TYPE
AIR COOLED
AIR COOLED
AIR COOLED
AIR COOLED
AIR COOLED
AIR COOLED
LOCATION
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
REFRIGERANT TYPE
R-22
R-22
R-22
R-22
R-22
R-22
AMBIENT AIR TEMPERATURE FDB
95OF
95'F
95'F
95'F=
S50F
95'F
NUMBER OF COMPRESSORS
1
I
1
1
1
2
NUMBER OF REFRIGERANT CIRCUITS
1
1
1
1
1
2
CAPACITY REDUCTION STEPS %
0-100
0-100
0-100
0-100
0-100
0-50-100
ELECTRICAL SERVICE AVAILABLE
208/1/60
208/1/60
208/1/60
208/1/60
208/1/60
208/1/60
RUNNING LOAD AMPS
24.0
24.0
24.0
24.0
24.0
25.0
MINIMUM CIRCUIT AMPS
35.0
38.0
38.0
38.0
38.0
40.0
MAXIMUM FUSE SIZE AMPS
60.0
60.0
60.0
60.0
60.0
60.0
UNIT WEIGHT
212
212
212
212
212
212
ACCESSORIES
REFRIGERANT PIPING LENGHT FT.
60
60
60
-' 60
0
-' 60
LIQUID LINE TYPE O.D.
-
-
-
-
-
-
SUCTION LINE SIZE O.D.
-
-
-
-
-
-
THERMOSTAT
HEAT/COOL
NEAT/COOL
HEAT/COOL
HEAT/COOL
HEAT/COOL
HEAT/COOL
FILTER SECTION AND FILTER TYPE
lli2' THROWAWAY
lIV, ' THROWAWAY
1'i2' THROWAWAY
1112' THROWAWAY
11/2' THROWAWAY
lie' THROWAWAY
SMOKE DETECTOR
IN SUPPLY
IN SUPPLY
IN SUPPLY
IN SUPPLY
IN SUPPLY
IN SUPPLY
V I B RATION ISOLATORS
FOR FAN COIL UNIT
-
-
-
-
-
FOR CONDENSING UNIT
-
-
-
-
-
AUTOO MATIC CONTROLS
TYPE
-
-
-
-
-
-
DESCRIPTION
-
-
-
-
-
-
1�1 PROVIDE SINGLE POINT ELECTRICAL CONNECTION WITH BUILT IN CIRCUIT BREAKER
457
JRT
.
Iri _ �j L
OUTSIDE AIR CALCULATIONS
AC -LOBBIES
LOBBY AND 3,050 5F - - - - - - -15 PEOPLE - - - - - Q 20 CFl" i/PERSON 300 CFM / O/A
CORRIDOR (5TH FL-) � -- - O/A PROVIDED - 300 CR I / O/A
AC-LOBBIE5
LOBBY AND 3,045 5F - - - - -15 PEOPLE - - - - - - fl 20 CFl" I/PE f;�50N 300 CFM / O/A
CORRIDOR (5TI4 FL-) 1 O/A PROVIDED 300 CFI" I / O/A
OFFICES (5TH FLOOR)
OFFICES 25,441 ' x 1 PERS 11000 0 = 200 PERS x 20 CFM./ PIERS = 4000 CFM / O/A
O/A PROVIDED 2121 CFI" 1 / O/A
OFFICES (4TH FLOOR)
OFFICES 16,263 *'x 1 PERS / 1000 0 = 114 PIERS x 20 CFM / PERS = 2211 CFM / O/A
OIA PROVIDED 2,400 CFM / O/A
AIR DISTRIBUTION SCHEDULE
DESIGNATION
C 4I
S
R
L
0
USE
SUPPLY
RETURN
SUPPLY
OUTSIDE AIR
EXH. LOUVER
CONSTRUCTION
ALL ALUMINUM
ALL ALUMINUM
ALL ALUMINUM
ALL ALUMINUM
ALL ALUMINUM
CAPACITY (C.F.M.)
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
SIZE
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
TYPE
24' x 24' MODUL
R PERFORATED
LINEAR
COMMENTS
4- 3/4' SLOTS
4' LONG W/
LINED PLENUM
WITH MIAMI-DADS COUNTY
PRODUCT APPROVAL
FINISH
BRUSHED ALUM.
BRUSHED ALUM.
BRUSHED ALUM.
ANODIZED ALUMINUM(PER
ARCH.)
MOUNTING TYPE
T - BAR
T - BAR
PLASTER
MASONRY FLANGIEMASONRY
PLANCx
NOISE CRITERIA
30 MAX
30 MAX
30 MAX
-
-
MANUFACTURER
METALAIRE
METALAIRE
METALAIRE
METALAIRE
PENN
MODEL
1000-6
RHF
6015
A C C E S S O R I E S
OPPOSED BLADE DAMPER
FIRE DAMPER
BIRD SCREEN
N/A
N/A
NIA
YES
YES
CONNECTION SIZE
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
SEE PLANS
NOTES
1. FINISHES AND TYPES OF MOUNTS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS.
2. PROVIDE O.B. DAMPER AT ALL SUPPLY OUTLETS.
3. AIR PATTERN AND DIFFUSER FACE SHOWN ON PLANS.
4. DIFFUSER NECK SIZE SHOWN ON PLANS.
VENTILATION EQUIPMENT SCHEDULE
DESIGNATION
EF-1
EF-2
EF-3
EF-4
OA-I
GR-I
QUANTITY
SEE PLAN
5EE PLAN
SEE PLAN
5EE PLAN
SEE PLAN
2
USE
EXHAUST
EXHAUST
EXHAUST
EXHAUST
0/A SUPPLY
ELEV. RELIEF
LOCATION
2ND, 3RD
ROOF
ROOF
WALL MOUNTED
ROOF
ROOF
AREA SERVED
PARKING:
4TH 4 5TH (TOILETS)
CfD. FL. TOILETS
ELECT! TE W.
GROUND F
MANUFACTURER
PENN
PENN
PENN
PENN
PENN
PENN
MODEL NO.
5CH36
DX16
DX16
P10VA
AF=-24
AIRETTE
F A N 36'x36'
TYPE
BELT PROPELLER
BELT CENTRIFUGAL
BELT CENTRIFUGAL
BELT PROPELLER
FILTERED SUPPLY
RELIEF
AIR FLOW C. F. M .
8100 CFM
1,5w am
1,000 CFM
450 CFM
2,000
N/A
EXTERNAL STATIC PRESSURE H 20
OJ25
0.50
050
025
0.50
NIA
FAN SPEED R.P.M.
690
650
150
N/A
FAN SOUND RATINGS, SONES
132
1 as
1,5
12
N/A
N/A
M O TO R
TYPE
-
-
-
-
ODP
N/A
HORSEPOWER H.P.
112
1/4
1/4
1/30
3/4
N/A
FULL LOAD AMPS.
Ss
5.8
5.8
13.5
NIA
ELECTRICAL SERVICE AVAILABLE
120AIC70
120-1-60
120-1-60
120-1-60
120/1/60
N/A
STARTER TYPE
AL.
A.L.
Al.
A.L.
Al.
N/A
STARTER FURNISHED BY
MECH. CONT.
MECH. CONT.
MECH. CONT.
MECH. CONT.
MECH. CONT.
N/A
G E N E R A L D A T A
LOCATION
SIDEWALL
ROOF
ROOF
SIDEWALL
ROOF
ROOF
MASONRY OPENING REQUIRED
-
2051
2051
15 3/4' 51
261*
36'x36'
OPERATING WEIGHT
-
150
150
12 (ONLY FAN)
2150
2E0
A C C ES S 0 R I E S
FACTORY CURB
N/A
YES
YES
N/A
YES
YES
SERVICE SWITCH
YES
YES
YES
YES
YES
N/A
BACKDRAFT DAMPER
-
YES
YES
-
MOTORIZED
N/A
BIRD SCREEN
YES
YES
YES
YES
YES
YES
DISCHARGE LOUVER
-
-
-
-
N/A
N/A
OTH ER
I
N/A
N/
1
N/A
N/A
V I B R A T I 0 N I S O L A T O R S
TYPE
N/A
N/A
N/A
N/A
N/A
NIA
MINIMUM STATIC DEFLECTION INCH.
N/A
N/A
N/A
N/A
N/A
N/A
A UTO MATIC CONTROLS
TYPE
-
-
-
-
��I
N/A
-
-
-
-
OTES
N/A
rDESCRIPTION
OVIDE W/ BACK GUARD, WALL SLEEVE, PANEL FAN 4 FRONT GUARD
ROL DESCRIPTION
NTERLOCK WITH GROUND FLOOR AHU'S TO OPERATE DURING OCCUPIED SCHEDULE.
ROVIDE MOTORIZED DAMPERS AT EACH O/A SUPPLY TO GROUND FLOOR UNITS TO CLOSE WHEN
NIT IS OFF DUTT_
ROVIDE AUTOMATIC DUCT PRESSURE RELIEF AS SHOUR
ANTONIO FRANYIE
FE #11640 MECH
LOSE I MORAGAS
PE #15115 ELECT.
*
VIVIANA FRANYIE CIURA
FE #49985 MECH
1€ 610 NW 27 Street MIAMI FL 33172
- (305)592--1360 •
FAX: (305)5mvg
`'
Ie�n inee
DESIGN
DRAWN
DATE
AF.
RR
1-10-03
JOB NUMBER c35-148 (2003)
CHANDLER AND ASSOCIATES
ARC P.A.
AA 0003050
5940 S.W. 73RD STREET
SOUTH NHAW FLOPMA 33143
T, L (305) 669--7592
FAX (305) 669-7593
carruoxr wo
HVAC NOTES
1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING
(HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS.
1.2 INSTALL IN ACCORDANCE WITH THE SOUTH FLORIDA CODE, ASHRAE
SMACNA, NFPA AND LOCAL ORDINANCES.
1.3 SCOPE OF WORK :
PROVIDE THE FOLLOWING COMPLETE SYSTEMS
A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM.
B. EXHAUST SYSTEM FOR TOILET ROOMS.
C. EXHAUST SYSTEMS FOR WAREHOUSE.
D. AIR CONDITIONING UNITS AND CONTROLS.
E. INDEPENDENT TEST AND BALANCE.
1.4 NOT USED
1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION
CHARGES REQUIRED
1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF
MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND FABRICATION
OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS FOR SERVICE
AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER TRADES.
1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND
TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A
COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE SPECIFICATIONS.
1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS SHOWING
DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL BEFORE
PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL INFORMATION FROM 1.6 ABOVE.
1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE
THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS.
ALL SHOP DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE
NO LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT.
1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A
A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE.
2.0 MATESU►I S
2.1 DUCTWORK
2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSIONS.
2.1.2 DUCTWORK MATERIALS:
A: GENERAL OFFICE AREAS:
FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER (R-6)
DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE
WITH SMACNA'S FIBROUS GLASS DUCT CONSTRUCTION STANDARDS.
DUCT JOINTS SHALL BE SEALED AND TAPED.
B: TOILET ROOM EXHAUST AND FRESH AIR INTAKES:
GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD. (0.5" W.G.)
C: EXPOSED AIR CONDITIONING DUCTWORK
SPIRAL GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD. (0.5" W.G.)
2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS.
WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS VANES.
.1 ALTERNATE A: PROVIDE 3-PIECE ELBOWS IN LIEU
OF TURNING VANES FOR GLASS FIBER DUCTS ONLY.
.2 ALTERNATE A: PROVIDE FULL RADIOS ELBOWS IN LIEU
OF TURNING VANES.
2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY
OUTLET AND AT EACH DUCT BRANCH.
2.2 NOT USED.
2.3 NOT USED.
2.4 AIR DISTRIBUTION PRODUCTS
2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS.
2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED
ON THE DRAWINGS AND SCHEDULES.
2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE
CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS.
2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS
BEHIND ALL AIR SUPPLY OUTLETS.
2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR CONDITIONING
COMPRESSORS STARTING FROM THE DATE OF PROJECT ACCEPTANCE.
2.6 CONTROLS:
2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION
OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK
WIRING INDICATED FOR EACH PIECE OF EQUIPMENT.
2.6.2 OFFICE AREA DX EQUIPMENT:
PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT/COOL
THERMOSTATS WITH ON -OFF AUTO SUB -BASE SWITCH AS FURNISHED
BY THE EQUIPMENT MANUFACTURER.
2.7 STARTERS:
PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION
AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST HAVE
HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED/GREEN PILOT LIGHTS.
PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS
FOR THE INTENDED OPERATION AND INTERLOCKS,
2.8 NOT USED.
2.9 IDENTIFICATION:
2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12"x4" HIGH WITH
WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE DOCUMENTS.
2.10 RETURN AIR CEILING PLENUMS:
2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS"
ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE
A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM
SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING SPACE.
SEE ARCHITECTURAL PLAN FOR COORDINATION
3.0 EXECUTION
3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION
TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION & SERVICE.
FOR INSTALLATION, OPERATION AND SERVICE.
3.2 PAINT ALL PIPING WITH 2-COATS OF LATEX PAINT WITH
COLORS AS FOLLOWS:
CWS - DARK GREEN CHWS - DARK BLUE CA - YELLOW
CWR - LIGHT GREEN CHWR - LIGHT BLUE
3.3 THERMOSTAT LOCATION.
THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION.
INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS.
RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING.
3.4 WHERE R/A IS PROPOSED BY WAY OF DOOR UNDERCUTS, PROVIDE A MINIMUM
1" CLEAR SPACE BETWEEN THE BOTTOM OF THE DOOR AND THE FLOOR FINISH
CARPET OR TILE. TYPICALLY USED FOR ROOMS WITH 50 CFM'S OR LESS.
3.4 WHERE R/A FOR ROOMS IS PROPOSED WITH DOOR LOUVER, CONTRACTOR MUST
COORDINATE WITH DOOR MANUFACTURER AND INSTALLER IN ORDER TO PROVIDE
CORRECT SIZE LOUVER AND DOOR.
3.6 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION
REPAIR AND/OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND
TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A/E.
3.7 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES
TO MATCH SPECIFIED FLOWS & CAPACITIES.
CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE.
PERMIT SET
DRAWING TITLE:
NO. DATE REVISION
NO, DATE REVISION
SCHEDULE
UrDATED rEIMSU
0
7 -10-Q3
4*fmUllm
AND NOTE
r
PLAN
k Nil
SCALE
DATE:.JIJiAE 1% 2003
PROJECT NO: "02.2
DRAWING NO:
AC-8
le 2003
s