Loading...
02-930-067FIRE RATED WALL FASTEN DUCT TO SLEEVE WITH "S" SLIP ON TOP is BOTTOM AND PROVIDE CLEARANCE ON TOP DRIVE SLIP ON SIDES is SIDES FOR EXPANSION FIRE DAMPER ACCESS DOOR LOCATE ON SIDE OR BOTTOM DAMPER SLEEVE SEE NOTE 2. DUCTWORK DUCTWORK, SEE PROJECT DRAWINGS FOR SIZE I ELEC. DAMPER ACTUATOR DUCT SMOKE DETECTOR CONNECT TO FIRE ALARM FIRE do SMOKE DAMPER FUSIBLE LINK RUSKIN MODEL FSD 60 (AIRFOIL) COMPONENT RETAINING ANGLES SECURED TO NOTES DAMPER SLEEVE. SEE NOTE 1. 1. 1-1/2"x1 — 1/2"x16 ga. FOR DAMPERS DO NOT SECURE ANGLES TO WALL OR FLOOR UP TO 50 x60 SECURED W/ #10(M5) PROVIDE ANGLES ON WALL FOUR SIDES OF SREWS 0 6" O/C SLEEVES AND BOTH SIDES OF WALL OR FLOOR 2. DAMPER SLEEVES SAME GAGE AS DUCT 16 ga. MIN. TO 10 ga. MAX. SMOKE AND FIRE DAMPER MOUNTING DETAIL N.T.S. INTAKE VENTILATOR (SEE M-6 FOR SPECIFICATION) C.U. G.U. G.U. G.U. NA C.U. C.U. C.U. C_U_ :OOF X xx ROOF PIPE SUPPORT Ibx5 O/A SUPPLY TO UNIT (TYPICAL) (291 CFM) W/ FIRE 4 SMOKE DAMPER REF. PIPES 12' MIN. (TYPICAL) (TYPICAL) A.H.U. A.H.U. AND MANUAL VOLUME DAMPER (SEE NOTE 4) RE RATED L5HjAFT_ (5EE ARCH. DXz5.) 5TH FLOOR 5TH FLOG' i 10x8 O/A SUPPLY TO UNIT (291 CFM) W/ FIRE 4 SMOKE DAMPER AND MANUAL VOLUME DAMPER A.N.U. A.H. (TYPICAL),(SEE NOTE 4) 0 5EE DETAIL FOR x d I -j AC CL05ET THI5 SHEET. ip 4TH FLOOR 4TH FLOO 2" A/C CONDENSATE DRAIN BY PLUMBER 2ND FLOOR 2ND FLOOR 1ST FLOOR 1ST FLOOR TYPICAL O/A SHAFT N.T.S. NOTES:- 1-PROVIDE FD/SD ON SHAFTS ID 4 OONLY AT G.F. / 2ND. PLR. SEPE"RATION. 2-PROVIDE 2HR. HORIZONTAL ENCLOSURE AT BOTTOM OF SHAFTS 4 4 SEE GF. PLAN. 3-5HAFT5 O, O 4 S O6 ONLY SERVE DOWN TO 2ND. FLOOR 4-SEE A/C SCHEDULES FOR ACTUAL O/A CFM REQUIRED. OWNER/DEVELOPER: THE RICFARID" RAWOn - 14f COMPANY SUITE 400 4960 S.W. 72 AVENUE MIAMI, FLORIDA 33155 305.662.1421 PLAZA 57 7300 S.W. 57 COURT CITY OF SOUTH MIAMI SOUTH MIAMI, FLORIDA 33143 24x10 SHEET METAL DUCT IN 2-HR DRYWALL SHAFT. SEE ARCH. DETAIL D FD VD LN, VD "'w F I RE1=R PIPING IN FIRE qk��z/A SUPPLY t0 UNIT PROTECTED SHAFT W/ FIRE 4 SMOKE DAMPER AND MANUAL VOLUME DAMPER (TYPICALXSEE NOTE 4). A/C CLOSETS 4TH FLOOR 1/211 = ]Loll INTAKE VENTILATOR 24x10 SHEET METAL DUCT ABOVE AT ROOF_ IN 2-HR DRYWALL SHAFT. SEE ARCH. DETAIL L — — REFR PIPING (DN) IN FI A �� lbx5 O/A SUPPLY TO UNIT PROTECTED SHAFT I ♦♦� �I W/ FIRE 4 SMOKE DAMPER RFFR PIPING (UP) IN FIRE I AND MANUAL VOLUME DAMPER PROTECTED "SHAFT L - _j (SEE NOTE 4) TO ROOF COWL A/C CLOSETS 5th FLOOR 1/211 = 11-011 GLASSF IBER SUPPLY DUCT rSCH. 40 P.V.C. COND. CONCRETE SLAB ! RISER DOWN (BY PLUMBER) II III r REFRIG. LIQ. & INSULATED CEILING I SUCTION LINES TO C.U. ON ROOF I Icc— II STRIP HEATER FACTORY FABRICATED FILTER SECTION 1 " THROW AWAY BLOWER 1 1 1 PRE -MANUFACTURED STEEL III CHANNEL SUPPORT UNIT. III II CONCRETE SLAB III I......... ............ ....... III.......... 1111 TYPICAL A/C EQUIPMENT CLOSET NO SCALE '----------- ACCESSIBLE CEILING MOISTURE DETECTOR IN J AUX. PAN TO SHUT OFF AHU 3/4" P.V.C. A/C CONDENSATE -AND ALARM (VISUAL k AUDIBLE) DRAIN. SEE PLUMBING DWGS. 4 EMERGENCY DRAIN PAN TO OVERHJANG 4" ALL AROUND AHU. HORIZONTAL FAN COIL MOUNTING DETAIL N.T.S. GALVANIZED SHEET METAL COWL 11/2' PVC SCH. 40 SLEEVE (TYPJ REFRIGERANT PIPES FILL WITH FOAM b. INSULATION (TYP.) GALV. STEEL 16 GA. /' SUPER STRUT TYPICAL SUPPORT 1 1 ( I I I III 11 BETWEEN FLOORS AT 8'-0' O/C PIPE SUPPORT VERTICALLY 14" 2'0 ALUM. PIPE 12" *8'-0' O/C ROOF CURB ROOF FLA5HING r ROOFING 496 REFRIGERANT PIPE SUPPORT BASE CHASE IN PARTITION ANCHORED TO ROOF SLAB_ W/ 1/4'xl-1/2' LONG TAPCONS ROOF CURB AND 'STEEL WASHER5 (4 TOTAL) ANCHORED TO ROOF BLAB. W/ 1/4"xl-1/2" LONG TAPCONS AND STEEL WASHERS ,v 1210/C REFRIGERANT PIPING COWL AND SUPPORT DETAIL N.T.S. TYPICAL REFRIGERANT PIPE SET CLAMPED TO SUPER STRUT 1--1 /2 .x4 LONG SLEEVE FILLED W/, VC SCH. 40 FOAM INSULATION GALV. STEEL 16 GA. SUPER STRUT ALUMINUM BIRD SCREEN ALL AROUND FOAM-RUNIER GASKET APPLIED TO UNDER SIDE OF FAN CURB CAP - SECURE FAN TO CURB WITH S/M SCREWS 12" O.C. ALL AROUND TYPICAL SUPPORT - - -- -- BETWEEN FLOORS REFRIGERANT PIPING SUPPORT DETAIL N.T.S. 0 NFUSED DISCONNECT SWITCH 14" A.F. ROOF 411 I 11 BACKDRAFT DAMPER v 1 ,ANCHOR TO SLAB * 12' O/G RUN POWER SUPPLY LEADS WITH 1/4' x 1112' TAPCON IN CORNER INSIDE CURB N SI '�) ROOF STRUCTURE —SEE ARCH WIND LOAD CALCULATIONS: DESIGN WIND PRESSURE AT 35 FT. PEIGHT - 33.5 PSF GF. = 2.0 DESIGN WIND PRESSURE = 61.0 PSF CONDENSING UNIT AREA = 4.3x3.1 = 14.1 BF Mo= 61.0 PSF x 14.1 SF x 3.13 FT= 2,B46 FT -LB. Fr = 1,000 x 1.5 FT. / 3 FT - 1/2 W = 436 LB. Fy = 6-1.0 PSF x 1.5 SF x 1.5 FT = 1,414 LB - ALLOWABLE STRESS FOR ONE TAPCON 1/4' x 1' EMBEDMENT IN 2000 PSI CONCRETE = Fr = 190 LB. F6 = 325 LB. PROVIDE 4 TAPCON 1/4' x 11/2' PER LEG Fr = 190 LB. x 4 = 160 LB. VS. 436 LB. REQ. Fs = 325 LB. x 8 = 2;600 LB. VS. 1,414 LB. REQ. 4 - 1' ISOLATION PADS VV STEEL CABLE HURRICANE 5TRAn BOLTED TO UNIT AND FRAME: 52' x 3!3' WIDE un cq CONDENSING UNIT C3x6 STEEL CHANNEL FRAME: WELDED TO ^� C3xr. STEEL CHANNEL FRAME TOP PLATE ul nl nl ui STEEL PLATE WELDED TO PIPE ill III I I�� 18' FLASHING BOOT W/COLLAR I'V=' STEEL PIPE u l I I I (BY ROOF CONTRACTOR II1111 SUPPORT III III * 36 O/C iiiiii ROOF INSULATION � III I11 F�,, ' �' E j'� � t � ' �'�r'` � � �' iiiiii � , � .,� � Fi ,� •.� .• f ��� / WITH 1/4' x 1'V2' TAPCON CONCRETE ROOF DECK (TYPICAL 4 PER LEG) G'xVx'/4' STEEL PLATE WELDED TO I'h' PIPE CONDENSING UNIT MOUNTING DETAIL N TS. NOTE: ALL FRAME STEEL SHALL BE SHOP PRIMED WITH RED LEAD AND FIELD PANTED WIT14 A IRUST INHIBITIVE PRIMER ALUMINUM FRAME A55EM13LY LU/ DECORATIVE EXPANDED METAL GRILL SEE ARCH. DUJG5. 15EE SCHEDULE WALL MOUNTED EXHAUST FAN DETAIL SCALE: 1/4" ,4T1-IERIOROOF �N WALL SLEEvE SHROUD SUFFL IED r FAN MANUFACTURER. S.S. BIRD SCREEN DISCHARGE DAMi=r=R HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR YES - FIRE DAMPER(S) YES - SMOKE DAMPER(S) YES - FIRE RATED ENCLOSURE YES - FIRE RATED ROOF/FLOOR CEILING ASSEMBLY - NO FIRE STOPPING YES - l2 MI _PER D AND STRUCTURAL PLANS FOR DETAIL W A L L E F MOUNTING DETAIL SMOKE CONTROL - NO N.T.S. CENTRIFUGAL ROOF EXHAUST FAN N.T.S. PERMIT SET DRAWING TITLE: ANTONlO FRANYIE NO (DATE REVISION nln nATP REVISION PE #11640 MECH CHANDLER AND ASSOCIATES JOSE I MORACAS ARCHITECTURE, P.A. © CONDO UNI" PE f15115 ELECT. AA 0003050 ' VIVIANA FRANYIE CIURA ►' PE f499i5 MECH 10i170 NW 27 Street MIAMI FL33'I'l2 5940 S.W. 731tD STREET SOUTH MIAMI, FLtJRIDA 33143 (3Q3 592--1360 + FAX 005?554W9 DESICN DRAWN DATE m TEL (305) 669-7392 A.F. A.F. 1-10-03 FAX (305) 669-7593 JOB NUMUR 99-145 (2003) CDFYMHT ti 11101 =1 i r .• n SCALE: DATE: JUNE A 2003 PROJECT NO: SW2.2 ` "• DRAWING NO: zz • Amy �- �1� AC-7 ZQ