BRB21-0949POOL BARRIER NOTES OUTDOOR SWIMMING POOL BARRIER SHALL COMPLY WITH FBC 7TH EDITION 2020 SECTIONS R4501.17.1.1 THROUGH R4501.17.1.14. ` a THE TOP OF THE BARRIER SHALL BE AT LEAST 48 INCHES (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. THE MAXIMUM VERTICAL CLEARANCE ` BETWEEN GRADE AND THE BOTTOM OF THE BARRIER SHALL BE 2 INCHES (51 MM) MEASURED ON THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. WHERE THE TOP OF THE POOL STRUCTURE IS ABOVE GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE THE BARRIER IS MOUNTED ON TOP OF THE POOL STRUCTURE, THE MAXIMUM VERTICAL CLEARANCE BETWEEN THE TOP OF THE POOL STRUCTURE AND THE BOTTOM OF THE BARRIER SHALL BE 4 INCHES (102 EXISTING 6' H MM). EXISTING 6' H CHAIN LINK FENCE 7 5 . 0 ' WOOD FENCE THE BARRIER MAY NOT HAVE ANY GAPS, OPENINGS, INDENTATIONS, PROTRUSIONS, OR STRUCTURAL COMPONENTS THAT COULD ALLOW A YOUNG CHILD TO CRAWL UNDER, SQUEEZE THROUGH, OR CLIMB OVER THE BARRIER AS HEREIN DESCRIBED BELOW. ONE END OF A REMOVABLE CHILD BARRIER SHALL NOT BE REMOVABLE WITHOUT THE AID OF TOOLS. OPENINGS IN ANY BARRIER SHALL NOT ALLOW PASSAGE OF A 4—INCH—DIAMETER (102 MM) SPHERE. f V . SOLID BARRIERS WHICH DO NOT HAVE OPENINGS SHALL NOT CONTAIN INDENTATIONS OR PROTRUSIONS ^° EXCEPT FOR NORMAL CONSTRUCTION TOLERANCES AND TOOLED MASONRY JOINTS. WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND VERTICAL MEMBERS AND THE DISTANCE BETWEEN — — — — - — �u THE TOPS OF THE HORIZONTAL MEMBERS IS LESS THAN 45 INCHES (1143 MM), THE HORIZONTAL MEMBERS - - -- _ SHALL BE LOCATED ON THE SWIMMING POOL SIDE OF THE FENCE. SPACING BETWEEN VERTICAL MEMBERS — SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. WHERE THERE ARE DECORATIVE CUTOUTS WITHIN r I I VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. PROPOSED lfi'-10" SWIMMING POOL ! 2'-3 WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF THE HORIZONTAL MEMBERS IS 45 INCHES (1143 MM) OR MORE, SPACING BETWEEN VERTICAL ! I MEMBERS SHALL NOT EXCEED 4 INCHES '(102 MM). WHERE THERE ARE DECORATIVE CUTOUTS WITHIN 31 VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. - MAXIMUM MESH SIZE FOR CHAIN LINK FENCES SHALL BE A 2-1/4 INCH SQUARE (57 MM) UNLESS THE FENCE i9 IS PROVIDED WITH SLATS FASTENED AT THE TOP OR BOTTOM WHICH REDUCE THE OPENINGS TO NO MORE z i O - THAN 1-3/4 INCHES (44 MM). N M! 1 ° X U NO ADDITIONAL DECK TO BE EXISTING RESIDENCE WHERE THE BARRIER IS COMPOSED OF DIAGONAL MEMBERS, THE MAXIMUM OPENING FORMED BY THE INSTALLED UNDER THE ; #7720 DIAGONAL MEMBERS SHALL BE NO MORE THAN 1-3/4 INCHES (44 MM). SCOPE OF THIS PERMIT i FFE _ +14.0' NGVD I ACCESS GATES, WHEN PROVIDED, SHALL BE SELF -CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS =- j OF SECTIONS R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED WITH A SELF -LATCHING LOCKING I DEVICE LOCATED ON THE POOL SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED NO LESS THAN _ 54 INCHES 13 M ( 72 M) FROM THE BOTTOM OF THE GATE, THE DEVICE RELEASE MECHANISM MAYBE LOCATED ON EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 MM) OF THE RELEASE MECHANISM. PROPOSED ELECTRIC I POOL EQUIPMENT METER WHERE A WALL OF A DWELLING SERVES AS PART OF THE BARRIER, ONE OF THE FOLLOWING SHALL APPLY: N - 36" TALL 1 __ .. SHRUBBERY SCREEN N s' 1. ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL SHALL BE AROUND EQUIPPED WITH AN EXIT ALARM COMPLYING WITH UL 2017 THAT HAS A MINIMUM SOUND PRESSURE EQUIPMENT r RATING OF 85 DBA AT 10 FEET (3048 MM). ANY DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 I i INCHES (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE ALARMS ARE NOT REQUIRED FOR �" �"`"w w EACH DOOR OR WINDOW IF SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS BROKEN AT " — X — " — X — " —4— x w ANY OPENING. EXCEPTIONS: EXISTING 6' H WATER EXISTING 6' H A. SCREENED OR PROTECTED WINDOWS HAVING A BOTTOM SILL HEIGHT OF 48 INCHES (1219 MM) OR CHAIN LINK FENCE WOOD FENCE METER MORE MEASURED FROM THE INTERIOR FINISHED FLOOR AT THE POOL ACCESS LEVEL. B. WINDOWS FACING THE POOL ON FLOOR ABOVE THE FIRST STORY. C. SCREENED OR PROTECTED PASS -THROUGH KITCHEN WINDOWS 42 INCHES (1067 MM) OR HIGHER WITH A COUNTER BENEATH. 2. ALL DOORS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL MUST BE EQUIPPED WITH A SELF —CLOSING, SELF -LATCHING DEVICE WITH POSITIVE MECHANICAL LATCHING/LOCKING INSTALLED A MINIMUM OF 54 INCHES (1372 MM) ABOVE THE THRESHOLD, WHICH IS APPROVED BY THE AUTHORITY HAVING JURISDICTION. SITE PLAN nDcKI eoCe rep rl 11 eTInKl Al ALLOWABLEMAXIMUM • • 1'. .1 MAX. IMPERVIOUS AREA ALLOWED (SF1 4f202 % 71 ..'.f f 168 _ • 1 SF ® 1 SF ••'• r •39.68% •. .•• • COPINGSPACE r, 6,350 NO ADDITIONAL DECK TO BE INSTALLED UNDER THE 60.4S% SCOPE OF THIS PERMIT ... • . • • GUESTIONS• s • • • ••s• s•w•• ••• •••• • ••• • • • • i • 4,•090 • ••••• • •w• • •••• • LEGAL DESCRIPTION LOT: 15 AND THE NORTH % OF LOT 14 BLOCK: 3 SUBDIVISION: LARKIN PINES PLAT BOOK: 24 PAGE: 20 COUNTY: MIAMI-DADE FOLIO/PARCEL: 09-4036-027-0280 CONTRACTOR TO SECURE AND PROTECT ALL MATERIAL BROUGHT ON SITE. CONTRACTOR TO RESTORE ALL AREAS IMPACTED BY PROPOSED WORK TO EXISTING CONDITION OR BETTER. VIYJ I nv%t 1 IVIY lnnLr% l'1nL 1 ;MAIN AND TO BE PROTECT TH 6' WOOD 04S BURIED WITH ATTACHED V%6"X6" ;WIMMING POOL ALARM THAT, WHEN PLACED IN A POOL, SOUNDS AN 4RM UPON DETECTION OF AN ACCIDENTAL OR UNAUTHORIZED ENTRANT 'O THE WATER. SUCH POOL ALARM MUST MEET AND BE INDEPENDENTLY ITIFIED TO ASTM STANDARD F2208, TITLED "STANDARD SAFETY 'CIFICATION FOR RESIDENTIAL POOL ALARMS;' WHICH INCLUDES SURFAC )TION, PRESSURE, SONAR, LASER, AND INFRARED ALARMS. FOR PURPOSES IS PARAGRAPH, THE TERM "SWIMMING POOL ALARM" DOES NOT INCLUD Y SWIMMING PROTECTION ALARM DEVICE DESIGNED FOR INDIVIDUAL U.1 C'I-I AS AN Ai ARM ATTArwl: 1 TC) A rwil n THAT 4Znl IKIM IA/4JRN TWi: ('wn I POOL CONTRACTOR 7-70 Eli- TURLE'S POOL CPC052527 8785 SW 129 TERRACE 3 0 5. 2 5 2. 0 0 1 6 RAYMOND TUTTLE MIAMI, FL 33176 SHEET INDEX SITE PLAN SP1.0 LAYOUT PLAN SP2.0 PLUMBING PLAN SP3.0 STRUCTURAL PLAN SP4.0 ELECTRICAL PLAN SP5.0 PLOT . ,ATE 29 September 2021 POOL BARRIER NOTES OUTDOOR SWIMMING POOL BARRIER SHALL COMPLY WITH FBC 7TH EDITION 2020 SECTIONS R4501.17.1.1 THROUGH R4501.17.1.14. THE TOP OF THE BARRIER SHALL BE AT LEAST 48 INCHES (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. THE MAXIMUM VERTICAL CLEARANCE BETWEEN GRADE AND THE BOTTOM OF THE BARRIER SHALL BE 2 INCHES (51 MM) MEASURED ON THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. WHERE THE TOP OF THE POOL STRUCTURE IS ABOVE GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE THE BARRIER IS MOUNTED ON TOP OF THE POOL STRUCTURE, THE MAXIMUM VERTICAL CLEARANCE BETWEEN THE TOP OF THE POOL STRUCTURE AND THE BOTTOM OF THE BARRIER SHALL BE 4 INCHES (102 MM). THE BARRIER MAY NOT HAVE ANY GAPS, OPENINGS, INDENTATIONS, PROTRUSIONS, OR STRUCTURAL COMPONENTS THAT COULD ALLOW A YOUNG CHILD TO CRAWL UNDER, SQUEEZE THROUGH, OR CLIMB OVER THE BARRIER AS HEREIN DESCRIBED BELOW. ONE END OF A REMOVABLE CHILD BARRIER SHALL NOT BE REMOVABLE WITHOUT THE AID OF TOOLS. OPENINGS IN ANY BARRIER SHALL NOT ALLOW PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE. SOLID BARRIERS WHICH DO NOT HAVE OPENINGS SHALL NOT CONTAIN INDENTATIONS OR PROTRUSIONS EXCEPT FOR NORMAL CONSTRUCTION TOLERANCES AND TOOLED MASONRY JOINTS. WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF THE HORIZONTAL MEMBERS IS LESS THAN 45 INCHES (1143 MM), THE HORIZONTAL MEMBERS SHALL BE LOCATED ON THE SWIMMING POOL SIDE OF THE FENCE. SPACING BETWEEN VERTICAL MEMBERS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. WHERE THERE ARE DECORATIVE CUTOUTS WITHIN VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. WHERE THE BARRIER IS COMPOSED OF HORIZONTAL AND VERTICAL MEMBERS AND THE DISTANCE BETWEEN THE TOPS OF THE HORIZONTAL MEMBERS IS 45 INCHES (1143 MM) OR MORE, SPACING BETWEEN VERTICAL MEMBERS SHALL NOT EXCEED 4 INCHES (102 MM). WHERE THERE ARE DECORATIVE CUTOUTS WITHIN VERTICAL MEMBERS, SPACING WITHIN THE CUTOUTS SHALL NOT EXCEED 1-3/4 INCHES (44 MM) IN WIDTH. MAXIMUM MESH SIZE FOR CHAIN LINK FENCES SHALL BE A 2-1/4 INCH SQUARE (57 MM) UNLESS THE FENCE IS PROVIDED WITH SLATS FASTENED AT THE TOP OR BOTTOM WHICH REDUCE THE OPENINGS TO NO MORE THAN 1-3/4 INCHES (44 MM). WHERE THE BARRIER IS COMPOSED OF DIAGONAL MEMBERS, THE MAXIMUM OPENING FORMED BY THE DIAGONAL MEMBERS SHALL BE NO MORE THAN 1-3/4 INCHES (44 MM). ACCESS GATES, WHEN PROVIDED, SHALL BE SELF -CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED WITH A SELF -LATCHING LOCKING DEVICE LOCATED ON THE POOL SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 MM) OF THE RELEASE MECHANISM. WHERE A WALL OF A DWELLING SERVES AS PART OF THE BARRIER, ONE OF THE FOLLOWING SHALL APPLY: 1. ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL SHALL BE EQUIPPED WITH AN EXIT ALARM COMPLYING WITH UL 2017 THAT HAS A MINIMUM SOUND PRESSURE RATING OF 85 DBA AT 10 FEET (3048 MM). ANY DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 INCHES (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE ALARMS ARE NOT REQUIRED FOR EACH DOOR OR WINDOW IF SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS BROKEN AT ANY OPENING. EXCEPTIONS: A. SCREENED OR PROTECTED WINDOWS HAVING A BOTTOM SILL HEIGHT OF 48 INCHES (1219 MM) OR MORE MEASURED FROM THE INTERIOR FINISHED FLOOR AT THE POOL ACCESS LEVEL. B. WINDOWS FACING THE POOL ON FLOOR ABOVE THE FIRST STORY. C. SCREENED OR PROTECTED PASS -THROUGH KITCHEN WINDOWS 42 INCHES (1067 MM) OR HIGHER WITH A COUNTER BENEATH. 2. ALL DOORS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL MUST BE EQUIPPED WITH A SELF -CLOSING, SELF -LATCHING DEVICE WITH POSITIVE MECHANICAL LATCHING/LOCKING INSTALLED A MINIMUM OF 54 INCHES (1372 MM) ABOVE THE THRESHOLD, WHICH IS APPROVED BY THE AUTHORITY HAVING JURISDICTION. SITE PLAN OLIESTIONS? • • • • t CONCERNS? - .. • • • . •• • I Q ..•a • 4, • • - LEGAL DESCRIPTION '•"• ' "'•' LOT: 15 AND THE NORTH y OF LOT 14 BLOCK: 3 SUBDIVISION: LARKIN PINES PLAT BOOK: 24 PAGE: 20 COUNTY: MIAMI-DADE I FOLIO/PARCEL: 09-4036-027-0280 - i W 1 I W I i I I P _ to I P CONTRACTOR TO SECURE AND � PROTECT ALL MATERIAL BROUGHT ON SITE. f CONTRACTOR TO RESTORE ALL I 3 AREAS IMPACTED BY PROPOSED WORK TO EXISTING 1 I CONDITION OR BETTER. a NOTE: ALL TREES IN THE CONSTRUCTION AREA ARE TO REMAIN AND TO BE PROTECTED WITH 6' WOOD 4X4S BURIED 24" WITH ATTACHED 6"X6"X6" METAL WIRE MESHING THOUGHOUT CONSTRUCTION FLOATING BOUY ALARM / BARRIER NOTES A SWIMMING POOL ALARM THAT, WHEN PLACED IN A POOL, SOUNDS AN ALARM UPON DETECTION OF AN ACCIDENTALOR UNAUTHORIZED ENTRANCE INTO THE WATER. SUCH POOL ALARM MUST MEET AND BE INDEPENDENTLY CERTIFIED TO ASTM STANDARD F2208, TITLED"STANDARD SAFETY SPECIFICATION FOR RESIDENTIAL POOL ALARMS," WHICH INCLUDES SURFACE MOTION, PRESSURE, SONAR, LASER, AND INFRARED ALARMS. FOR PURPOSES OF. THIS PARAGRAPH, THE TERM "SWIMMING POOL ALARM" DOES NOT INCLUDE ANY SWIMMING PROTECTION ALARM DEVICE DESIGNED FOR INDIVIDUAL USE, SUCH AS AN ALARM ATTACHED TO A CHILD THAT SOUNDS WHEN THE CHILD. ` EXCEEDS A CERTAIN DISTANCE OR BECOMES SUBMERGED IN WATER. I OPEN AREA CALCULATION Ai 360 SF 10,505 SF NEW POOL 346 SF 1,997 SF TOTAL LOT AREA [SF) 10,505 TOTAL (BELOW GRADE) EXIST. DECK EXIST. IOUSE EXISTING IMPERVIOUS AREA (SF) 3,697 . < ` SHEET INDEX EXISTING OPEN AREA (SF) 6,808 �. SITE PLAN SP1.0 EXISTING OPEN AREA PERCENTAGE 64.8% 360 F LAYOUT PLAN P2.0 NEW SWIMMING POOL (SF) (BELOW GRADE) i PLUMBING PLAN SP3.0 NEW POOL DECK &EQUIP. SLAB (SF) 1,100 i STRUCTURAL PLAN SP4.0 r SUBTOTAL NEW IMPERVIOUS AREA 1,460 i ELECTRICAL PLAN SP5.0 PROPOSED TOTAL IMPERVIOUS AREA 5,157 , f 5,348 SF 1,091 SF 9 F 17 SF 1,18 SF Mimi PROPOSED TOTAL OPEN AREA 5,348 OPEN/GREEN NEW DECK NEW EQUIP. EXIST. SLAB EXIST. SPACE SLAB DRIVEWAY/ WALKWAY TOTAL PROPOSED OPEN AREA PERCENTAGE 50.9% 9 September PLOT DATE - 2021 ® o RATING OF 85 DBA AT 10 FEET (3048 MM). ANY DEACTIVATION SWITCH SHALL BE LOCATED AT LEAST 54 INCHES (1372 MM) ABOVE THE THRESHOLD OF THE ACCESS. SEPARATE ALARMS ARE NOT REQUIRED FOR — w w w w w-0 EACH DOOR OR WINDOW IF SENSORS WIRED TO A CENTRAL ALARM SOUND WHEN CONTACT IS BROKEN AT "� X — X — "— — "T ANY OPENING. EXCEPTIONS: EXISTING & H WATER EXISTING 6 H A. SCREENED OR PROTECTED WINDOWS HAVING A BOTTOM SILL HEIGHT OF 48 INCHES (1219 MM) OR CHAIN LINK FENCE WOOD FENCE METER MORE MEASURED FROM THE INTERIOR FINISHED FLOOR AT THE POOL ACCESS LEVEL. B. WINDOWS FACING THE POOL ON FLOOR ABOVE THE FIRST STORY. C SCRE i ENED OR PROTECTED PASS —THROUGH KITCHEN WINDOWS 42 INCHES (1067 MM) OR HIGHER i WITH A COUNTER BENEATH: 2. ALL DOORS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL MUST BE EQUIPPED WITH A I s SELF —CLOSING, SELF —LATCHING DEVICEWITH -POSITIVE MECHANICAL LATCHING/LOCKING INSTALLED A: MINIMUM OF 54 INCHES (1372 MM) ABOVE THE THRESHOLD, WHICH IS APPROVED BY THE AUTHORITY' HAVING JURISDICTION. SITE PLAN 3/32"=1'-0" I. SWIMMING POOL WAS DESIGNED ACCORDING TO ANSI/NSPI-8 AND ANSI/NSPI-5 2. THE DESIGN ENGINEER ASSUMES NO RESPONSIBILITY FOR POOL CONSTRUCTION IN EASEMENT OR REQUIRED SETBACK AREAS. PLOT PLANS NOT PREPARED FROM LEGAL SURVEYS OF THE EXISTING LOT AND RESIDENCE ARE SO INDICATED. POOL CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND ESTABLISH LOT LINES. IF NECESSARY, POOL CONTRACTOR AND/OR OWNER SHALL VERIFY SHOWN AND ALL DIMENSIONS PRIOR TO CONSTRUCTION. 3. IN ALL CASES, THE POOL CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO PROTECT EXISTINGS STRUCTURES FROM FAILURE BY SHEATHING AND/OR SHORING, OR OTHER METHODS AS REQUIRED. THE DESIGN ENGINEER ACCEPTS NO RESPONSIBILITY FOR THE SAFETY OF EXISTING STRUCTURES. 4. CONTRACTOR SHALL ESTABLISH LOCATIONS OF UTILITIES AT THE SITE, MINIMUM CLEARANCE DIMENSIONS SHALL BE HELD AND SHALL BE AS REQUIRED BY THE LOCAL REGULATORY AGENCY. IN GENERAL, HOLD A DISTANCE OF 10 FEET FROM OVERHEAD ELECTRIC LINES TO POOL'S WATER EDGE. S. DO NOT DRAIN POOL UNDER HIGH GROUND WATER OR STORM CONDITIONS. 6. CONTRACTOR TO FOLLOW FLOATATION ANALYSIS AS INDICATED. 7. CONTRACTOR SHALL VERIFY ALL PLAN DIMENSIONS AND CONDITIONS AT THE JOB SITE AND REPORT ANY INCONSISTENCIES TO THE ENGINEER, IF ANY CHANGES ARE REQUIRED; OTHERWISE, THE CONTRACTOR SHALL BEAR FULL RESPONSIBILITY OF SUCH CHANGES AND ANY REQUIRED REVISION TO THE.PLANS. POOL DATA CHART MAXIMUM WIDTH (FT) 12'-0 MAXIMUM LENGTH (FT) 30'-0" SHALLOW END (FT) 3'-6" DEEP END (FT) 5'-6" AREA (SF) 360 PERIMETER (LF) 84'-0" VOLUME (GAL) 12,118 TURNOVER RATE (HR) 6 HR ... . . . . . . . . . . . . . . ..... .... . ..... . ... . .... . - ... ••• low 0 POOL GENERAL NOTES so ••• •A•• 1. SWIMMING POOL WAS DESIGNED ACCORDING TO ANSI/NSPI-8 AND ANSI/NSPI-5 . . . ® •• . 2. THE DESIGN ENGINEER ASSUMES NO RESPONSIBILITY FOR POOL CONSTRUCTION IN .. . i / • • EASEMENT OR REQUIRED SETBACK AREAS. PLOT PLANS NOT PREPARED FROM LEGAL SURVEYS OF THE EXISTING LOT AND RESIDENCE ARE SO INDICATED. POOL CONTRACTOR • - SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND ESTABLISH LOT LINES. IF NECESSARY, ',. •••• • POOL CONTRACTOR AND/OR OWNER SHALL VERIFY SHOWN AND ALL DIMENSIONS 0 0 f000 PRIOR TO CONSTRUCTION. 3. IN ALL CASES, THE POOL CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO PROTECT EXISTINGS STRUCTURES FROM FAILURE BY SHEATHING AND/OR SHORING, OR OTHER ' METHODS AS REQUIRED THE DESIGN ENGINEER ACCEPTS NO RESPONSIBILITY FOR THE 30. 10,, BEAM FOR SAFETY OF EXISTING STRUCTURES. 2 -� e 4. CONTRACTOR SHALL ESTABLISH LOCATIONS OF UTILITIES AT THE SITE, MINIMUM WIDENED COPING M v CLEARANCE DIMENSIONS SHALL BE HELD AND SHALL BE AS REQUIRED BY THE LOCAL I REGULATORY AGENCY. IN GENERAL, HOLD A DISTANCE OF 10 FEET FROM OVERHEAD ELECTRIC LINES TO POOL'S WATER EDGE. BENCH -^ I 5. DO NOT DRAIN POOL UNDER HIGH GROUND WATER OR STORM CONDITIONS. iv I 6. CONTRACTOR TO FOLLOW FLOATATION ANALYSIS AS INDICATED. - 7. CONTRACTOR SHALL VERIFY ALL PLAN DIMENSIONS AND CONDITIONS AT THE JOB SITE f AND REPORT ANY INCONSISTENCIES TO THE ENGINEER, IF ANY CHANGES ARE REQUIRED; { OTHERWISE, THE CONTRACTOR SHALL BEAR FULL RESPONSIBILITY OF SUCH CHANGES , AND ANY REQUIRED REVISION TO THE PLANS. 5'-6" DEEP 3'-6" DEEP POOL DATA CHART - N(CHELESS MAXIMUM WIDTH (FT) 12'-0" _ LED LIGHT N - BENCH (TYP. OF 41 P ' , W/P G.F.I. SHALL BE MAXIMUM LENGTH (FT) 30'-0• I FROM 6' TO 20' AWAY FROM FOOL SHALLOW END (FT) 3,_6., 2 �t - 30' F DEEP END (FT) 5-6" I AREA (SF] 360 PERIMETER (LF) 84'-0" • e VOLUME (GAL) 12,118 DECK BY OTHERS UNDER SEPARATE PERMIT TURNOVER RATE (HR) 6 HR xP WOO 000 79448 % ft *o Z* 8T T� OF t�I: 40000 .10 ...... �i� ALE � .r� � x �. =sa ,� ,_ �° . POOL INSTALL VACUUM BREAKERh EQUIP ON EXISTING HOSE BIBB. 4 CONTRACTOR TO CONFIRM LOCATION ON SITE • / J POOL LAYOUT PLAN 1/41=1. �r e � a 1 PLOT DATE - 27 July 2021 s ® i •• ••• •• • • • • • • • • • • • • ® ® Y • ..•• • • • COPING � ADUSTABLE LID WEIR CONCRETE zm e l� a { k POOL WALL - ( t BASKET MIN. r .� 75 SO. IN.) SKIMMER INLET 2" SUCTION LINE'; 2" PLUGxr;: SKIMMER DETAIL NTS 2-1/2" SUCTION PIPING 4' MIN. ANTIVORTEX MAIN 1-1/2" HYDROSTATIC RELIEF VALVE. IF REO'D, ONE AT N POOL MAIN DRAIN PUMP MAIN DRAIN DETAIL ° WATER LINE d a PIPE SIZING SUCTION PIPING 1.5 INCH @ 10 FPS = 55 GPM 1.5 INCH @ 8 FPS = 44 GPM 2.0 INCH @ 10 FPS = 98 GPM 2.0 INCH @ 8 FPS = 78 GPM 2.5 INCH @ 10 FPS =152 GPM 2.5 INCH @ 8 FPS =122 GPM PUMP RATING 1/2 3/4 1.0 1.5 2.0 2.5 3.0 PUMP CAPACITY (GPM) 30 47 55 75 102 126 150 LAILCJKINAIUKuj z z U 10uj 10 a - • ¢ z a cn > ili iv • •' • •. •••• • AVON II ISECTION §%6, A it Ale 30' 3 „ o _ io SECTION 6„ B i -St MAX 1.7 #3 BARS @ 9" w #3 BARS @ g„ C/C, EACH WAY C/C, EACH WAY SECTION A P 1/4 =1 b" r STRUCTURAL NOTES: SOIL STATEMENT 1. ALL FLOOR & WALLS TO BE PNEUMATICALLY APPLIED CONC. BASED UPON VISUAL INSPECTION OF THE SITE, SOIL p WITH A MIM. 28 DAY COMPRESSIVE 3,000 P.S.I. CONDITIONS, LIMESTONE AND SAND, APPEAR ADEQUATE FOR 12 0 •• .F ������ 2. ALL REINF. STEEL TO CONFIRM TO A.S.T.M. A615 GRADE 60 AND THE DESIGN BEARING LOAD OF 2,000 PSF. AFTER EXCAVATION, p" 2' 2� p ���� .••� F••;'9����� SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI. THE SITE SHALL BE INSPECTED TO DETERMINE THAT THE 0 4439 3. ALL REINFORCING SPLICES SHALL BE AT LEAST 18" IN LENGTH PREVIOUSLY ASSUMED CONDITIONS EXIST THROUGHOUT THE __T: .a_ _z ------ .._.__ . T .r ..:.0,00 UNLESS OTHERWISE NOTED ON THESE PLANS. EXCAVATION OR THAT EXPOSED CONDITIONS ARE ADEQUATE - U� • 4. MAINTAIN MIN. 3" CLEAR COVER FROM STEEL TO SOIL SIDE. FOR THE PROPOSED SWIMMING POOL BEARING. A SIGNED :� . 8T T : �� OF s AND SEALED LETTER WILL BE PROVIDED TO THE BUILDING 6„ „ o 0 0 •, * . A* t- • OFFICIAL STATING THAT THE SOIL BEARING CONDITIONS ARE �s�C i�i,�� ••:�O R 1'0••'(�j����, AS ASSUMED OR VISUALLY DETERMINED FROM THE • EXCAVATION TO BE ADEQUATE FOR THE DESIGN BEARING. u #3 BARS @ 9" _ #3 BARS @ g„ C/C, EACH WAY `° C/C, EACH WAY SECTION HYDROSTATIC UPLIFT ANALYSIS i WATER LEVEL (NGVD) 13.0 • - • HYDROSTATIC VALVE IS OPTIONAL. DEPTH OF POOL (FT) 5.5 MINIMUM 6" SLAB REQUIRED. PER FBC R4501.21.4 IN AREAS OF ANTICIPATED POOL BOTTOM ELEV. (NGVD) 7.5 WATER TABLE, AN APPROVED HYDROSTATIC RELIEF DEVICE SHALL BE INSTALLED. FLOOD CRITERIA (NGVD) 6.0 WARNING: TO EMPTY POOL AFTER CONSTRUCTION FOR ANY REASON, THE UPLIFT 0 HYDROSTATIC UPLIFT PRESSURES BENEATH THE POOL MUST BE ELIMINATED TO PREVENT THE POOL FROM FLOATING UPWARD. OWNER MUST CONSULT A POOL CONTRACTOR EXPERIENCED IN ELIMINATING UPLIFT PRESSURES. :ITY OF SOU1 H MIAM_ • - BUILDING DEPT. STRUCTURAL SECTION BY: AM PLOT DATE - 27 July 2021 s - - 00 • • • NOTE: PRIOR TO ELECTRICAL ROUGH, ELECTRICAL CONTRACTOR SHALL SUBMIT A REVISION TO THIS DRAWING SHOWING EXISTING SERVICE WITH ADDITIONAL LOADS, CALCULATIONS, AND EXPECTED AS BUILT CONFIGURATION, IF DIFFERENT FROM THIS DRAWING. W/P G.F.I. SHALL BE FROM 6' TO ELECTRICAL CONTRACTOR TO VERIFY ON FIELD CAPACITY AND 20' AWAY FROM POOL: CONDITIONS OF EXISTING SERVICE, REPORTING TO THE ENGINEER SEE SP2.0 FOR LOCATION. ANY INCONSISTENCY AND/OR THE NECESSITY TO REPLACE ANY iw EXISTING ELECTRICAL COMPONENTS. EXISTING 2 #12 THWN 2 #14 THWN 125A 1 #12 GND. 1 #12 GND: I- 2P GFCI 20A PANEL IN 1/2" C. IN 1/2" C. 1-1P 15A 1- 2P 50A 2 #8 THWN TRANSFORMER TO PANEL'MDP' 1 #10 GND. 50A IN 112" C. DISC. 3 #12 THWN PANEL AND SERVICE HAVE SUFFICIENT CAPACITY FOR ADDITIONAL LOADS EXISTING IN 1/2" C. (3) #4 THWN (1) #6 GND JUNCTION IN 11/4" C. o BOX (TYP.) SALT CHLORINATOR • TO CONNECT TO 3HP POOL (4) 20W 130K BTU LOAD SIDE OF POOL RECIRCULATION NICHELESS HEAT PUMP PUMP TIMER PUMP LED LIGHTS ELECTRICAL SCHEMATIC :. 4 O - POOL EQUIPMENT .ELECTRICAL _ _ 0„MI - LOAD CALCULATION JUNCTION 1. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE F.B.C. BOX NOTE: POOL GROUND WIRE PER 2020, 7TH EDITION AND ARTICLE 680 N.E.C. 2017 EDITION. ALL BOND WIRES (4) NICHELESS LIGHTS 80 W NEC 680.25. SHALL BE PROTECTED WITH APPROVED MATERIAL: THE CONTRACTOR SHALL GRADE = . . • ° INSURE THAT AN ELECTRICAL BONDING INSPECTION IS CALLED FOR AND WATER LEVEL . •.. APPROVED PRIOR TO PLACEMENT OF CONCRETE OVER THE BOND WIRE COPING FBCRECIRCULATION PUMP 3,680 W E360ON CONNECTIONS. CONNECTIONS DIRECTLY FROM THE POOL LIGHT TO A AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED NDI TRANSFORMER BOX IS PROHIBITED. ALL METAL PARTS IN THE POOL AREA, IN z ; IN SECTION E3908 SHALL BE RUN WITH THE SUPPLY ADDITION TO ALL METAL DOORS, WINDOWS, SREENED ENCLOSURES, OR POOL WALL SALT CHLORINATOR 300 W CONDUCTORS AND CONNECTED TO THE BUILDING OR OTHER ITEMS CONTAINING METAL WITHIN A DISTANCE OF 5 FEET FROM THE STRUCTURE DISCONNECTING MEANS AND TO THE POOL WATERS EDGE SHALL ALSO BE GROUNDED. GROUNDING ELECTRODE(S). THE EQUIPMENT GROUNDING 2. POOL EQUIPMENT TO BE GROUNDED TO COMMON BONDING GRID ` - • HEAT PUMP 6,700 W CONDUCTOR SHALL BE USED FOR GROUNDING OR BONDING CONSISTING OF 1 #8 CONTINUOUS COPPER WIRE LOOPED AROUND POOL ( ) -1 PVC COND, TO OF EQUIPMENT STRUCTURES OR FRAMES REQUIRED TO BE PERIMETER. JUNC . BOX GROUNDED OR BONDED. THEEQUIPMENT GROUNDING - SUBTOTAL 10,760 W 3. LOOP SHALL BE GROUNDED TO PANEL VIA POOL WALL STEEL, DECK CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH SECTION REINFORCING, POOL EQUIPMENT, AND PUMP MOTOR CASING, PER NEC 1-1/2" PVC PIPE E3908.12. ANY INSTALLED GROUNDED CONDUCTOR SHALL 680.25. MIN.16" TOTAL DEMAND 10,760 / 240 NOT BE CONNECTED TO THE EQUIPMENT GROUNDING 4. PROVIDE GROUND WIRE SYSTEMS LOOP WITH #8 COOPER WIRE FOR THE CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). POOL DECK WIRE MESH AND STRUCTURAL STEEL. [ 2 5 0 . 3 2 ( B) AND TABLE 2 5 0 . 1 2 2 ] TOTAL DEMAND 44.8A 5. ALL WIRING SHALL BE COPPER THWN 6. POOL PUMP REQUIRES OVERLOAD PROTECTION PER NEC 430.32 NICHELESS LIGHT DETAIL 7. COMPLY WITH FBC E403:12 AND NEC 430.32 NTS TUUCI S/S HANDRAILS O UMBRELLA MOUNT EQUIPOTENTIAL BONDING DIVING ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE F.B.C. 2020 BOARDS DECK : DRAINS EDITION AND ARTICLE 680 N.E.C. 2017 EDITION. JUNCTION LADDERS BOXES (G) FORMING THIS GRID SHALL FOLLOW THE CONTOUR OF THE POOL AND EXTEND UNDER SHELLS PAVED WALKING AREAS AT LEAST 3 FEET HORIZONTALLY FROM THE INSIDE EDGE OF THE POOL. 1 STR C U TURAL REINFORCING STEEL WHERE REINFORCING RODS ARE BONDED s, TOGETHER BY THE USUAL STEEL TIE WIRES. WATER Y 2. THE WALL OF A BOLTED OR WELDED METAL POOL CIRCULATING FENCE METAL DOOR - #8 BARE SOLID COPPER CONDUCTOR BONDED WITH APPROVED EQUIPMENT METAL FRAMES, <5' POOL DECK • • CONNECTIONS FROM WATER EDGE - THE GRID SHALL FOLLOW THE CONTOUR OF A POOL IN A 12"x 12" PATERN BOND WIRE TO BE SECURED TO DECK STEEL WITH BONDED AT ALL POINTS OF CROSSING o POOL COVER MOTOR APPROVED CLAMP. TO BE ENCASED IN DECK SLAB OR - THE GRID SHALL BE SECURED WITHIN OR UNDER THE POOL AND DECK MEDIA - CONCRETE BOX PROVIDING MIN: 3" OF OF COVER AROUND NOTE: ALL METAL PARTS SHALL BE BONDED AS PER N.E.C. 680.26 B BONDING �) GROUND WATER BAR HEATER FIXED METAL, <= 5' FROM WATER CLAMP GRIDS ARE NOT REQUIRED: EDGE - UNDER NON -PAVED WALKING AREAS - UNDER WOOD OR OTHER NON-CONDUCTIVE DECKING -WHERE FENCES OR OTHER BARRIERS PREVENT ONE FROM STANDING ON THE COMMON BONDING GRID POOL BOND SCHEMATIC ' GROUND TOUCHING THE WATER WITHIN THE POOL NTS NTS PLOT DATE - 27 July 2021