07-1060-001PIRA YI;NETRATION DIC;'fAII. 1.-Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 12 in. See Concrete Blocks (CAZT) category in the Fire REsistance Directory for names of manufacturers. 2. Through Penetrants - One metallicpipe, conduit or tubing to be installed within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The annular space shall be 0 in. (point contact) to max 1-1/4 in., The following types and s!zes of metallic pipes, conduits or tubing may be ,used: A. Steel Pipe - Nom 10 in. diam, (or smaller) Schedule 10 (or heavier) steel pipe. B. Conduit - Nom 4 in. diam (or, smaller) steel electrical metalric tubing or steel conduit. C. Copper Tubing - Nom 4 in digm or smaller Type L (or heavier) steel pipe D. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Pocking Material -Min 3 in thickness of min 4 pcf mineral wool butt insulation for nom 4 in. diam (and smaller) pipes conduits or tubings and a min 4 in. thickness of min 4 pcf mineral wool bott insulation for pipe greater than nom 4 in. diam, firmly packed into opening as a permanent form .packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. 4. fill, void or cavity material -Sealant -Min 1/2 in . thickness of fill material applied within the annulus ,flush with the top surface of floor or both surfaces of wall. At the point of contact location between pipe and concrete, a min 1/2 in diam bead of fill ',material shall be applied at the concrete /pipe interface on the top surface of floor and on both surfaces of wall. HILTI CONSTRUCCION CHEMICALS, DN OF HILTI INC-CP601S,CP606 OR FS -ONE Sealant ( Note L Ratings apply only when FS -ONE Sealant in used). NAC's VOLTAGE CROP FOR 20AV STARTING VOLTAGE .... . .........................................- .... .---................ -------.........---........__..............................----...................... __........ .... ............... _............ ........ .............. VOLTAGE VOLTAGE MINIMUM V OK 4C;. DESCRIPTION LENGHT (FT) LOAD (AMP) DROP TO LOAD OPERATING OLTE ,§C= (VOLTS) ('VOLTS) VOLTAGE CROP ......... .................................... .................................._.......................................................................................-.............-......................... ..........tyGLTS)...... _..... NAC 1 801<2 086 0.44 19' 6 16.0 4.40 NAC 2 100X2 0.70 0.4.5 19.95 16.0 4.110 NAC 3 N,A N A N'A N;A NIA NIA NAC 4 NIA IJ'A NIA N;A NIA N,A SMOKE DETECTOR MOUNTING DETAIL N.T.S. CEILING SMOKE DETECTOR A/C DIFUSER AND / OR FLOURECENT LIGHT Notification Appliance Circuit Load Calculations Description Total Alarm Current (Amp) Maximum Capacity (Amp) 75% derated Max. Alarm Current(Amp) NAC 1 0.86 3.0 2.25 NAC 2 0.70 3.0 2.25 NAC 3 N/A WA N/A NAC 4 N/A N/A N/A TOTAL 1.56 6.0 4.5 FIRE ALARM SY10BOL LEGEND SYMBOLS DESCRIPTION E hNUFAf iURER MODEL QT �' �i EXISTING FIRE PA. AM RRELITE 00 N/A I'AC J CONTROL P.4h3E'L FGPS POWER ..... FIRELITE ............... ................. ......... _.............. 24FS5 ....... .... _............. 1 _................ _.....-_-_.......... _......... .... _............ EXISTiNG ADDRESSABLE l BtdCiKE DETECTOR FIRELITE SD355 1 CEILING M0 NT MULII SYSTEM SENSOR PC2R 1 CANDELA K*413TROBF _.-....................__..._.... CEILING MOUN'r !v1ULTECANDELASTROBE _-........ _............. __...... Y,�M SENSOR S STE ....... ......... .... _........................ SCR 4 INALL MOUNT MULTI CANDI HORNISTROBE SYSTEM SENSOR P2R t ..................................... L ........ -............... .- ............. ...........-...... YVALL MOUNT MULT:(W4DELA STROl2iE .................. ............ .......... SYSTEM SENSOR SR 3 OENFR!C 4.7K END OF f j U111E RESISTOR GENEREC 4 TOTAL FLOOR PLAN i SCALE: 1 /8" = 1'-0" NORTH ADA HEIGHT REQUIREMENT. N.T.S. STROBE OR 60 BELOW OR HORN / STROBE K °o e ° (WHICHEVER IS LOWER) I PULL STATION ° 48" A.F.F. ° FIRE ALARM CONTROL PANEL STANDBY BATTERY CALCULATIONS CURRENT STOGY CURRENT ALARM DEVOCE QN (AMPS) (AMPS) (AMPS) (AMPS) MAKE 24FS8 FIRE CCONTROL 1 0.091 0.091 0,145 0,145 FIRELITE POWER B0083TER PC2R MULTIClANDELA CEILING 1 0.00000 0.00000 0.227 0.227 SYSTEM MOUNT HORN41STROBE SENSOR SCR MULTICANNDELA CEILi NG 4 0.00000 0.00000 0.158 0.632 SYSTEM MOUNT STRODBE SENSOR P1224MC MULITICANDELA 1 0.00000 0.00000 0.227 0.227 SYSTEM HORNISTROBBE SENSOR S1224MC MUI.LTICANDELA 3 0.00000 0.00000 0.158 0.474 SYSTEM STROBE SENSOR TOTAL. 11 0.091 1.71 BATT = [( ffSB X 24hour) +( TAL X 0.084hour )) ( 0.091A * 24hour + 1.71A * 0.084 )*1,20 GATTT = Battery size in Amp/hour (2.18A/hour + 0.144A/hour) * 1.20 TSB = Totalil StQndby Current in Amp 2.32A/hour * 1,20 TAL = T'otalll Alarm current in Amp 2.79Ajhour 1.2 = Conttingency factor BATTERY SUPPLIED = 2 X12v X 4A/hour The Total Load Current for all NAC's can not exceed 6.0 amps. EXISTING 75.d 151d Md 75W 75d FIRELITE FIRELITE��--�4�� v� vs n 1.� nn eaA 5LCT 0.15✓iA 21'. 0.15BA 0.227A 0.150A sx,e AY10 �s�-- -- 9600 2 4 F S 6 7 :� rya NAC 2 m.i N.d~e Numbw d M d _ 1 ]tL 81a�". J E.....t Lcea 0.701A Y.dmwm Numbw d m.M. fi 311 2 212 2 2/4 E 241 dt d" blAd-a. FACP F C P S a nA n.158A a � 0.027A 03 madidai insta0.6 t, C3 Sills ! SLCi l/ __LR Df! AWe FPLP $ EaR srarlE AAc. r BATTERY BATTERY ulA Izx7zvacx�A/h DACT l zx�2vd.x�A/h EOM ___-_- ' --_L_ RE ALARM SYSTEM TO BE 11 OVac _ 11 ovac - INSTALLED IN ACCORDANCE kVTiH Dedicated Ck. = Dedicated Ck. - 0 GROUND GROUND NFPA 72;70;101• ADDITION TO EXISTING CENTRAL STATION SERVICE FIRE ALARM SYSTEM RISER FIRE ALr'lI2M SHALL BE A CENTRAL AS STATION SERVICE. A CERTIFICATE p p,,i C1%j NOTED OR PLACARD SHALL 6E POSTED AT FINAL, INSPECripN, AS PER NFPA 72 MIAMI-D WE COUNTY ff.,V� 1) r'AItn, mvT 6LGG. PERMIT_ FIRE ALf'A11_z__,,, FIRE SUPPRESSION WAISR MAIN EXT. DAfEt 7 �.%O+7 BY:� &IMMI-DADE CO. FIRE DEPtUn MENI' APPLICATION # f 7 0 3 //L/ SCOPE OF WORK 7i;., The scope of this project shall be adding to a NFPA 72 compliant Existing Central Station- Serv�ceh Addressable Fire Alarm System 1 Power Booster 5 Notification Appliances and relocate 1 Smoke W Detector. The premise is a one floor Existing Mercantile Occupancy as a part of a six floor ; Mixed Occupancy Building. THE WHOLE BUILDING IS FULLY SPRINKLED, ' ! SEQUENCE OF OPERATION In the situation of a fire emergency, alerting people inside the building will be accornplished either by activating any of the existing pull stations or the existing smoke, heatiandbi duct detectors will trigger automatically the Fire Alarm System.Visuol and audible signals will be • •' generated to alert people about such emergency. �Q The Fire Alarm Digital Dialer will route all signals to the rton. All events will be shown in the FACP main display. In order to reset the system is necesory to clear up the cause of the alarm �- In case that the Fire Alarm System is not working properly, the specific problemill indicated in the FACP main display accompanied by a audible warning signal which can be acknowledged and silenced by pressing specific buttons at the FACP. ,yam The system can not be reset without fixing the problem. Specific trouble signals will be sent - ,1 to Central Station. GENERAL NOTES 1.THIS IS AN ADDITION TO AN EXISTING CENTRAL STATION SERVICE ADDRESSABLE FIRE ALARM SYSTEM DESIGNED FOR NATASHA LERATTI L.L.C. LOCATED /IT 6001 SW 70th STREET SUITES #105-106 SOUTH MIAMI, FL. 2. THIS FIRE ALARM SYSTEM IS UL LISTED AS POWER LIMITED AND OF THE GENERAL ALARM TYPE PER NFPA 72. 3. ALL WIRING AS APPLICABLE SHALL BE 18 AWG FPLP FOR INITIATING DEVICES AND 14 AWG FPLP FOR NOTIFICATION DEVICES. 4. CONDUIT AS REQUIRED SHALL BE 1/2" EMT MINIMUM AND IT SHALL BE SIZED AS PER NEC 2002 MAX. FILLED 40%. AS NdrFO 5. INSTALLATION SHALL COMPLY WITH NFPA 72 2002 ALL APP ABP, CHAPTERS. �oP 3 6. INSTALLATION SHALL COMPLY WITH NFPA 101 PPLICABLE CHAPTERS. 7 INSTALLATION SHALL COMPLY WITH NEC 2002 ALL APPLICABLE CHAPTERS. 8. SYSTEM SHALL BE GROUNDED AS PER MANUFACTURER SPECIFICATIONS AND NEC 2002 ARTICLE 250. 9. COMMUNICATION TO CENTRAL STATION IS PERFORMED USING A DIGITAL ALARM COMMUNICATOR/TRANSMITTER THAT TRANSMIT SYSTEM STATUS VIA PUBLIC SWITCHED TELEPHONE NETWORK. 10. ALL SYSTEM COMPONENTS SHALL BE UL LISTED, COMPATIBLE AND SUITABLE FOR FIRE SERVICE USE WITH FIRELITE 9600 FACP. 11-THE CEILING HEIGHT ALL AROUND THE PLACE IS LESS THAN 10'. 12. THE 120Vac POWER FEEDER FOR THE FAPS SHALL BE A DEDICATED BRANCH CIRCUIT AND MUST BE IDENTIFIED IN THE ELECTRIC BREAKERS PANEL. 13. SMOKE DETECTOR TO BE INSTALLED AS PER NFPA 72. WALL MOUNTED SMOKE DETECTOR SHALL BE INSTALLED 4" MINIMUM AND 12" MAXIMUM FROM CEILING. 14. CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR FLOW NOR CLOSER THAN S 2" FROM AN AIR SUPPLY DIFFUSER OR FLUORESCENT LIGHT. 15. ALL STROBE LIGHTS TO BE SELF- SYNCRONIZED TO AVOID EPILEPTIC SEIZURES ON PHOTOSENSITIVE PERSONS. THE INTENSITY OF LIGH WILL BE SET TO 75 CANDLES. 16. PROVIDE BATTERY CALCULATIONS AND VOLTAGE DROP CALCULATIONS AS PART OF SUBMITTAL USING AVERAGE OPERATING CURRENT FOR SIGNAL AND 24 HOURS OF STANDBY AND 5 MINUTES IN ALARM FOR BATTERY CALCULATIONS. 17. THE FIRE ALARM EVACUATION SIGNAL SHALL SOUND IN A TEMPORAL PATTERN AS PER NFPA 72 2002. Ld D Z Ld Q V) `~W Rgth '�TRFFT SW 70th STREET SITEKEY TO 6001 SW 70th STREET W U Q t1 01 Ln V) NO 4 OATE DESCRIPTION i . i i . i i 0 i ' co L.L) r 0 >� 'ltz (� I.. I J _ J _ i Li_ 0 ...s� 0 W _ I. ! J c....- (� r- < CO f) o < < ,.... I....._ (O I----- < < .� Z z) I...E..J U) I-LJ L..)..J � ....... � z <1 zi < C� F--- < 0- C) Wj C....) W I I U 0 C L.I..J z .. :1b PM � 5 N a z I LaJ 0 � - (J) as p I......_ U) 0-) N t� 0 C -) i r LL_ 0 (\J r .r �....._ i� Li ) C..) 0 C,..) (f) LL_ I..,1 ... L_I_.l LI...J L..- I I J LL.. SHEET 1 /1 4 Vw 7 L=�10