06-1948-004GENERAL ELECTRICAL NOTES:
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING
CODE, NEC AND OTHER APPLICABLE CODES AND STANDARDS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR EVALUATING FIELD CONDITIONS
BY VISITING THE SITE PRIOR TO COMMENCING BIDDING WORK.
3. CONTRACTOR SHALL SCHEDULE WITH OWNER ANY INTERRUPTION OF
POWER
4. APPROVAL SHALL BE OBTAINED FROM A REGISTERED STRUCTURAL
ENGINEER PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT
MEMBER.
5. ALL LOADS EXCEPT GENERAL LIGHTING ARE BEING CONSIDERED NOW
CONTINUOUS LOADS.
6. ALL MATERIAL SHALL BE UL APPROVED.
7. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
8. CIRCUIT DESIGNATIONS ARE SHOWN FOR IDENTIFICATION ONLY. EXISTING
FIELD CONDITIONS WILL DICTATE ACTUAL CIRCUITS TO BE USED.
CONTRACTOR SHALL RECORD ON DRAWINGS THE ACTUAL CIRCUIT USED.
9. ALL PULL BOXES OR JUNCTION BOXES SHALL BE ACCESIBLE AT
ALL TIMES.
10. ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
11. PROVIDE ALL FINAL CONNECTIONS TO ALL EQUIPMENT AND APPLIANCES.
12. BATHROOM RECEPTACLE SHALL BE GFCI PROTECTED.
13. ALL WIRING TO BE THHN INSIDE EMT PIPE OR MC CABLE.
14. HEIGHT OF SWITCHES AND RECEPTACLES SHALL BE CHECKED WITH
ARCHITECT. RECOMMENDED HEIGHTS:
- COUNTER RECEPTACLES AND LAVATORIES: 18" ABOVE COUNTER
- LIGHT SWITCHES: 48" FROM FINISHED FLOOR
15. ALL LUMINAIRIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE
WITH THE CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL
CODE REQUIREMENT.
16. SHORT CIRCUIT AMPERES IS 22 KA FOR PROTECTION DEVICES, BUT
DEFINITIVE VALUE SHALL BE OBTAINED BY ELECTRICAL CONTRACTOR AT
EXECUTION TIME.
17. INDICATED TRACK LIGHTS SHALL BE 6 FEET LONG, BUT MODEL
WILL BE SELECTED BY OWNER AT EXECUTION TIME.
ELECT. LEGEND
Wall Switch 15 A, 125 V
(D= Duplex Receptacle 15 A 125 V
O Incandescent Lighting Fixture
FO Wall Bracket Light
Q Junction Box
--4 PH Phone Outlet
-0 Tv T.V. Outlet
nElectrical Panel
I-fl Disconnecting Switch
SID Smoke Detector
Electrical Meter
H8 Exit Light W/ Battery Back Up
Emergency Light W/ Battery Back Up
l® 1. I KILAL K1 1=K
SCALE: N.T.S.
0
COMMERCIAL MAIN (E) --J F.P.L. SERVICE (E)
SEE ELECTRICAL RISER
EQUAL TO: CUTTLER
HAMMER
ELECTRICAL
PANES
VOLTAGE:
1 0125 V 1 PH. 3W
TYPE:
MA INS
MOUNTING: RECESSED
PE)
TYPE MAINS: MLO
z
PHASE
CIRCUIT
CIRCUIT
PHASE
z
LOAD DESCRIPTION
LOAD DESCRIPTION
Y
A
B
BRK.
P
W
C
C
W
P
BRK.
A
B
1
BATHROOM RECEPTACLE
1500
20
1
12
12
1
20
760
SEWING MACHINE
2
3
SIGN
1200
20
1
12
12
1
20
360
GRAL. RECEPTACLES (2)
4
5
SIGN
1200
20
1
12
12
1
20
900
GRAL. RECEPTACLES (5)
6
7
GRAL. RECEPTACLES (4)
720
20
1
12
12
1
20
900
GRAL. RECEPTACLES (5)
8
9
GRAL. RECEPTACLES (5)
900
20
1
12
12
1
30
1758
C,U,
10
11
GRAL. LIGHT
1400
20
1
12
1758
12
13
TRACK LIGHT (4 X 6 FEET)
1800
20
1
12
6
1
60
5000
A.H.U.
14
15
TRACK LIGHT (4 X 6 FEET)
1800
20
1
12
5000
16
17
18
19
20
C❑NTINU❑US LOAD,
N❑N-C❑NTINU❑US LOAD,
FEEDERI 3C-No. i+ IC -No, 6 THHN, 0 11/2' (ENT)
GRAL, LIGHT = 881 SQF X 3 VA = 2643 VA (TAB.
220,12)
GRAL, RECEPTACLES = 21 X
180
= 3780 VA
(EXISTING TU
2643 VA X 1.25 = 3304 VA (❑MIT)
SEWING MACHINE = 760 VA
_ : Cu N NLLP4 -Gk. r ' 'VEXISTING
LIGHT X 1.25 = 5176 X 1.25 = 6470 VA
AIR C❑NDITI❑NER = 10000 VA
Ia A,rAL0rl0N,
SIGNS X 1.25 = 2 X 1200 X 1.25 = 3000 VASUB-T❑TAL
= 14540 VA
SEE N
SUB-TOTAL = 9470 VA
�..-..
-IT❑TAL DEMANDED LOAD = 24010
VA (115 A)
7(/of�; T%�s rs fj� �irs��,�n� �� fie dJi/aii:il. ��inin:�c��•/ /��,�c/ �'f ���n�,�cie% ��n�,/,.
-�� 670intrlzt C,A/S/v,•J,i �J /ZiGnce c),,/�.
L�1
41
COMMERCIAL PANEL
PARTIAL SITE PLAN
'*'' .
i
0
GROUNDING SYSTEM W/
TWO GROUNDING RODS 1/2" X 10 FEET
SPACED @ 6 FEET MINIMUM
(E)
SW. 69th. ST.
--i--------------------------------- i ----
w
co
Lr�
V)
___ _ _
---1-----------------SW. 70th. ST. ----------t-----
OCATION
MNIIIIII SCALE: N.T.S.
CONDUCTOR SQUEDULE
800 A/ 3PH, 120/208 V (F.P.L. EXISTING SERVICE)
0 1 C-No. 2/0 THWN (E)
0 2 (3C- No. 500MCM + 1(N)- No. 250 MCM + 1(G)- No. 4/0 THWN- 0 4")
® 3C-No. 1 + 1(G) No. 6 THWN, ENT 0 11/2" (EXISTING TUBE ONLY)
F.F.L. FINISHED FLOOR LEVEL
C W.P COLD WATER PIPE (E)
F.P.L. SERVICE
(E)
LIGHTING PLAN C2
SCALE: 1/4" = 1'-0"
0
AHU / ABOVE CLG.
C-9 C 9 C-6 FITTING STOR. o
FITTING ROOM (-
ROOM C-6
C-9 -
C-6 C- 14/16
H.C.RESTROOM
E.P.
C-6 C-6
C-9 C-7
l�P � BT PH OFFICE
RETAIL PH C-7
AREA
C-7
Ito
_ s
t .rlrt&;i ai:4 s' �r�G ..ca.^.-"vc+•:=.a
PARTIAL SITE PLAN
��
Iml
[� : =i='A
mmmmmi
ELECTRICAL PLAN
SCALE: 1 /4" = 1'-0
0
C-4
SEWING C-4
WORKSHOP
C-8 C-2
C-5
BASIL'S
TAILOR
SHOP
SEAL
.. �'➢E�rf.
.,:. ANUELC6T] LEy9y•'?
ELECTRICAL. ENO: #7�9''f
•'k4$35 SW. 25th. LANt':'.,
MIAMI, FL.331 r..,•, ^r
ho.` • 30 883 6200 , u
F :3 3%72
CONSULT,
WRITTEN DIMENSIONS ON THIS DRAWING Sh4LL
HAVE PRECEDENCE OVER SCALED DIMENSIONS.
CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE
FOR ALL DIMENSIONS AND CONDITIONS ON
THE JOB AND THIS OFFICE MUST BE NOTIFIED
OF ANY VARIATION FROM THE DIMENSIONS.
Revisions
D'*
Al,
Project Name:
BASIL'S TAILOR SHOP
INTERIOR REMODELING
6001 SW. 70 ST. UNIT C-103
MIAMI, FLORIDA
File:
Scale:
Date: OCT/ 2006
Drawn: A.P.
Checked:
Submittal:
Drawing Title:
ELECTRICAL PLAN
NOTES
Sheet No. E-1