06-1796-006A/C EQUIPMENT SCHEDULE
UNIT NUMBER
AHU-1
AREA SERVED
SEE FL. PLAN
z
TOTAL SUPPLY AIR CFM
1600
a
OUTSIDE AIR CFM
245
EXTERNAL STATIC PRESS. H
0.5
FAN MOTOR HP FLA
1 2
El Fr. CHAR. V ti
208 10 60
COOL COIL CAP. BTU HR
48,000
TOTAL SENS, HEAT BTU HR
33,500
ENT. AIR TEMP. 'F DB 'F WB
80 67
MODEL NUMBER
--
UNIT MANUFACTURER
RHEEM
i
MODEL NUMBER
R HK- 4
d
WEIGHT LBS.
126
REMARKS: REF. PIPING RS/RL
AS PER MANUF.
z
UNIT NUMBER
CU-1
LOCATION
SEE FL PLAN
AMBIENT TEMP. OF
95
REFRIGERANT R
22
c >
COMP./COND. FAN FLA
ELEC. CHAR. V _.
19.2 1.4 FLA
240 1 60
MANUFACTURER
RHEEM
MODEL NUMBER
RAMC-048JA
WEIGHT LBS.
245
a
REMARKS SEER NOTES
13.0
c�
UNIT MTD. ELEC. HEAT CAP.
10.0 KW
F
STEPS OF ELEC. HEAT NO.
1
=
ELEC. CHAR. V 0
208 10 60
NOTES:
1. PROVIDE ALL AHU'S WITH 7 DAYS PROGRAMMABLE THERMOSTAT.
lNNm
+ AIR COOLED COIDEN m uwr
•
ANGLE VALVE
FLExM11.E CONNECTION
+�
AIR MUM M
a SUCDON LK
++
DX COIL
VALVE
1s2
VALVE W/
L
• SL
MILIALM
• I" LME
+a
MOLE PORT SOff GI.J M
DW
• GM VALVE
GERANT PIPING DIAGRAM
PM m DPGIm TYPICAL PER REFRIUXRw CMICUT FOR Um WITN
NUUM'LE CIRIM
FAN SCHEDULE
UNIT NUMBER
EF-1
AREAS SERVED
BATH
ROOM
LOCATION
CEILING
DUTY SUPPLY/EXH.
EXH.
FAN TYPE
CEIUNG FAN
DRIVE BELT/DIRECT
DIRECT
FAN SPEED RPM
AIR QUANTITY CFM
70
TOTAL STATIC PRESS. H 0
.125
OPENING REQUIRED IN.
-
FAN MOTOR
ELECTRICAL CHAR. V/-/,
115/1/60
MANUFACTURER
BROAN
MODEL NUMBER
671
WEIGHT LBS.
REMARKS SONESI
3.0
NOTES:
1. FAN EF-1 SHALL BE INTERLOCKED TO LIGHT FIXTURES.
2. ALL FANS SHALL BE PROVIDED WITH BACKDRAFT DAMPER
INSULATED ROUND
COLLAR W/
S.A. DUCT MANUAL VOLUME DAMPER
F� IF
L
DRAWBAND
CONNECTOR
BENEATH INSULATION
DIFFUSER OR
GRILLE
INSULATED FLEXIBLE DUCT
INSULATED ROUND
CEILING
INSULATED SQUARE BOX
FOR
SQUARE NECK gp�
IRED WITH REDUCER
TYPICAL CONNECTION TO AIR DIFFUSER
N.T.S.
SOUND INSULATED
HOUSING
ADJUSTABLE
MOUNTING
FLANGE
REMOVABLE
ALUM. CEILING
GRILLE
NARROW WALL TYPE
FIRE BARRIER TYP.'
1/8" PER UNEAR FOOT CLEARENCE FOR N.T.S.
EXPANSION AT TOP AND AT EACH VERTICAL
SIDE
RETAINING ANGLES SIZED ACCORDING TO
"SMACNA7 RECOMMENDATIONS FASTENED
W/2-1/4" BOLTS,6" O.C. TO FD SLEEVE
ONLY
BLADES OUT OF AIR STREAM
ELECTRIC -THERMAL MANUAL UNK
FIRE DAMPER FRAME, FASTENED TO SLEEVE AS
PER F.D. MANUFACTURER'S INSTRUCTION
SHEET METAL DUCTWORK
"S" SUP TYPE CONNECTION ON TOP do
BOTTOM AND DRIVE SLIP AT F.A. SIDE
STEEL PLATE SHALL OVERLAP MASONRY
A MIN. OF 1" ALL AROUND OPENING
DUCT ACCESS PANEL SHALL BE 16"x16",OR MAX. SIZE
DUCT WILL ALLOW,LOCATED WITHIN 12" OF FIRE DAMPER'S
UNK AND LABELED"FIRE DAMPER ACCESS" CONSTRUCTED
IN ACCORDANCE W/SMACNA RECOMMENDATIONS.
WIDE WALL TYPE FIRE BARRIER
NOTES*
APPLY NON -HARDENING SEALANT AT ALL
JOINTS FOR AIR TIGHTNESS.
TYPICAL FIRE DAMPER
WALL MOUNTING DETAIL
N.T.S.
FIRE DAMPERS SHALL BE U.L. CLASSIFIED
DYNAMIC TYPE FIRE DAMPER
FLOW
C \ AIR FLAW
EXHAUST DUCT
CENTRIFUGAL
FAN INSIDE
HOUSING
UST FAN DET
1/4"0 STAINLESS STEEL
CABLE W/ PLASTIC COVER
BOLTED TO STEEL SUPPOR
FRAME W/ 3/8" BOLTS
TO WITHSTAND 150 MPH
HURRICANE FORCE WINDS.
(TYPICAL)
ROOFING
0
AIR
DISTRIBUTION
SCHEDULE
SYMBOL
NECK SIZE
MFGR.
MODEL NUMBER
REMARKS
cc)
FL
TAUS
TDC (24X24 MODULES)
S/A DIF
U,L
FL PLM
BUSKIN
ENE 6M
LOUVER
Q
SEE FIX PLAN
TIRES
ER
R/A OR.
NOTES:
1. REFER TO PLAN FOR QUANTITY, LOCATION AR THROW
PATTERN AND SIZES.
2. ALL AIR DISTRIBUTION DEVICES SHALL BE OF EXTRUDED
ALUMINUM CONSTRUCTION, FURNISH WITH OPPOSED
BLADE DAMPERS AND CONCEALED MOUNTING FRAME
FOR ACOUSTICAL OR PLASTER CEILING INSTALLATION.
HVAC SYMBOL LEGENDi
m
THERMOSTAT
®
ROOF MTD. DR FAN
®
DUCT SMOKE DETECTOR
J�__M
DUCT TURN DOWN
TRANSITION
DUCT TURN UP
TURNING VANE
FLEXIBLE DUCT
9HORIZONTAL
45 BRANCH DUCT TAKE -OFF
EXISTING SUPPLY
FIRE DAMPER
EXISTING RETURN
ttaD.
MANUAL VOLUME DAMPER
®
NEW SUPPLY
ti V`
RETURN REGISTER
®
NEW RETURN
IM
SUPPLY DIFFUSER
V_
FIRE DAB
tm
RETURN AR GRILLE
-do-
VALVE
-►
AIR FLOW DIRECTION
NOTES.
SUPPLY DUCT -n r-RETURN DUCT
CONNECTION
FILTER E
REFRIGERANT
WITH FILTER
UNES
L
CONDENSATE DRAIN TRAP
AIR HANDING
UNIT
m
FOR CONTINUATION SEE
PLUMBING DRAWINGS.
A
DISCONNECT SWITCH
(SEE ELECT DWG.)
24'MIN.
NEOPHRENE PAD ANGLE IRON FREE STANDING
(FOUR CORNERS) SUPPORT SECURE TO AHU THRU
VIBRATION ISOLATORS AND TO
FLOOR W/ BOLT.
THRU BOLT UNIT TO sm-J AFLOAT SWITCH
ANGLE FRAME STAND WIRED IN SERIES
THROUGH VIBRATION ISOLATION WITH T'STAT CIRCUIT
AUXILIARY DRAIN PAN (GALVANIZED SHEET TO SHUT OFF UNIT
18 GA.) PROVIDE FLOAT SWITCH WIRED TO IN CASE OF AN OVERFILL
STOP UNIT UPON OVERFLOW DETECTION. TO DRAIN PAN.
AIR HANDLING UNIT MOUNTING DETAIL
N.T.S.
CONDENSING UNIT
BOLTED TO STEEL SUPPORT
FRAME W/ 3/8" BOLTS
TO WITHSTAND 150 MPH
HURRICANE FORCE WINDS.
(TYPICAL AT UNIT MOUNTING POINTS)
-"'- VIBRATION ISOLATORS (TYP.)
MIAMI-DADE COUNTY APPROVE[
SUPPORT
FOR FLASHING SEE DETAIL
a.. WELD
INSULATION
STL. PLATE
THRU-BOLTS WITH NUTS
MAINTAIN MFR'S RECOMMENDED
CLEARANCES FOR AIRFLOW AND
MAINTENANCE ACCESS
CONC. SLAB
CONDENSING UNIT ROOF
MOUNTING DETAIL
N.T.S.
NOTE:
CONDENSING UNIT SUPPORT FRAME SHALL BE AS MANUFACTURED BY
PRECISION ALUMINUM PRODUCTS, INC., MIAMI-DADE COUNTY APPROVED
NOA No, 02-0514.02 ALUMINUM ALLOY CONSTRUCTION
"0 STAINLESS STEEL
N/PLASTIC COVER
OENSING UNIT
1/4"0 STAINLESS STEEL
CABLE W/ PLASTIC COVER
BOLTED TO STEEL SUPPORT
FRAME W/ 3/8" BOLTS
TO WITHSTAND 150 MPH
HURRICANE FORCE WINDS.
(TYPICAL)
ROOF MOUNTED
EQUIPMENT HEIGHT REQUIREMENTS
WIDTH OF EQUIPMENT HEIGHT OF LEGS
(INCHES)
(INCHES)
UP TO 24
14
25 TO 36
18
37 TO 48
24
49 TO 60
30
61 AND WIDER
48
HVAC GENERAL NOTES
1. CONTRACTOR SWILL COORDINATE WITH LANDLORD REOUIS PRIOR TO
ORDERING AND/OR INSTALLATION OF MY E"MENT AND ACCESSORIES SHOWN.
2, THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE
FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT PERMITS,
FEES, INSPECTIONS, TESTS, INSURANCE, ETC., REQUIRED FOR THE
COMPLETION OF THE AIR CONDITIONING. HEATING AND VENTILATION
SYSTEMS SHOWN ON DRAWINGS OR LISTED BELOW.
3. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW
EVERY BEND, OFF -SET, ELBOWS OR OTHER FITTINGS WHICH MAY BE
REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR
FOR COORDINATION WITH OTHER TRADES.
4. DRAWINGS ARE NOT TO BE SCALED. UNLESS SPECIFIC
DIMENSIONS ARE SHOWN, THE ARCHITECTURAL AND/OR STRUCTURAL
DRAWINGS, AND SITE CONDITIONS SWILL GOVERN EXACT
LOCATION OF MECHANICAL EQUIPMENT AND APPURTENANCES.
5. VERIFY ALL SPACE CONDITIONS & DIMENSIONS AT JOB SITE PRIOR TO
FABRICATION
OF DUCTWORK AND INSTALLATION OF EQUIPMENT AND
ACCES6 A BALANCING CONTRACTOR SHALL ADJUST AND BALANCE AIR DISTRIBU-
71ON DEVICES IN ACCORDANCE WITH QUANTITIES SHOWN ON PLANS FOR
RREEGU�HVAC OPERATION AND FOR REQUIRED BUILDING PRESSURIZATION
7. CONTRACTOR SHALL COORDINATE WITH TENANT SO THAT
ANY EQUIPMENT OR DEVICE TO REMAIN THAT MAY HAVE TO BE
DISCONNECTED BECAUSE OF THE REMOVAL OF ANY OTHER DEVICE
IS RECONNECTED AND TIED BACK TO THE EXISTING BUILDING
SYSTEMS) AND TESTED FOR CORRECT OPERATION.
8. ANY WORK NOT SHOWN ON DRAWINGS OR SPECIFICALLY MENTIONED IN
THE HVAC NOTES BUT CONSIDERED NECESSARY FOR THE COMPLETION
OF THE WORK IN PROPER MANNER SHALL BE PROVIDED BY THE
CONTRACTOR WITHOUT ADDITIONAL CHARGE.
9. COORDINATE SPACE ACCESSIBMY AND WORKING HOURS REQUIREMENTS
WITH OWNER'S REPRESENTATIVE PRIOR TD BIDDING THIS PROJECT.
OTHER AREAS IN THIS OR ADJACENT SPACES MAY HAVE SPECIAL
REQUIREMENTS FOR ACCESSIBILITY TO EXISTING BUILDING SYSTEMS
PRESENTLY IN THEIR SPACES BUT WHICH MAY NEED TO BE ACCESSED
FOR THIS PROJECT.
10. CONTRACTOR SHALT. DO HIS OWN CUTTING AND REMOVAL OF ALL HIS
RELATED WORK IN ALL LOCATIONS WHERE REQUIRED EXCEPT WHERE
OTHERWISE SHOWN ON THE DRAWINGS AND/OR AS SPECIFIED AND/OR
AS COORDINATED WITH TENANTS.
11. ALL BUILDING CONSTRUCTION AFFECTED BY THE REMOVAL, RELOCATION,
INSTALLATION OF ANY PIECE OF EQUIPMENT SHALL BE REPAIRED AND
REFINISHED AS REQUIRED TO MATCH EXISTING CONDITIONS OR AS
DIRECTED BY THE ARCHITECTURAL DRAWINGS AND/OR SPECIFICATIONS.
12. DUCTWORK:
A. VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES,
DUCT CONSTRUCTION, BRACING AND SUSPENSION IN ACCORDANCE WITH
THE RECOMMENDATIONS SET FORTH IN THE LATEST EDITION OF THE
A.S.H.RAE. GUIDE AND S.MAC.NA STANDARDS. DUCT SIZES SHOWN
ARE INSIDE" DIMENSIONS. VERIFY EXACT LOCATION OF DUCT WITH
RESPECT TO STRUCTURE BEFORE FABRICATION.
B. AR CONDITIONING SUPPLY AND RETURN DUCTWORK SHALL BE 1-1/2"
(R-6 MIN.) FIBERGLASS U.L 181 LISTED, CLASS I AIR DUCT.
DUCTWORK SHALL BE FABRICATED IN ACCORDANCE WITH S.MAC.NA
STANDARDS.
C. FLEXIBLE DUCT SHALL BE STEEL HELIX WIRE ON 7/8" CENTERS,
ENCAPSULATED IN A CONTINUOUS SOFT VNYL FILM, JOINED BY MOLECULAR
WELDING TO FORM AN AR TIGHT INNER CORE, THE CORE IS TO BE
INSULATED WITH FIBERGLASS INSULATION (R-6), AND SHEATHED IN A
REINFORCED, ALUMINUM METALIZED POLYESTER VAPOR BARRIER JACKET.
PROVIDE SPIN COLLAR WITH BAILER AND EXTRACTOR WHERE FLEXIBLE
DUCT IS CONNECTED TO RECTANGULAR DUCTWORK. DAMPER ACTUATOR
SHALL BE EXTENDED OUTSIDE INSULATION.
13. AIR DISTRIBUTION:
A. SUPPLY AND RETURN AR DIFFUSERS SHALL BE OF EXTRUDED
EXTRUDED ALUMINUM CONSTRUCTION OR AS SPECIFIED.
14. PROVIDE ACCESS PANELS IN WALLS OR CEILING FOR DAMPERS, CONTROL
DEVICES, ETC. ACCESS PANELS SHALL BE MI.COR FLUSH TYPE
COORDINATE LOCATION WITH ARCHITECT.
15. SUBMIT SHOP DRAWINGS OF ALL MATERIALS. DUCTWORK AND EQUIPMENT
FOR REVIEW PRIOR INSTALLATION AND/OR FABRICATION.
16. ALL EQUIPMENT AND MATERIELS SWILL BE GUARANTEED FOR THE
PERIOD OF ONE YEAR. PERIOD OF GUARANTEE SFWl COMMENCE
UPON RECEIPT OF CERTIFICATE OF OCCUPANCY.
17. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2001 FLORA
BUILDING CODE
18. SUBMIT A COMPLETE "AS -BUILT" RECORD SET IN REPRODUCIBLE PAPER
SEPIA FORM TO ARCHITECT/ENGINEER FOR REVIEW PRIOR TO FINAL
PAYMENT REQUISITION.
19. TESTING:
A. BALANCE AIR SYSTEM TO DELIVER SPECIFIED AR QUANTITIES AT
EACH OUTLET WITHIN 10% USING AA.B.C. PROCEDURES AND
TESTS. SUBMIT AIR BALANCE TEST RESULTS FOR REVIEW PRIOR
TO FINAL INSPECTION AND ACCEPTANCE.
20. ALL HVAC EQUIPMENT, AIR DISTRIBUTION, CONTROLS, APPURTENANCES, ETC.
SHALL BE AS SHOWN ON THE DRAWINGS WITH RESPECT TO CAPACITY,QUAUTY
PERFORMANCE,ACCESSORIES,ETC.MANUFACTURERS USED FOR THE BASIS OF
DESIGN ARE LISTED ON THE DRAWINGS SCHEDULES OR SPECIFIED HEREIN.
SUBSTITUTIONS MUST MEET OR EXCEED ALL SPECIFIED REQUIREMENTS.
NAMING ACCEPTABLE MANUFACTURERS DOES NOT RELIEVE THE CONTRACTOR
FROM COMPLIANCE WITH ALL DESIGN REQUIREMENTS SHOWN ON THE
DRAWINGS OR LISTED HEREIN.
21. ALL INSULATION PRODUCTS AND ACCESSORIES SHALL HAVE A FLAME SPREAD
RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50 OR
LESS IN ACCORDANCE WITH ASTM E84.
22. SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENT FOR
APPROVAL PRIOR TO FABRICATION.
23. TEMPERATURE CONTROL SHALL. BE A PROGRAMMABLE ROOM THERMOSTAT FOR
HEATING/COOLING WITH STAGES AS REQUIRED.
24. VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER
RECOMMENDATIONS TO ELIMINATE ANY EQUIPMENT NOISE FROM BEING
HEARD.
25. GUARANTEES:
A. ALL COMPRESSOR MOTORS ON NEW EQUIPMENT FURNISHED UNDER
THIS CONTRACT SHALL HAVE A MIN. 5 YEARS PRODUCT GUARANTEE FROM
DATE OF START-UP.
B. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP
FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN A 1 YEAR
FROM DATE OF ACCEPTANCE
26. TESTING:
A ALL REFRIGERANT HIGH SIDE PIPING TO 300 PSIG. LOW SIDE
TO 150 PSIG. AFTER TESTING EVACUATE SYSTEM TO 28%
MERCURY GAUGE PRESSURE WN VACUUM PUMP. HOLD FOR 25
HOURS WITH PUMP OFF BREAK VACUUM WITH REFRIGERANT.
27. ALL CONDENSATE PIPING SHALL BE COPPER DWV. INSULATE COND. PIPES
ABOVE GROUND WITH 3/4 INCH ARMAFLEX INSULATION.
AM Consulting Engineers LLC
Certificate OF Authorization #9692
r Jose If. lfulinez, P.B. #56018
:MR SDuth Dine HWY. Suite 209 TEL (305) 255-1621
;MiwL Florida 33156 FAX (305) 29-1732
TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED
HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE
APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF
'JMM CONSULTING ENGINEERS LLC' AND IS AN INSTRUMENT OF SERVICE NOT TO BE
REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION
OF JAM CONSULTING ENGINNERS• LLC.
�
Q
min
0
m
m
�Q
a
cc
W
-
4
aW
c
SON
Z
W
V)
CO)
cc
a
1H
y�
Uj 400
H ,
Q
O�
oil
oa
i
DATE : KALE :
09-21-" 1/4• - T
DA1! SUWM M FOR ■ M
DRAINNO NO :
M-2 OF 2