06-1796-006A/C EQUIPMENT SCHEDULE UNIT NUMBER AHU-1 AREA SERVED SEE FL. PLAN z TOTAL SUPPLY AIR CFM 1600 a OUTSIDE AIR CFM 245 EXTERNAL STATIC PRESS. H 0.5 FAN MOTOR HP FLA 1 2 El Fr. CHAR. V ti 208 10 60 COOL COIL CAP. BTU HR 48,000 TOTAL SENS, HEAT BTU HR 33,500 ENT. AIR TEMP. 'F DB 'F WB 80 67 MODEL NUMBER -- UNIT MANUFACTURER RHEEM i MODEL NUMBER R HK- 4 d WEIGHT LBS. 126 REMARKS: REF. PIPING RS/RL AS PER MANUF. z UNIT NUMBER CU-1 LOCATION SEE FL PLAN AMBIENT TEMP. OF 95 REFRIGERANT R 22 c > COMP./COND. FAN FLA ELEC. CHAR. V _. 19.2 1.4 FLA 240 1 60 MANUFACTURER RHEEM MODEL NUMBER RAMC-048JA WEIGHT LBS. 245 a REMARKS SEER NOTES 13.0 c� UNIT MTD. ELEC. HEAT CAP. 10.0 KW F STEPS OF ELEC. HEAT NO. 1 = ELEC. CHAR. V 0 208 10 60 NOTES: 1. PROVIDE ALL AHU'S WITH 7 DAYS PROGRAMMABLE THERMOSTAT. lNNm + AIR COOLED COIDEN m uwr • ANGLE VALVE FLExM11.E CONNECTION +� AIR MUM M a SUCDON LK ++ DX COIL VALVE 1s2 VALVE W/ L • SL MILIALM • I" LME +a MOLE PORT SOff GI.J M DW • GM VALVE GERANT PIPING DIAGRAM PM m DPGIm TYPICAL PER REFRIUXRw CMICUT FOR Um WITN NUUM'LE CIRIM FAN SCHEDULE UNIT NUMBER EF-1 AREAS SERVED BATH ROOM LOCATION CEILING DUTY SUPPLY/EXH. EXH. FAN TYPE CEIUNG FAN DRIVE BELT/DIRECT DIRECT FAN SPEED RPM AIR QUANTITY CFM 70 TOTAL STATIC PRESS. H 0 .125 OPENING REQUIRED IN. - FAN MOTOR ELECTRICAL CHAR. V/-/, 115/1/60 MANUFACTURER BROAN MODEL NUMBER 671 WEIGHT LBS. REMARKS SONESI 3.0 NOTES: 1. FAN EF-1 SHALL BE INTERLOCKED TO LIGHT FIXTURES. 2. ALL FANS SHALL BE PROVIDED WITH BACKDRAFT DAMPER INSULATED ROUND COLLAR W/ S.A. DUCT MANUAL VOLUME DAMPER F� IF L DRAWBAND CONNECTOR BENEATH INSULATION DIFFUSER OR GRILLE INSULATED FLEXIBLE DUCT INSULATED ROUND CEILING INSULATED SQUARE BOX FOR SQUARE NECK gp� IRED WITH REDUCER TYPICAL CONNECTION TO AIR DIFFUSER N.T.S. SOUND INSULATED HOUSING ADJUSTABLE MOUNTING FLANGE REMOVABLE ALUM. CEILING GRILLE NARROW WALL TYPE FIRE BARRIER TYP.' 1/8" PER UNEAR FOOT CLEARENCE FOR N.T.S. EXPANSION AT TOP AND AT EACH VERTICAL SIDE RETAINING ANGLES SIZED ACCORDING TO "SMACNA7 RECOMMENDATIONS FASTENED W/2-1/4" BOLTS,6" O.C. TO FD SLEEVE ONLY BLADES OUT OF AIR STREAM ELECTRIC -THERMAL MANUAL UNK FIRE DAMPER FRAME, FASTENED TO SLEEVE AS PER F.D. MANUFACTURER'S INSTRUCTION SHEET METAL DUCTWORK "S" SUP TYPE CONNECTION ON TOP do BOTTOM AND DRIVE SLIP AT F.A. SIDE STEEL PLATE SHALL OVERLAP MASONRY A MIN. OF 1" ALL AROUND OPENING DUCT ACCESS PANEL SHALL BE 16"x16",OR MAX. SIZE DUCT WILL ALLOW,LOCATED WITHIN 12" OF FIRE DAMPER'S UNK AND LABELED"FIRE DAMPER ACCESS" CONSTRUCTED IN ACCORDANCE W/SMACNA RECOMMENDATIONS. WIDE WALL TYPE FIRE BARRIER NOTES* APPLY NON -HARDENING SEALANT AT ALL JOINTS FOR AIR TIGHTNESS. TYPICAL FIRE DAMPER WALL MOUNTING DETAIL N.T.S. FIRE DAMPERS SHALL BE U.L. CLASSIFIED DYNAMIC TYPE FIRE DAMPER FLOW C \ AIR FLAW EXHAUST DUCT CENTRIFUGAL FAN INSIDE HOUSING UST FAN DET 1/4"0 STAINLESS STEEL CABLE W/ PLASTIC COVER BOLTED TO STEEL SUPPOR FRAME W/ 3/8" BOLTS TO WITHSTAND 150 MPH HURRICANE FORCE WINDS. (TYPICAL) ROOFING 0 AIR DISTRIBUTION SCHEDULE SYMBOL NECK SIZE MFGR. MODEL NUMBER REMARKS cc) FL TAUS TDC (24X24 MODULES) S/A DIF U,L FL PLM BUSKIN ENE 6M LOUVER Q SEE FIX PLAN TIRES ER R/A OR. NOTES: 1. REFER TO PLAN FOR QUANTITY, LOCATION AR THROW PATTERN AND SIZES. 2. ALL AIR DISTRIBUTION DEVICES SHALL BE OF EXTRUDED ALUMINUM CONSTRUCTION, FURNISH WITH OPPOSED BLADE DAMPERS AND CONCEALED MOUNTING FRAME FOR ACOUSTICAL OR PLASTER CEILING INSTALLATION. HVAC SYMBOL LEGENDi m THERMOSTAT ® ROOF MTD. DR FAN ® DUCT SMOKE DETECTOR J�__M DUCT TURN DOWN TRANSITION DUCT TURN UP TURNING VANE FLEXIBLE DUCT 9HORIZONTAL 45 BRANCH DUCT TAKE -OFF EXISTING SUPPLY FIRE DAMPER EXISTING RETURN ttaD. MANUAL VOLUME DAMPER ® NEW SUPPLY ti V` RETURN REGISTER ® NEW RETURN IM SUPPLY DIFFUSER V_ FIRE DAB tm RETURN AR GRILLE -do- VALVE -► AIR FLOW DIRECTION NOTES. SUPPLY DUCT -n r-RETURN DUCT CONNECTION FILTER E REFRIGERANT WITH FILTER UNES L CONDENSATE DRAIN TRAP AIR HANDING UNIT m FOR CONTINUATION SEE PLUMBING DRAWINGS. A DISCONNECT SWITCH (SEE ELECT DWG.) 24'MIN. NEOPHRENE PAD ANGLE IRON FREE STANDING (FOUR CORNERS) SUPPORT SECURE TO AHU THRU VIBRATION ISOLATORS AND TO FLOOR W/ BOLT. THRU BOLT UNIT TO sm-J AFLOAT SWITCH ANGLE FRAME STAND WIRED IN SERIES THROUGH VIBRATION ISOLATION WITH T'STAT CIRCUIT AUXILIARY DRAIN PAN (GALVANIZED SHEET TO SHUT OFF UNIT 18 GA.) PROVIDE FLOAT SWITCH WIRED TO IN CASE OF AN OVERFILL STOP UNIT UPON OVERFLOW DETECTION. TO DRAIN PAN. AIR HANDLING UNIT MOUNTING DETAIL N.T.S. CONDENSING UNIT BOLTED TO STEEL SUPPORT FRAME W/ 3/8" BOLTS TO WITHSTAND 150 MPH HURRICANE FORCE WINDS. (TYPICAL AT UNIT MOUNTING POINTS) -"'- VIBRATION ISOLATORS (TYP.) MIAMI-DADE COUNTY APPROVE[ SUPPORT FOR FLASHING SEE DETAIL a.. WELD INSULATION STL. PLATE THRU-BOLTS WITH NUTS MAINTAIN MFR'S RECOMMENDED CLEARANCES FOR AIRFLOW AND MAINTENANCE ACCESS CONC. SLAB CONDENSING UNIT ROOF MOUNTING DETAIL N.T.S. NOTE: CONDENSING UNIT SUPPORT FRAME SHALL BE AS MANUFACTURED BY PRECISION ALUMINUM PRODUCTS, INC., MIAMI-DADE COUNTY APPROVED NOA No, 02-0514.02 ALUMINUM ALLOY CONSTRUCTION "0 STAINLESS STEEL N/PLASTIC COVER OENSING UNIT 1/4"0 STAINLESS STEEL CABLE W/ PLASTIC COVER BOLTED TO STEEL SUPPORT FRAME W/ 3/8" BOLTS TO WITHSTAND 150 MPH HURRICANE FORCE WINDS. (TYPICAL) ROOF MOUNTED EQUIPMENT HEIGHT REQUIREMENTS WIDTH OF EQUIPMENT HEIGHT OF LEGS (INCHES) (INCHES) UP TO 24 14 25 TO 36 18 37 TO 48 24 49 TO 60 30 61 AND WIDER 48 HVAC GENERAL NOTES 1. CONTRACTOR SWILL COORDINATE WITH LANDLORD REOUIS PRIOR TO ORDERING AND/OR INSTALLATION OF MY E"MENT AND ACCESSORIES SHOWN. 2, THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT PERMITS, FEES, INSPECTIONS, TESTS, INSURANCE, ETC., REQUIRED FOR THE COMPLETION OF THE AIR CONDITIONING. HEATING AND VENTILATION SYSTEMS SHOWN ON DRAWINGS OR LISTED BELOW. 3. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW EVERY BEND, OFF -SET, ELBOWS OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES. 4. DRAWINGS ARE NOT TO BE SCALED. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE ARCHITECTURAL AND/OR STRUCTURAL DRAWINGS, AND SITE CONDITIONS SWILL GOVERN EXACT LOCATION OF MECHANICAL EQUIPMENT AND APPURTENANCES. 5. VERIFY ALL SPACE CONDITIONS & DIMENSIONS AT JOB SITE PRIOR TO FABRICATION OF DUCTWORK AND INSTALLATION OF EQUIPMENT AND ACCES6 A BALANCING CONTRACTOR SHALL ADJUST AND BALANCE AIR DISTRIBU- 71ON DEVICES IN ACCORDANCE WITH QUANTITIES SHOWN ON PLANS FOR RREEGU�HVAC OPERATION AND FOR REQUIRED BUILDING PRESSURIZATION 7. CONTRACTOR SHALL COORDINATE WITH TENANT SO THAT ANY EQUIPMENT OR DEVICE TO REMAIN THAT MAY HAVE TO BE DISCONNECTED BECAUSE OF THE REMOVAL OF ANY OTHER DEVICE IS RECONNECTED AND TIED BACK TO THE EXISTING BUILDING SYSTEMS) AND TESTED FOR CORRECT OPERATION. 8. ANY WORK NOT SHOWN ON DRAWINGS OR SPECIFICALLY MENTIONED IN THE HVAC NOTES BUT CONSIDERED NECESSARY FOR THE COMPLETION OF THE WORK IN PROPER MANNER SHALL BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE. 9. COORDINATE SPACE ACCESSIBMY AND WORKING HOURS REQUIREMENTS WITH OWNER'S REPRESENTATIVE PRIOR TD BIDDING THIS PROJECT. OTHER AREAS IN THIS OR ADJACENT SPACES MAY HAVE SPECIAL REQUIREMENTS FOR ACCESSIBILITY TO EXISTING BUILDING SYSTEMS PRESENTLY IN THEIR SPACES BUT WHICH MAY NEED TO BE ACCESSED FOR THIS PROJECT. 10. CONTRACTOR SHALT. DO HIS OWN CUTTING AND REMOVAL OF ALL HIS RELATED WORK IN ALL LOCATIONS WHERE REQUIRED EXCEPT WHERE OTHERWISE SHOWN ON THE DRAWINGS AND/OR AS SPECIFIED AND/OR AS COORDINATED WITH TENANTS. 11. ALL BUILDING CONSTRUCTION AFFECTED BY THE REMOVAL, RELOCATION, INSTALLATION OF ANY PIECE OF EQUIPMENT SHALL BE REPAIRED AND REFINISHED AS REQUIRED TO MATCH EXISTING CONDITIONS OR AS DIRECTED BY THE ARCHITECTURAL DRAWINGS AND/OR SPECIFICATIONS. 12. DUCTWORK: A. VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES, DUCT CONSTRUCTION, BRACING AND SUSPENSION IN ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE LATEST EDITION OF THE A.S.H.RAE. GUIDE AND S.MAC.NA STANDARDS. DUCT SIZES SHOWN ARE INSIDE" DIMENSIONS. VERIFY EXACT LOCATION OF DUCT WITH RESPECT TO STRUCTURE BEFORE FABRICATION. B. AR CONDITIONING SUPPLY AND RETURN DUCTWORK SHALL BE 1-1/2" (R-6 MIN.) FIBERGLASS U.L 181 LISTED, CLASS I AIR DUCT. DUCTWORK SHALL BE FABRICATED IN ACCORDANCE WITH S.MAC.NA STANDARDS. C. FLEXIBLE DUCT SHALL BE STEEL HELIX WIRE ON 7/8" CENTERS, ENCAPSULATED IN A CONTINUOUS SOFT VNYL FILM, JOINED BY MOLECULAR WELDING TO FORM AN AR TIGHT INNER CORE, THE CORE IS TO BE INSULATED WITH FIBERGLASS INSULATION (R-6), AND SHEATHED IN A REINFORCED, ALUMINUM METALIZED POLYESTER VAPOR BARRIER JACKET. PROVIDE SPIN COLLAR WITH BAILER AND EXTRACTOR WHERE FLEXIBLE DUCT IS CONNECTED TO RECTANGULAR DUCTWORK. DAMPER ACTUATOR SHALL BE EXTENDED OUTSIDE INSULATION. 13. AIR DISTRIBUTION: A. SUPPLY AND RETURN AR DIFFUSERS SHALL BE OF EXTRUDED EXTRUDED ALUMINUM CONSTRUCTION OR AS SPECIFIED. 14. PROVIDE ACCESS PANELS IN WALLS OR CEILING FOR DAMPERS, CONTROL DEVICES, ETC. ACCESS PANELS SHALL BE MI.COR FLUSH TYPE COORDINATE LOCATION WITH ARCHITECT. 15. SUBMIT SHOP DRAWINGS OF ALL MATERIALS. DUCTWORK AND EQUIPMENT FOR REVIEW PRIOR INSTALLATION AND/OR FABRICATION. 16. ALL EQUIPMENT AND MATERIELS SWILL BE GUARANTEED FOR THE PERIOD OF ONE YEAR. PERIOD OF GUARANTEE SFWl COMMENCE UPON RECEIPT OF CERTIFICATE OF OCCUPANCY. 17. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2001 FLORA BUILDING CODE 18. SUBMIT A COMPLETE "AS -BUILT" RECORD SET IN REPRODUCIBLE PAPER SEPIA FORM TO ARCHITECT/ENGINEER FOR REVIEW PRIOR TO FINAL PAYMENT REQUISITION. 19. TESTING: A. BALANCE AIR SYSTEM TO DELIVER SPECIFIED AR QUANTITIES AT EACH OUTLET WITHIN 10% USING AA.B.C. PROCEDURES AND TESTS. SUBMIT AIR BALANCE TEST RESULTS FOR REVIEW PRIOR TO FINAL INSPECTION AND ACCEPTANCE. 20. ALL HVAC EQUIPMENT, AIR DISTRIBUTION, CONTROLS, APPURTENANCES, ETC. SHALL BE AS SHOWN ON THE DRAWINGS WITH RESPECT TO CAPACITY,QUAUTY PERFORMANCE,ACCESSORIES,ETC.MANUFACTURERS USED FOR THE BASIS OF DESIGN ARE LISTED ON THE DRAWINGS SCHEDULES OR SPECIFIED HEREIN. SUBSTITUTIONS MUST MEET OR EXCEED ALL SPECIFIED REQUIREMENTS. NAMING ACCEPTABLE MANUFACTURERS DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH ALL DESIGN REQUIREMENTS SHOWN ON THE DRAWINGS OR LISTED HEREIN. 21. ALL INSULATION PRODUCTS AND ACCESSORIES SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50 OR LESS IN ACCORDANCE WITH ASTM E84. 22. SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENT FOR APPROVAL PRIOR TO FABRICATION. 23. TEMPERATURE CONTROL SHALL. BE A PROGRAMMABLE ROOM THERMOSTAT FOR HEATING/COOLING WITH STAGES AS REQUIRED. 24. VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER RECOMMENDATIONS TO ELIMINATE ANY EQUIPMENT NOISE FROM BEING HEARD. 25. GUARANTEES: A. ALL COMPRESSOR MOTORS ON NEW EQUIPMENT FURNISHED UNDER THIS CONTRACT SHALL HAVE A MIN. 5 YEARS PRODUCT GUARANTEE FROM DATE OF START-UP. B. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN A 1 YEAR FROM DATE OF ACCEPTANCE 26. TESTING: A ALL REFRIGERANT HIGH SIDE PIPING TO 300 PSIG. LOW SIDE TO 150 PSIG. AFTER TESTING EVACUATE SYSTEM TO 28% MERCURY GAUGE PRESSURE WN VACUUM PUMP. HOLD FOR 25 HOURS WITH PUMP OFF BREAK VACUUM WITH REFRIGERANT. 27. ALL CONDENSATE PIPING SHALL BE COPPER DWV. INSULATE COND. PIPES ABOVE GROUND WITH 3/4 INCH ARMAFLEX INSULATION. AM Consulting Engineers LLC Certificate OF Authorization #9692 r Jose If. lfulinez, P.B. #56018 :MR SDuth Dine HWY. Suite 209 TEL (305) 255-1621 ;MiwL Florida 33156 FAX (305) 29-1732 TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF 'JMM CONSULTING ENGINEERS LLC' AND IS AN INSTRUMENT OF SERVICE NOT TO BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF JAM CONSULTING ENGINNERS• LLC. � Q min 0 m m �Q a cc W - 4 aW c SON Z W V) CO) cc a 1H y� Uj 400 H , Q O� oil oa i DATE : KALE : 09-21-" 1/4• - T DA1! SUWM M FOR ■ M DRAINNO NO : M-2 OF 2