06-1154-003ELECTRICAL NOTES:
PART 1 - GENERAL:-
I.- THE GENERAL AND SPECIAL CONDITION AND REQUIREMENTS OF THE CONTRACT AND
SPECIFICATION AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND
TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFI-
CATION AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE
FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS.
2.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE
WITH —THE LATEST EDITION OF NEC (IN SPECIAL SEC. 680),FBC, NFPA, NEMA, IEEE; OTHER
APPLICABLE NATIONAL STATE & LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY
AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER
RECOGNIZED STANDARDS WHERE "PART 1 - GENERAL" THE REQUIREMENTS ARE MORE
STRINGENT THAN THOSE CITED ABOVE.
3.- WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST
CLASS MANNER AND SHALL BE COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE
OF THE ARCHITECT/ENGINEER.
4.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS, BEARING THE UNDER-
WRITER S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE
AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR
ON PLANS. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE DELIVERY SCHEDULES
OF MATERIALS.
5.- DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT
LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL; PLANS SHALL
NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS,
FITTINGS AND ACCESSORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, WORKING INSTALLATION.
6.- SUPPLEMENTAL MATERIALS OR MANUFACTURED PRODUCTS NECESSARY TO COMPLY
WITH THE INTENT OF THE CONTRACT DRAWINGS OR SPECIFICATIONS, BUT NOT NOTED
OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED AS REQUIRED TO COMPLETE
THE INATALLATION AT NOT ADDITIONAL COST TO THE OWNER.
7 - EXISTING CONDITION: CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL
EXISTING CONDITIONS, WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL
NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING
CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION
FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIA-
TELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. CORRECTION OF
ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY
HAVE BEEN DAMAGED THEREBY.
8 - PERMITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES. TAXES, INSPECTION,
TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE
ELECTRICAL SYSTEM AS OUTLINED HERE IN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED
INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR
THE DURATION OF THE WORK.
9 - INTERFERENCE: PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SIIALL
COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES, SO THAT INTERFERENCES
WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL. STRUCTURAL
AND WORK WITH OTHER TRADES WILL BE AVOIDED.
PART 2 - PRODUCTS:
1 - DISCONNECT SWITCHES FOR POOL AREA SHALL BE QUICK -MADE, QUICK -BRAKE ACTION,
LOCKABLE TYPE PER "NEC 680-12".
2 - CONDUCTORS SHALL BE THW/THWN SOFT -DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN
CONDUIT, COLOR CODED PER "NEC AND TRADE STANDARDS. MINIMUM SIZE SHA.11 BE #12
FOR POWER WIRING AND #14 FOR CONTROL CIRCUITS. PROVIDE #10 WIRES FOR 120V POWER
CIRCUIT HOMERUNS LONGER THAN 100 FEET. ASIDE FROM THE PANELBOARD GUTTER,
CONDUCTORS ON THE LOAD SIDE OF A GFCI MUST NOT BE USED IN ANY RACEWAY OR OTHER
ENCLOSURE CONTAINING CONDUCTORS THAT ARE NOT GFCI-PROTECTED.
3 - CONDUIT SHALL BE "RGS" OR "IMC" HOT -DIPPED GALVANIZED FOR ALL EXTERIOR LOCATIONS,
WHERE EXPOSED TO PHYSICAL DAMAGE. ALL FITTING SHALL BE STEEL. "PVC" SCHEDULE
40 SHALL BE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS; "PVC" MAY BE RUN
UNDERGROUND WHERE BURIED 18" BELOW FINISHED GRADE, 24" UNDER VEHICULAR TRAFFIC
AREAS. GREENFIELD TYPE FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR MOTORS AND
VIBRATING EQUIPMENT CONNECTIONS, NOT TO EXCEED 18"; PROVIDE "PVC" JACKETED TYPE
FOR EXTERIOR AND/OR MOISTURE EXPOSED LOCATIONS. FOR UNDERWATER LIGHTING FIXTURES
AS PER "NEC 680-20.
4 - CONNECT ALL SMOKE DETECTORS AHEAD OF SWITCHES THRU BATHROOMS OR KITCHEN
CIRCUIT. SMOKE DETECTORS SHALL OPERATE AT 120V AND HAVE BATTERY BACK-UP.
5 - THIS CONTRACTOR SHALL COORDINATE WITH FP&L THE CONNECTION FOR THIS SERVICE
AND REVISE INTERRUPTING CAPACITY AVAILABLE PRIOR INSTALLATION OF ALL DISCONNECTING
DEVISES, AND INCREASE THE INTERRUPTING CAPACITY IN PANELS AND DISCONNECTING DEVISES
IF REQUIRED.
PART 3 - EXECUTION:
1 - CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS
AND PARTITIONS; NO RACEWAYS SHALL BE EXPOSED WITHIN INTERIOR SPACES EXCEPT FOR
OPEN CEILING AREAS.
2 - GROUNDING AND BONDING SHALL COMPLY WITH "NEC 250, 680-24 & 25". ALL PIETALLIC
RACEWAYS SHALL BE GROUNDED AND BONDED PER "NEC 250". NON-METALLIC RACEWAYS
SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER "NEC 250-95". PROVIDE
1#8 SOLID BOUNDING CONDUCTOR TO CONNECT ALL METAL PARTS AT THE POOL SUCH AS
POOL REINFORCE STEEL, METAL JB'S, PUMP MOTORS, METAL CONDUITS, LIGHTING FIXTURES,
METAL SHIELD PRIMARY AND SECONDARY WINDING OF POOL TRANSFORMERS, POOL STAIRS,
ETC. TO COMPLY WITH 1996 NEC CODE SECTION 680-22.
3 - MOTORS, TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH GREENFIELD
FLEXIBLE CONNECTIONS, WATERLIGHT WHERE EXPOSED TO MOISTURE AND WEATHER CONDITIONS.
OTORS TRANSFORMERS AND MECHANICAL EQUIPMENT FOR THE POOL AND JACUZZI PER
EC 6$0-42.
4 - OUTLETS AND ANY OTHER EQUIPMENT INSTALLED IN POOL AREA SHALL BE INSTALL AT A
MINNIMUN DISTANCE OF 10'-0" FROM POOL'S EDGE OR AS PER 1999 NEC CODE SECTION 680.
GENERAL NOTE:
ALL ELECTRICAL OUTLETS ON DEMISE FIRE
RATED PARTITIONS SHALL NOT BE LOCATED
BACK-TO-BACK BUT WITH A MINIMUM DISTANCE
OF 24" IN BETWEEN.
ELECTRICAL LIGHTING FLOOR PlANI
SCALE: 1/4"=V-0'
SCOPE OF WORKS
NEW RETAIL SPACE AT EXISTING
BUILDING.
THIS CONTRACTOR SHALL PROVIDE
AND INSTALL 3 # 1 /0 THW CU IN 2"
CONDUIT FROM PANEL TO EXISTING
SWITCHGEAR. APPROXIMATE
DISTANCE 150 FT.
PROVIDE AND INSTALL 150 AMPS,
208V BREAKER AT SWITCHGEAR.
FIRE ALARM SPECIAL NOTE
THIS CONTRACTOR SHALL
COORDINATE WITH LANDLORD
REQUIREMENTS FOR FIRE ALARM
AND COORDINATE WITH THE FIRE
ALARM CONTRACTOR THE ADDITION
OF THE NEW DIVISES SHOWN ON
THIS DRAWING
COORDINATE EXACT
LOCATION AT FIELD
FOR CU.
/,38/10
2r—;,240V
,NE�,iA� 3R
(ON ROOF)
_ ... : w► COORDINATE EXACT LOCATION FOR SIGN WITH LANDLORD
O NOs��1LA12M
�T.
MJAM1-DADS 00UN Y FIRH 0EFIREATVAE'�J�r ELECTRICAL POWER FLOOR PLAN PERTMS 1DRawIN
B�t� �hat.r �. SCALE: 1/4"=1'-7 BEFOR s`�T?,I L TI0�1fIgr. SUPPAESSiO:4 �� Vim Alarm. ContraC'Car'S «crl n pl_u�s 8$ali
be swim ifatpermit approval to :41iarnni-
Dude County Fire Depwtinerit.
Approved for Building Permit Onlyt
Date ��!/._._- =—'i-�
TYPE: ITE MAIN BUS: 150 AMPS
PANEL
SERVICE: 10, 3W NEUTRAL: FIN
VOLTAGE: 120/208 V. 42 KAIC MAIN: M.L.O.
MOUNTING: FLUSH LOCATION: WALL
K/VOLT
POLE
TRIP
CONDUIT
WIRE
REMARKS
CKT.
CKT.
REMARKS
WIRE
CONDUIT
TRIP
POLE
K/VOLT
AMP
NO.
NO.
AMPS.
1.50
1
20
3/4"
#12
SIGN **
1
2
LIGHTS
#12
3/4"
20
1
1.20
1.00
1
20
3/4"
#12
RESTROOM & EXIT SIGN LIGHTS
3
4
AHU W/7.5 KW HEATER *
#8
i"
40
2
8.00
1.20
1
20
3/4"
#12
LIGHTS
5
6
1.00
1
20
3/4"
#12
RECEPTACLES
7
8
GU *
#10
3/4"
30
2
6.25
--
--
--
--
--
SPACE
9
10
--
--
--
--
--
SPACE
11
12
RECEPTACLES
#12
3/4"
20
1
1.50
--
--
--
--
--
SPACE
13
14
RECEPTACLES
#12
3/4"
20
1
1.60
--
--
--
--
---
SPACE
15
16
SPACE
---
---
---
---
1.50
--
--
--
--
--
SPACE
17
18
SPACE
---
---
---
---
1.50
--
--
--
--
--
SPACE
19
20
SPACE
--
--
--
--
--
SPACE
21
22
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
23
24
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
25
26
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
27
28
SPACE
--
--
--
--
--
SPACE
29
30
SPACE
4.70 TOTAL TOTAL CONNECTED LOAD: 26.15 KVA TOTAL 21.45
* NON COINCIDENT
** PROVIDE & INSTALL TIMER/CLOCK I=126 AMPS
COORDINATE LOCATION AT FIELD
DANIEL F. G UTIERREZ, P. E. 3360 CORAL WAY
LIC. ,J049086 SUITE 15 MMMI FL 33145
PH. (305)461-3178
FAX (306)461-8229
D 1127 "
CONSULTING ENGINEERS, INC.
.DIGN
H
W
Q
H
Q
O
�
NW
O
M
�
I`
a
N�
w
�
w
w
Cf)
E
H
O
�4
F-,
project no.
date: 05/22/06
drawn by: WA
checked by:Di:
approved by:DFG
REVISIONS
no./item/date
SHEET
E - 1
1 OF 1
---I