06-1154(2)-005GENERAL PLUMBING NOTES
1. ALL WORK TO BE DONE IN ACCORDANCE WITH THE FLORIDA
BUILDING CODE AND LOCAL ORDINANCES.
2. BUILDING DRAINAGE SYSTEM TO BE SLOPED AT 1/8" PER FT. MIN. FALL. ANY
DEVIATIONS SHALL BE APPROVED BY ARCHITECT/ENGINEER. ,
3. PROVIDE CLEANOUTS EVERY 75 FT. AND AT BASE OF EVERY WASTESTACK.
ALL CLOSEOUTS TO BE FLUSH MOUNTED.
4. MATERIALS SHALL BE ALL NEW AND AS FOLLOWS:
A. DRAINAGE WASTE AND VENT PIPING INCLUDING GREASE
WASTE; PVC DRAINAGE WASTE AND PIPING (DWV) CONFORMING TO
ASTM D-2665, NO HUB CAST IRON CISPI STANDARD 301 ABOVE
GROUND AND CAST IRON HUB, PLAIN END ASTM A-74 WITH NEO-
PRENE GASKETS UNDERGROUND.
B. WATER PIPING: COPPER TYPE "L" ASTM B-88 ABOVE GROUND AND
COPPER TYPE "K" ASTM B-88 UNDERGROUND.
C. CONDENSATE DRAIN PIPING: COPPER TYPE "M" ASTM B-88 INSIDE
THE BUILDING AND PVC SCHEDULE 40 ABOVE ROOF AND UNDERGROUND.
PROVIDE 1/2" ARMAFLEX PIPE INSULATION TO ALL CONDENSATE DRAIN
PIPING.
D. FLOOR DRAINS (IF REQUIRED): JOSAM SERIES 30,000 OR EQUAL EXCEPT AT
TRANSFORMER VAULT WHICH SHALL BE JOSAM SERIES 32,000 OR EQUAL.
KITCHEN FLOOR DRAIN: JOSAM 35420-50, 12" SQUARE NHCALOY TOP, SATIN
FINISH, 1/2" PRIMER CONNECTION, BRONZE SEDIMENT BUCKET.
E. FLOOR CLEANOUTS: JOSAM SERIES 56020 OR EQUAL.
F. WALL CLEANOUTS: JOSAM SERIES 58750 WITH ACCESS COVER OR EQUAL.
G. VALVES: 125 PSI NIBCO SCOTT, STOCKHAM OR EQUAL
H. HOSE BIBBS: CHICAGO 837 OR EQUAL WITH VACUUM BREAKER.
I. ELECTRIC WATER HEATER: GLASS -LINED, P & T RELIEF VALVE, 5 YEAR
WARRANTY MINIMUM.
5. PERFORM THE FOLLOWING TEST:
A. WATER PIPING SHALL BE SUBJECTED TO HYDROSTATIC PRESS TEST OF
100 PSIG FOR A PERIOD OF TIME SUFFICIENT TO EXAMINE E TIRE SYSTEM
BUT NOT LESS THAN ONE HOUR.
B. DRAINAGE SYSTEM: BEFORE INSTALLATION OF ANY DRAINS, 'I E END OF THE
SYSTEM SHALL BE CAPPED & ALL LINES FILLED WITH WATER TO HIGHEST
POINT & ALLOWED TO STAND UNTIL INSPECTION IS MADE AhT WATER TZVELS
REMAIN CONSTANT.
C. CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTS.
D. COMPLETE SYSTEM FIXTURE & EQUIPMENT SHALL BE GIVEN .:21 IN-SERVICE
TEST AFTER COMPLETION OF THE INSTALLATION.
E. STERILIZE ALL WATER LINES WITH A MIXTURE OF (2) POUND33 OF CHLORINATED
LIME TO EACH 1000 gal. OF WATER (50 PPM OF AVALIBLE CHLORINE.) RETAIN
MIXTURE IN PIPES FOR 24 HOURS AND FLUSH THROUGHLY . TH POTABLE WATER
BEFORE PLACING IN SERVICE.
6. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING
WORK SHALL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSIiIP FOR A PERIOD
OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE, AND THAT HE WILL, AT HIS EXPENSE,
REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING GUARANTEE PERIOD.
7. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION OF EXISTING U'PILITIES AND POINTS OF
CONNECTION BEFORE COMMENCING ANY WORK.
8. PLUMBING CuIMP14CTOR SHALL PAY ALL FEES, INSPECTION AND CONNECTION
CHARGES REQUIREL.
9. SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL EQUIPMENT,
MATERIALS AND LAYOUTS PRIOR INSTALLATION.
10.OFFSET PIPING AS REQUIRED TO CLEAR BUILDING STRUCTURE, DUCTWORK, ETC.
AS SHOWN ON DRAWINGS AND AS REQUIRED BY FIELD CONDITIONS.
11. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL A/C CONDESAIE DRAIN
AND TRAP. SEE A/C PLANS FOR LOCATION OF UNITS AND DARINS.
12.PLUMBING CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AND LIMENSIONS
AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT.
13.000RDINATE WORK WITH OTHER TRADES.
14.FURNISH AND INSTALL FIXTURES AS SPECIFIED IN SCHEDULE IF PROVIDED, OTHERWISE
PROVIDE SHOP DRAWINGS.
15.EACH BATHROOM GROUP AND KITCHEN SHALL BE PROVIDE WITH AIR CHAMBERS OR SHOCK
ABSORBER AS PER S.F.B.C.
I6.PROVIDE SHUT-OFF VALVE FOR EACH FIXTURE, JUST BEFORE CONNECTING TO FIXTURE.
17.WHEREVER DISSIMILAR METALS ARE TO BE JOINED, A DIELECTRIC FITTING
SHALL BE PROVIDED TO CONNECT BOTH TYPES OF PIPES.
18.MECHANICAL CONTRACTOR SHALL COORDINATE AND VERIFY HEIGHT AND LOCATION OF
STUB -UPS.
19.REFER TO SUPPLIER DRAWING AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND COORDINATION OF EQUIPMENT TERMINATION DETAILS.
20.PROVIDE AT REFRIGERATOR LOCATION: 3/8" C.W. LINE TO 1/4" PETCOCK 6" ABOVE
FLOOR . FURNISH 48" OF 1/4" SOFT COPPER TUBING FOR CONNECTION TO REFRIGERATOR .
21. PROVIDE ANTI SCALD AT ALL TUB AND SHOWERS.
2"VTR
,—
PLUMBING SYMBOLS
S- • — - — • -S
COLD WATER PIPE
f---S
HOT WATER PIPE
'Q
WATER HAMMER ARRESTOR
n
AIR CHAMBER
HB
HOSE BIBB W / VACUUM BREAKER
AND SHUT-OFF VALVE
S S
SANITARY LINE
S C.D. S
CONDENSATE LINE
WCO
WALL CLEANOUT
FCO
FLOOR CLEANOUT
GATE VALVE ( SHUT-OFF
VALVE )
Sr' - j ►♦�
WATER METER
"(2FU)
3 "(4
33"(9FU)»�I
PLUMBING FIXTURE CONNECTION SCHEDULE
MARK
DESCRIPTION
FU'S
WASTE
C.W.
B.W.
REIfARK3/SPECS
P-1
WATER CLOSET
3
S.
1/2.
-
FLOOR MOUNTED. FLUSH TANK
P-2
BATHTUB
2
2'
1/2'
1/2"
5 FT. LONG. PRESSURE BALANCING FAUCET
P-2A
SHOWER
2
2"
1/2'
1/2-
PRESS. BALANCING FAUCET.
P-3
LAVATORY
1
1 1/2'
1/2"
1 1/2'
COUNTER TOP
P-3A
LAVATORY
1
1 1/2'
1/2'
1/2"
FLOOR MOUNTED
P-4
KITCHEN SDLI(
2
1 1/2'
1/2'
1/2'
COUNTER TOP
P-5
DISH WASHER
1 1/2"
1/2'
1/2-
__------
P-8
WASHER (RESIDENTIAL)
2
2'
1/2'
1/2'
WATER SUPPLY VALVE & DRAIN IN RECESSED
BOX WALL MOUNTED.
P-7
BIDET
4
2'
3/4'
--
----------
P-8
REFRIGERATOR
I --
--
1 1/2-
--
----------
NOTE : CONTRACTOR TO COORDINATION PLUMBING FIXTURE SELECTION, WITH OWNER/ ARCHITECT FOR FIXTURE AND
FAUCET STYLE & COLOR.
NOTE-
2- PIPE & LESS • 1/4- SLOPE
3- PIPE & MORE • 1/8- SLOPE
SCOPE OF WORKS
INSTALATION OF NEW BATHROOM:
THE DRAIN LINES AND VENTS ARE
EXISTING BY LAND LORD
EXISTING 4" PIPE
PROVIDE FOR
BATHROOM,MAX. FU
PERMITED 10 FU
CONDENSATE DRAIN NOTE:
THIS CONTRACTOR SHALL
EXTEND THE %it
CONDENSATE DRAIN FOR
THE AHU PIPE TO
DISCHARD AT EXISTING 2".
COORDINATE EXACT
LOCATION FOR 2" PIPE AT
FIELD.
ii
PLUMBINGDRAIN FLOOR PLAN
SCALE:1/4"=1'-0'
EXISTING 4" PIPE PROVIDE FOR BATHROOM
MAXI FU PERMITED 10 FU
12 " VENT
4N"'� L.-.�
2"(2FU)
LAV
WC0
WC
3""(4FU)
/ 3"(9FU)
3"(4FU)
F DQ��1] 6#)we
SANITARY RISER
DMaEL F. GUTIERREZ, P. E
LIC #049066 SUITE #5 WAX FL 33145
{ 78
FAX (3 5)461 8229
DI=G
- = CON.SULFING ENGF)" INC.
_TDx.S'SGN i'ION.S'
�o
coco
�"-4...
c
co
•
�
�w
A
a�
~
C>
,4r'
wCO
�
w
O
co
W
� cfl
0? O
O
Z
��
�
rD
o
Z
�
O �
O
O
co
f
C)
z14
W
A
O
a
Cl)
C
coH
f�
I�
w
O
�
L-4
CD
�
project no.
date: 05/22/06
drawn by: WA
checked by:DFG
approved by:DFG
REVISIONS
no./item/date
SHEET
P.1
1 OF 1