06-1154(2)-003ELECTRICAL NOTES:
PART 1 - GENERAL:
1.- THE GENERAL AND SPECIAL CONDITION AND REQUIREMENTS OF THE CONTRACT AND
SPECIFICATION AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND
TRADES SHALL APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFI-
CATION AND THE ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE
FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS.
2.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE
ITH THE LATEST EDITION OF NEC (IN SPECIAL SEC. 680),FBC, NFPA, NEMA, IEEE; OTHER
APPLICABLE NATIONAL STATE & LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY
AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER
RECOGNIZED STANDARDS WHERE "PART 1 - GENERAL" THE REQUIREMENTS ARE MORE
STRINGENT THAN THOSE CITED ABOVE.
3.- WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST
CLASS MANNER AND SHALL BE COMPLETED AND FULLY OPERATIVE TO THE ACCEPTANCE
OF THE ARCHITECT/ENGINEER.
4•- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS, BEARING THE UNDER-
WRITER S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE ACCEPTABLE
AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR
ON PLANS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE DELIVERY SCHEDULES
OF MATERIALS.
5.- DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE EQUIPMENT
LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL; PLANS SHALL
NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. PROVIDE ALL OFFSETS,
FITTINGS AND ACCESSORIES REQUIRED FOR A COMPLETE, ACCEPTABLE, ITORKING INSTALLATION.
6.- SUPPLEMENTAL MATERIALS OR MANUFACTURED PRODUCTS NECESSARY TO COMPLY
WITH THE INTENT OF THE CONTRACT DRAWINGS OR SPECIFICATIONS, BUT NOT NOTED
OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED AS REQUIRED TO COMPLETE
THE INATAU A77ON AT NOT ADDITIONAL COST TO THE OWNER.
7 - EXISTING CONDITION: CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL
EXISTING CONDITIONS, WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WELL
NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING
CONDITIONS RESULT IN EXTRA MATERIAL OR LABOR. ANY EXISTING CONDITION
FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIA-
TELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. CORRECTION OF
ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY
HAVE BEEN DAMAGED THEREBY.
8 - PERMITS: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES. TAXES, INSPECTION,
TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF A COMPLETE
ELECTRICAL SYSTEM AS OUTLINED HERE IN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED
INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR
THE DURATION OF THE WORK
9 - INTERFERENCE: PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL
COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES, SO THAT EIIERFERENCES
WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL STRU•',TIJRAL
AND WORK WITH OTHER TRADES WILL BE AVOIDED.
1 - DISCONNECT SWITCHES FOR POOL AREA SHALL BE QUICK -MADE, A"- ON,
LOCKABLE TYPE PER "NEC 680-12".
2 - CONDUCTORS SHALL BE THW/THWN SOFT -DRAWN 98% CONDUCTIVITY COPPER INSTALLED IN
CONDUIT, COLOR CODED PER "NEC" AND TRADE STANDARDS. MINIMUM SIZE SHALL BE 12
FOR POWER WIRING AND #14 FOR CONTROL CIRCUITS. PROVIDE #10 WI14ES FOR 120V DOWER
CIRCUIT HOMERUNS LONGER THAN 100 FEET. ASIDE FROM THE PANELBOARD GUTTER,
CONDUCTORS ON THE LOAD SIDE OF A GFCI MUST NOT BE USED IN A1,P1 RACEWAY OR OTHER
ENCLOSURE CONTAINING CONDUCTORS THAT ARE NOT GFCI-PROTECTED.
3 - CONDUIT SHALL BE "RGS" OR "IMC" HOT -DIPPED GALVANIZED FOR ALL EXTERIOR LOCATIONS,
WHERE EXPOSED TO PHYSICAL DAMAGE. ALL FITTING SHALL BE STEEL. "PVC" SCHEDULE
40 SHALL BE USED WHERE CONDUIT IS RUN IN CONCRETE SLABS; "PVC" MAY BE RUN
UNDERGROUND WHERE BURIED 18" BELOW FINISHED GRADE, 24" UNDER VEHICULAR TRAFFIC
AREAS. GREENFIELD TYPE FLEXIBLE METALLIC CONDUIT SHALL BE USED FOR MOTORS AND
_ - VIBRATING EQUIPMENT CONNECTIONS, NOT TO EXCEED 18"; PROVIDE "PVC" JACKETED TYPE
FOR iia;n`'�.�_R_ AND/ MOISTURE EXPOSED LOCATIONS. FOR UNDERWATH LIGHTING FIXTURES
AS PER "NEC 680-20.
4 - CONNECT ALL SMOKE DETECTORS AHEAD OF SWITCHES THRU BATHROOMS OR KITCHEN
CIRCUIT. SMOKE DETECTORS SHALL OPERATE AT 120V AND HAVE BATTERY BACK-UP.
5 - THIS CONTRACTOR SHALL COORDINATE WITH FP&L THE CONNECTION FOR THIS SERVICE
AND REVISE INTERRUPTING CAPACITY AVAILABLE PRIOR INSTALLATION 07 ALL DISCONNECTING
DEVISES, AND INCREASE THE INTERRUPTING CAPACITY IN PANELS AND DISCONNECTING DEVISES
IF REQUIRED.
PART 3 - EXECUTION:
1 - CONDUIT RUNS, RACEWAYS AND PIPING SHALL BE CONCEALED IN WALLS, CEILINGS, SLABS
AND PARTITIONS; NO RACEWAYS SHALL BE EXPOSED WITHIN INTERIOR SPACES EXCEPT FOR
OPEN CEILING AREAS.
2 - GROUNDING AND BONDING SHALL COMPLY WITH "NEC 250, 680-24 & 25". ALL METALLIC
RACEWAYS SHALL BE GROUNDED AND BONDED PER "NEC 250". NON-METALLIC RACEWAYS
SHALL BE PROVIDED WITH A GROUNDING CONDUCTOR SIZED PER "NEC 250-95". PROVIDE
1#8 SOLID BOUNDING CONDUCTOR TO CONNECT ALL METAL PARTS AT THE POOL SUCH AS
POOL REINFORCE STEEL, METAL JB'S, PUMP MOTORS, METAL CONDUITS, LIGHTING FIXTURES,
METAL SHIELD PRIMARY AND SECONDARY WINDING OF POOL TRANSFORMERS, POOL STAIRS,
ETC. TO COMPLY WITH 1996 NEC CODE SECTION 680-22.
3-- MOTORS, TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH GREENF]EL D
FLEXIBLE CONNECTIONS, WATERUGHT WHERE EXPOSED TO MOISTURE AND WEATHER CONDITIONS.
WMOTORS TRANSFORMERS AND MECHANICAL EQUIPMENT FOR THE POOL AND JACUZZI PER
C 6�0-42 .
4 - OUTLETS AND ANY OTHER EQUIPMENT INSTALLED IN POOL AREA SHALL BE INSTALL AT A
MINNIMUN DISTANCE OF 10'-0" FROM POOL'S EDGE OR AS PER 1999 NEC CODE SECTION 680.
GENERAL NOTE:
AIL, ELECTRICAL OUTLETS ON DEMISE FIRE
RATED PARTITIONS SHALL NOT BE LOCATED
BACK-TO-BACK BUT WITH A MINIMUM DISTANCE
OF 24" IN BETWEEN.
ELECTRICAL LIGHTING FLOOR PLAN
SCALE: 1/4"=V-0"
SCOPE OF WORKS
NEW RETAIL SPACE AT EXISTING
BUILDING.
THIS CONTRACTOR SHALL PROVIDE
AND INSTALL 3#1/0 THW CU IN 2"
CONDUIT FROM PANEL TO EXISTING
SWITCHGEAR. APPROXIMATE
DISTANCE 150 FT.
PROVIDE AND INSTALL 150 AMPS,
208V BREAKER AT SWITCHGEAR.
FIRE ALARM SPECIAL NOTE
THIS CONTRACTOR SHALL
COORDINATE WITH LANDLORD
REQUIREMENTS FOR FIRE ALARM
AND COORDINATE WITH THE FIRE
ALARM CONTRACTOR THE ADDITION
OF THE NEW DIVISES SHOWN ON
THIS DRAWING
COORDINATE EXACT
LOCATION AT FIELD
FOR CU.
z3U/120
0V30;.4
EM3R
ON ROOF)
)
L�� DEPPTNMNT
MVO 1 4DADB Go �� F? Ft AW ��
SLAG. PER"""-`q;6101 t.1p►N EXT•s�
' ARE SU?PRESS10t1.r-.�- �y/�
. ATFe
COORDINATE EXACT LOCATION FOR SIGN WITH LANDLORD
ELECTRICAL POWER FLOOR PLAN
SCALE: 1/4"=11-0" DO NOT INSTALL FIRE AI ARM
PER THIS DRAWI1`-JG!
BEFORE Pi 1,STALLATTON
Fire Alarm contractor's worldni; ph nsns shall
be submitted for permit approwd to Nlian i-
Dade County Fire Department.
Approved for Building Permit only!
Date - P
TYPE: ITE PANEL MAIN BUS: 150 AMPS
SERVICE: 10, 3W NEUTRAL: FIN
VOLTAGE: 120/208 V. 42 KAIi; MAIN: M.L.O.
MOUNTING: FLUSH LOCATION: WALL
K/VOLT
POLE
TRIP
CONDUIT
WIRE
REMARKS
CKT.
CKT.
REMARKS
WIRE
CONDUIT
TRIP
POLE
K/VOLT
AMP
N0.
N0.
AMPS.
1.50
1
20
3/4"
#12
SIGN **
1
2
LIGHTS
#12
3/4"
20
1
1.20
1.00
1
20
3/4"
#12
RESTROOM &EXIT SIGN LIGHTS
3
4
AHU W/7.5 KW HEATER *
#8
1"
40
2
8.00
1.20
1
20
3/4"
#12
LIGHTS
5
6
1.00
1
20
3/4"
#12
RECEPTACLES
7
8
CU *
#10
3/4"
30
2
6.25
--
--
--
--
--
SPACE
9
10
--
--
--
--
--
SPACE
11
12
RECEPTACLES
#12
3/4"
20
1
1.50
--
--
--
--
--
SPACE
13
14
RECEPTACLES
#12
3/4"
20
1
1.50
--
--
--
--
--
SPACE
15
16
SPACE
---
---
---
---
1.50
--
--
--
--
--
SPACE
17
18
SPACE
---
---
---
---
1.50
--
--
--
--
--
SPACE
19
20
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
21
22
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
23
24
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
25
26
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
27
28
SPACE
---
---
---
---
---
--
--
--
--
--
SPACE
29
30 1
SPACE
---
---
---
---
---
4.70 TOTAL TOTAL CONNECTED LOAD: 26.15 KVA TOTAL 21.45
* NON COINCIDENT
** PROVIDE & INSTALL TIMER/CLOCK I=126 AMPS
COORDINATE LOCATION AT FIELD
DANIEL F. GUTIERREZ, P.E. 3360 CORAL WAY
LTC. 11049086 SUITE 15 ML4MI FZ 33145
PH.- (305)461-3178
LN=4G FAX (305)461-8229
CONSULTING ENGINEERS, INC.
.D.2✓S'IGN - INSP.2✓CTIONS
H
V
z
W
Q
~
Q
O
w
E�
d+
�
O
H
E" 1
Z
�D
O
H
I- l
C0
project no.
date: 05/22/06
drawn by: WA
checked by:DFG
approved by:DFG
REVISIONS
no./item/date
SHEET
E-1
1 OF 1