06-1789-013SPLIT SYSTEM SCHEDULE AIR HANDLING UNIT AIR COOLED CONDENSING UNIT SYSTEM DATA PLAN MODEL CFM � ESP FAN HEATER WT PLAN MODEL WT COMPRESSOR FAN UNIT MAX CAPACITY SEER REF. LINES ELECTRICAL TOTAL 1 OA HP KW STEP LBS QTY. I TONS I FLA QTY FLA TMBH SMBH SUCTION1 LIQUID VOLTS-PH-HZ MARK NO. MARK NO. LBS MCA FUSE AHU-1 TWEO42P13FB 1,400 250 0.5 16 9.6 1 150 CU-1 TTPO42C100A 245 1 1 5 1 16.0 1 1.9 32 50 42.0 1 28.7 12.0 7/8 1 3/8 240/1/60 SPLIT SYSTEM NOTES. 1. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 79'FDB. 2. PROVIDE A/C UNITS WITH PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH ON -OFF SWITCH SUB -BASE, (WIRED AND INSTALLED BY ELECTRICAL CONTRACTOR) 3. SIZE AND RUN REFRIGERANT PIPING AS MANUFACTURER'S PUBLISHED RECOMMENDATIONS. 4. PROVIDE PROPER VIBRATION ISOLATORS AS PER ISOLATION MANUFACTURER'S RECOMMENDATIONS. PROVIDE FILTER RACK UNDER AHU. RETURN AIR THRU LOUVERED DOOR UNLESS OTHERWISE NOTED. 5. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" FIRE RETARDANT ARMAFLEX. 6. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. 7. PROVIDE BUILT-IN DISCONNECT WITH ALL AIR HANDLING UNITS. IAO - VENTILATION DESIGN CRITERIA OElm Owfiliff, am mu vQrrurrrcll+i RATE vwn Amm CASHEIR/OFFICE 1 NO 20 20 LUNCH/ALT 3 YES 15 23 SHOW ROOM 1 NO 0.3 CFM/SQ. FT. 181 AHU-1 (TOTAL) 16 224 NOTES: 1. DESIGN BASED ON THE VENTILATION RATE PROCEDURE PER ASHRAE STANDARD 62. 2, THE DESIGN WILL NEED TO BE RE-EVALUATED IF, AT A LATER TIME, CHANGES OCCUR IN THE USAGE OF THE SPACE, OR IF UNUSUALLY STRONG SOURCES OF SPECIFIC CONTAMINANTS ARE INTRODUCED INTO THE SPACE. 3. FOR AREAS WITH PEAK OCCUPANCIES OF LESS THAN THREE HOURS DURATION, THE 50% RULE APPLIES PER ASHRAE STANDARD 62, PARAGRAPH 6.1.3.4. 0, WAC FMUIRES: m NO DUCT SMOKE DETECTOR X FIRE DAMPER(S) X SMOKE DAMPER(S) X FIRE RATED ENCLOSURE EXISTING X FIRE RATED ROOF/ FLOOR CEILING ASSEMBLY X FIRE STOPPING X SMOKE CONTROL X AIR DISTRIBUTION SCHEDULE MARK CFM NECK FACE SIZE DESCRIPTION SIZE LENGTH A 000-110 60 24x24 SUPPLY DIFFUSER 111-240 80 24x24 BASIS OF DESIGN: TITUS TDCA-AA 241-420 100 24x24 COLOR: WHITE 421-620 120 24x24 MATERIAL: ALUMINUM 621-750 140 24x24 OPPOSED BLADE DAMPERS: NO 751-980 160 24x24 BACK PAN SIZE: 18x18 B 000-110 6x6 24x24 RETURN / EXHAUST GRILLE 111-220 8x8 24x24 BASIS OF DESIGN: TITUS 350FL 221-350 10x10 24x24 COLOR: WHITE 351-530 12x12 24x24 MATERIAL: ALUMINUM 531-730 14x14 24x24 OPPOSED BLADE DAMPERS: NO 731-970 16x16 24x24 35' DEFLECTION 971-1240 18x18 24x24 1241-1540 20x2O 24x24 1541-1880 22x22 24x24 NOTES: 1. AIR DISTRIBUTION DEVICES LOCATED WITHIN ACOUSTICAL TILE CEILINGS SHALL BE PROVIDED WITH BORDER TYPE 3 FOR LAY -IN MOUNTING. AIR DISTRIBUTION DEVICES LOCATED WITHIN GYPSUM BOARD CEILINGS OR WALLS SHALL BE PROVIDED WITH BORDER TYPE 1 FOR SURFACE MOUNTING. REFER TO ARCHITECTURAL DOCUMENTS FOR CEILING TYPES. 2. AIR DISTRIBUTION DEVICES LOCATED IN SMALL ROOMS WHERE FULL 24"x24" GRID ARE NOT AVAILABLE SHALL BE PROVIDED WITH SURFACE MOUNTING BORDERS IN LIEU OF LAY -IN. SECURE EACH DEVICE TO CEILING GRID WITH FIELD -FABRICATED SUPPORTS. HVAC DRAWING INDEX SHEET DESCRIPTION ISSUED M1.0 M2.0 HVAC - LEGEND, GENERAL NOTES do DRAWING INDEX HVAC - FLOOR PLANS, LEGEND, SCHEDULES AND DRAWING INDEX Yes Yes -. r•• w F w w w � V W • • • • i V VVUir • • i • • • V V Y r • • • r • • • • *woo G • • • f • • f f • • f • • • i • • • • • r• r r • r w •• w f 00 •••• rr••• •r• •r•r r••• • M • • • • • • r r • • • • • • r wrrr f •r••r • •�s• • •rrr • - - --------.. - ............................. _ ITTI�TTIi FITTIGRO -------------------- {M ROOM ROOM - BATIK S T � REF�IC�t�JT PIPES IN CEILING SPACE- T O R. r^� _ �.... ROBS tt� LHROO :AHU-1 '' ' A 300 REF 0 KEYED NOTES 2424 RETURN AIR GRILLE MOUNTED IN WALL BELOW AHU. PROVIDE DUCTWORK FROM GRILLE TO TIE INTO RETURN AIR PLENUM BELOW AHU. EXHAUST AIR DUCTWORK UP IN EXISTING SHAFT TO EXISTING EXHAUST FAN ON ROOF EXHAUST FAN TO BE BALANCED FOR TOTAL EXHAUST FROM ALL SPACE SERVRED BY FAN. VERIFY IN THE FIELD 12x12 TRANSFER AIR GRILLES W/8" O SQUARE TO ROUND TRANSITION BACKPLATE. <3> REFRIGERANT PIPE UP IN EXISTING SHAFT TO LQACTION OF', NEW ACCU-1 ON ROOF. ACCU TO BE MOUNTED ON EXISTING STAND PROVIDED. SEEIDRAWING M2.0 FOR MOUNTING DETAILS. A 300 SHOW ROOM PLAN - SCALE: 1/4,)_1,-o„ HVAC SYMBOL LEGEND HVAC ABBREVATIONS SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION UP DN AFF --ABOVE FINISHED FLOOR UT -LEAVING AIR TEMPERATURE -CHANGE OF ELEVATION AFR -ABOVE FINISHED ROOF LWT -LEAVING WATER TEMPERATURE -FIRE DAMPER -OUTSIDE AIR DUCT UP THROUGH SLAB W/FAN (WITH ACCESS PANEL) AHU -AIR HANDLING UNIT MBH -THOUSAND BTUs PER HOUR ON ROOF ABOVE -FLEXIBLE DUCT BHP -BRAKE HORSEPOWER MCA -MINIMUM CIRCUIT AMPS -FIRE k SMOKE DAMPER MOCP -MAXIMUM OVER CURRENT PROTECTION -CEILING DIFFUSER, ROUND NECK (WITH ACCESS PANEL) BTU-BRITISH THERMAL UNIT (CEILING DIFFUSERS ARE 4-WAY THROW UNO) MOD MOTOR OPERATED CONTROL DAMPER (MOD) -CENTER LINE -MOTOR OPERATED CONTROL DAMPER (MOD) -TRANSITION, ECCENTRIC NITS -N,OT TO SCALE f -CFM (CUBIC FEET PER MINUTE) .OUTSIDE �+ -CEILING RETURN M 10x8 -TRANSITION, SQUARE TO ROUND CD -CEILING DIFFUSER AIR CV -CONSTANT AIR VOLUME 0AL -OUTSIDE AIR LOUVER -.. ® -CEILING EXHAUST -MANUAL BALANCING DAMPER -SQUARE THROAT ELBOW CFM -CUBIC FEET PER MINUTE `PSI ___-POU_ND5 PER-SQUAREIINCH W/TURNING VANES PSIG -PSI GAUGE -CEILING DIFFUSER, RECTANGULAR OR CU -CONDENSING UNIT -UNDERCUT DOOR DN -DOWN RA --RETURN AIR SQUARE NECK (CEILING DIFFUSERS RPM -REVOLUTIONS PER MINUTE ARE 4-WAY THROW UNb) EAT -ENTERING AIR TEMPERATURE -SQUARE THROAT TEE ESP -EXTERNAL STATIC PRESSURE RS/L -REFRIGERANT SUCTION do LIQUID LINES -REVISION REFERENCE�III -FLEXIBLE CONNECTION FD -FIRE DAMPER SA -SUPPLY AIR � -DETAIL REFERENCE: TOP - DETAIL ; EWT -ENTERING WATER TEMPERATURE SP -STATIC PRESSURE M-1 BOTTOM - DRAWING1 SHOWN ON 241.21 -NEW DUCTWORK FIRST DIMENSION IS SIDE SHOWN FF -FINAL FILTERS TSP -TOTAL STATIC PRESSURE Q -THERMOSTAT/TEMPERATURE SENSOR 12x8 -RADIUS TEE FLA -FULL LOAD AMPS LINO -UNLESS NOTED OTHERWISE -HUMIDISTAT/HUMIDITY SENSOR -DUCT ELBOW, POSITIVE PRESSURE (SUPPLY) FPM -FEET PER MINUTE V/PH -VOLTS/PHASE �- -DUCT SMOKE DETECTOR DOWN UP W/IN FLOOR KW -KILOWATT OP -CHANCE IN PRESSURE -RECTANGLE-TO-ROUND TAKE -OFF AT -CHANGE IN TEMPERATURE -CONNECT TO EXISTING -DUCT ELBOW, EXHAUST �-- -DEMOLISH TO POINT INDICATED -DUCT ELBOW, NEGATIVE PRESSURE, RETURN -STANDARD BRANCH TAKE -OFF HVAC EQUIPMENT TAGS �M --- -MOTORIZED CONTROL DAMPER T[] -TEMPERATURE SENSOR Q� -DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE -SPIN-IN TAKE -OFF TAG -RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE, -SHEET NOTE CALLOUT B SUPPLY OR OUTSIDE AIR -AIR DISTRIBUTION DEVICE �1 ---� -SHEET NOTE CALLOUT -RECTANGULAR DUCT SECTION UP, CFM NEGATIVE PRESSURE, RETURN -SHEET NOTE CALLOUT -RECTANGULAR DUCT SECTION UP, EXHAUST AHU NUMBER AHU-1 -AIR HANDLING UNIT IM A10910t" DOM OOMM m N m" AYE MAN / LI 3n �Y•yy/�� rM lM 14 EA4M►NUEL o UCHF, uc No : AR-00 001"TM M �F— M W ton I..L 0 � W Z� O S Q M V < - z Z z Ln ZzjFW-- „i w 0 7— u w 3 D 06 cn 0 .r.J W V Cn W LLI � __j I— Z � .< 0- me O O L "'a � •� •n I' J lilt p� 1 A� FNWT Na � P. IEI = P. lllN1 o r. u 01/bly 3HU MUM M1.0 Or. 2