05-1298(2)-054i
120'24OV PANEL "A,. 200M.L.O.
1 PH,3W SURFACE MTD
BRANCH CIRCUITS
LOCATION
WIRE AND
CONDUIT
TOTAL
BREAKER
TRIP
CKT
NO.
CKT
NO.
BREAKER
TRIP
TOTAL
WIRE AND
CONDUIT
LOCATION
VA
VA
ENTRY
#12-1/2'C
*
1P-20
1
2
1P-20
16M
412-124C
DINING REC.
FOYER
3
4
16W
APPLIANCES
LIVING ROOM
5
6
1600
APPLIANCES
LIVING ROOM
7
8
1600
APPLIANCES
HALLWAY
9
10
1000
DISHWASHER
VIDEO ROOM
11
12
800
G. DISPOSAL
13
14
1600
MICROWAVE
15
16
2P
3000
2#8,1#10
OVEN
17
18
40
3000
1#10 GRD-3/4'C
#12.112"C
TRASH COMPACTOR
D.R. / BREEZEWAY
19
20
1P-20
1000
PLAY ROOM
21
22
1 P-20
1000
SPARE
PLAY ROOM
23
24
2P
5600
2 #4.1-C
AHU No. 1
OFFICE
25
26
60
65W
(10 KW)
27
28
2P
(3000)
2 #6-3/4'C
C.U. No. t
-
29
30
60
(3000)
31
32
1P'20
1000
#12-12'C
DISHWASHER
33
34
900
#12-12"C
SPARE
BATH RECEPT.
35
36
900
SPARE
SPACE
37
38
SPACE
39
40
11
41
42
11
* 2400 S.F.
7200
SUBTOTAL
7200
TOTAL = 38,300
31,100
SUBTOTAL
(a) AFCI C/9
A/C @ 100%- 4200
HEAT @ 65'A=7150
DEMAND LOAD :s 27.3 KW
FIRST 10 KW @ 100 %
17.3KW@40%
A/C
(a)
(a)
(a)
120240V PANEL " B" 200 M.L.O.
1 PH,3W SURFACE MTD
BRANCH CIRCUITS
LOCATION
WIRE AND
CONDUIT
TOTAL
BREAKER
TRIP
CKT
NO.
CKT
NO.
BREAKER
TRIP
TOTAL
WIRE AND
CONDUIT
LOCATION
VA
VA
WASHER
#12-12'C
1500
1P-20
1
2
2P
6500
2#4-1'C
AHIU No.2
G. OPENER
600
3
4
60
65W
(101 KW)
G. OPENER
600
5
6
2P
(2000)
2 #8-3f4"C
CUI NO.2
GARAGE
1000
7
8
60
(2000)
GUEST ROOM
*
9
10
2P
6000
3 #8-3/4'C
W.LH. No.1
GUEST
ROOM
*
11
12
40
6000
TERRACE
*
13
14
2P
Y5M
3#10-12'C
DRYER
REFRIG.
15W
15
16
30
2600
W/GRD.
BAR
15W
17
18
1 P-20
*
#12-12"C
GREAT ROOM
BAR
*
19
20
*
GREAT ROOM
BAR
*
21
22
*
OUTSIDE LTG.
BAR
*
23
24
*
KITTCHEN LTG.
MAIDS
*
25
26
*
KITTCHEN LTG.
LAUNDRY ROOM
1500
27
28
900
MINI-AHU
SPARE
900
29
30
2P
900
#10-12'C
MINI
SPACE
31
32
25
900
COND.
33
34
SPACE
35
36
SPACE
37
38
39
40
41
42
* 1100 S.F.
3300
SUBTOTAL
12,400
TOTAL = 42,200
29.800
SUBTOTAL
(a) AFCI C/B
10.0 KW (b) ON TIMER
= 6.92 KW (c) GFI
= 1.15 KW
24.07 KW (100A)
120240V PANEL "CA' 1ODA M.C.B.
1 PH, 3W (CABANA) SURFACE M.T.D.
BRANCH CIRCUITS
LOCATION
WIRE AND
CONDUIT
TOTAL
BREAKER
TRIP
CKT
NO.
CKT
NO.
BREAKER
TRIP
TOTAL
WIRE AND
CONDUIT
LOCATION
VA
VA
STORAGE
#12 -12*C
900
1P-20
1
2
2P
16W
#10-12"C
POOL
BATH / PORCH
900
3
4
25
1500
PUMP
BATH RECEPT
900
5
6
2P
1500
#10-12"C
SPA
WATER HEATER
3010 -12'C
2100
2P
7
8
25
1500
PUMP
2100
30
9
10
1 P-20
600
#12-12'C
POOL / SPA LTG.
SPARE
900
1P-20
11
12
1P-20
600
#12-12"C
RECEPTACLE
SPACE
13
14
SPACE
15
16
17
18
11
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
SUBTOTAL
7,800
TOTAL = 15,000
7,200
SUBTOTAL
(b) ON TIMER DEMAND LOAD: = 15.0
(c) GFI FIRST 10 KW @ 100% = 10.0
5.0KW@400/9 = 2.0
12.00 KW (50A)
120R40V PANEL "M" 400AML0
1 PH, 3W W.PROCf) SURFACE MTD
CKT. NO.
DESCRIPTION
CS TRIP
LOAD
WIRE OONDUIT
REMARKS
1
PNL 'A'
2P-200
38.300
313/0, 1/6
GRO-1'C
MAIN %I
2
PNL "B'
2P-200
42.200
3)3/0' 1#6
GRD-1 C
MAIN /2
3
PNL 'C'
2P-100
15,900
3#3, 116-lyC
MAIN #3
4
PNL 'CA'
2P-100
15,000
3/3, 1 16
GRD-12 C
MAIN /4
5
PNL "EM'
2P-125
29,900
3%1. 1 /6
GRD-2 C
MAIN #5
TOTAL:
141,300
FIRST 10KW O 100X - 10.0
98.3 KW O 4OX - 39.32
A/C - 21.65
TOTAL - 70.97 KW (296A)
DEMAND-
PNL
'A'
27.3
7.15
PNL
"B'
31.2
7.15
PNL
"C'
15.9
--
PNL
"CA'
15.0
--
PNL
"EM'
18.9
7.15
108.3 21.45
DEMAND LOAD = 31.2 KW
A/C @ 100%= 4200
NEAT � 65%=7150 FIRST 10 KW @100 %= '10.0 KW
21.2 KW @ 40 % = 8.48 KW
A/C (7.15) = 7.15 KW
,25.63 KW (107A)
120/240V PANEL'EM' 125A M..L.O.
1PH, 3W (EMERGENCY)
BRANCH CIRCUITS
LOCATION
WIRE AND
CONDUIT
TOTAL
BREAKER
TRIP
CKT
NO.
CKT
NO.
BREAKER
TRIP
TOTAL
WIRE AND
CONDUIT
LOCATION
VA
VA
REFRIGERATOR
#12-12'C
16W
1P-20
1
2
2P
65W
2#4-1'C
A.H.U. No..3
FREEZER
16W
3
4
60
56W
(10 KW)
MICROWAVE
15W
5
6
2P
(3000)
2#6-3/4"C
C.U. No.31
KITCHEN LTG.
900
7
8
60
(3000)
FOYER / HALLWAY
900
9
10
1 P-20
900
#12-1
/2"C
GREAT RIM. / MAIDS
OFFICE / PLAY ROOM
900
1 J
11
12
900
2nd FL. LTG.
COOK TOP
2#8, 1#10
3000
2P
13
14
900
M. BEDRC)OM LTG.
1#10, GRD-3/4-C
3000
40
15
900
M. BEDRC)OM LTG.
SPARE
1 P-20
17
18
900
OFFICE
SPACE
19
116
20
600
M. BEDRC)OM RECEPT.
21
22
600
M. BEDRCOOM RECEPT.
23
24
SPARE
25
26
27
28
SPARE
29
30
31
32
33
34
35
36
37
38
39
40
41
42
SUBTOTAL
13,200
TOTAL = 29,900
16,700
SUBTOTAL
(a) AFCI C/B DEMAND LOAD: = 18.9 KW
(b) ON TIMER
FIRST 10 KW @ 100% = 7.15
(c) GFI 8.9 KW @ 40% = 10.0
A/C = 3.56
COMPLY WTH NEC MOAB)
%iOKE DETECTOR
uNE sty t2ov
av SWTCH
SYATCi
sWTCH LEG �. 11
PHASE CONDUCTOR
SMOKE DETECTOR
CONNECTION DETAIL NTS.
NOTES:
1-SMOKE DETECTOR SHALL BE HARO'MRED (110 CULT TYPE)
TO A NON-SYATCHABLE LIGHTING CIRCUIT
KITH BATTERY BACK-UP AND SHALL NOT BE
CONNECTED ONTO THE LOAD SIDE OF GROUND FAULT
CIRCUIT INTERRUPTER ALL SMOKE DETECTORS VIl" EACH
UNIT SHALL BE INTERCONNECTED(AFCI PROTECTED)
2-SMOKE DETECTOR SHALL NOT BE PLACED NITHIN 3FT.
OF ANY A/C GRILL
3-SMOKE DETECTORS LOCATED OUTSIDE OF SLEEPING
AREAS SHALL NOT BE PLACED CLOSER THAN 3FT.
TO BATHROOM DOOR.
4-THE MOUNTING AND LOCATION OF UNIT SMOKE DETECTORS
SHALL COMPLY WTH NFPA 72 SEC.2-all.fl . COLING MOUNTS
NOT LESS THAN 4' FROM A WALL -WALL MOUNTS NOT LESS
THAN V RN OEAJNG NOR MORE THA if TO TOP OF DETECTOR.
20.71 KW (86A)
C'WP (METAL) CU
5/8' COPPERCLAD
GROUND ROD
10 FT. LONG
(a)
120/240V PANEL "C' 1 ODA M. L.O.
1 PH, 3W (2nd FLOOR) FLUSH M.T.D.
BRANCH CIRCUITS
LOCATION
WIRE AND
CONDUIT
TOTAL
BREAKER
TRIP
CKT
NO.
CKT
NO.
BREAKER
TRIP
TOTAL
WIRE AND
CONDUIT
LOCATION
VA
VA
BEDROOM No. 1
#12 -1/2 C
*
1 P-20
1
2
2P
3000
3#8.3/4'C
W. HTR.
No.1
3
4
40
3000
No.2
No. 2
5
6
1P-20
900
#12-M1/2'C
FLOOD LIGHTS
No. 2
7
8
1 P-20
900
SPARE
MASTER BEDROOM
9
10
1 P-20
*
#12 -12"C
BATH RECEPT.
11
12
1 P-20
*
#12 -12V
BATH RECEPT.
13
14
SPACE
DEN / CORRIDOR
15
16
DEN / CORRIDOR
17
18
SPARE
900
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
* 2400 S.F.
7200
SUBTOTAL
8100
TOTAL = 15,900
7,800
SUBTOTAL
ELECTRICAL NOTES
DEMAND LOAD: 15.9
FIRST 10 KW @ 100 % = 10.0
5.9 KW @ 40 % = 2.36
= 12.36 KW (52A)
1.
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE AND ALL APPLICABLE LOCAL CODES.
2.
COORDINATE ELECTRICAL SERVICE W/FLORIOA POWER AND LIGHT
COMPANY.
3.
ALL TELEPHONE RELATED EQUIPMENT PER SFBC 4502.2(Ax11)
AND ANSI/EIA/TIA-570
4.
ELECTRICAL INSTALLATION DESIGN OF THIS PLAN IN IN COM-
PUANCE AS SET FORTH BY STATFT OF FLORIDA STATUTES MODEL
ENERGY EFFICIENCY CODES.
5.
THE CONTRACTOR ALL EXAMINE THE JOB SITE AND DETERMINE FOR
HIMSELF PRIOR TO SUBMISSION OF 810 EXISTING CONDITIONS.
6.
ALL ELECTRICAL WORK SHALL BE PERFORMED BY A LICENSED
ELECTRICAL CONTRACTOR. IT ALL BE HIS RESPONSIBILITY TO
SECURE AND PAY FOR ANY PERMITS. CERTICATES OF INSPECTION.
AS REQUIRED.
(a)
7.
SUBSTITUTE MATERIALS EQUIPMENT OR METHODS SHALL NOT BE
MADE ATHOUT APPROVAL OF THE ENGINEER. IF THE USE OF A
(a)
SUBSTITUTE REQUIRES ANY CHANGE IN WORK. THE NECESSARY FOR
SUCH CHANGE WILL BE BROUGHT TO THE ATTENTION OF THE ENGI-
NEER. AND IF APPROVED, SHALL BE MADE AT NO COST TO THE
OWNER.
(a)
8.
CLEAN UP SUCH TRASH AND DEBRIS GENERATED BY THE WORK AND
LEAVE COMPLETED WORK IN A CLEAN, UNDAMAGED. AND FINISHED
(a)
CONDITION READY TO RECEIVE WITHOUT FURTHER PREPARATION,
UNLESS SO SPECIFIED IN OTHER SECTIONS, ANY ADJACENT OR
ABUTTING WORK TO BE PERFORMED BY OTHERS.
120/240V 1 PH, 3W
3 15W THAN (CU)
3' C (EA)
3 #500 THWN (CU)
3'C (EA)
1# 1/0 (CU) - 3/4-C
BLDG. FOUNDATION STEEL
M
■
CWP (METAL)
5/8' COPPERCLAD
GROUND ROD
10 FL LONG
ELECT. RISER., SCHEDULES & NOTES
N.T.S. SCALE: SE�DYRCRAF�
��
NTs
JOHN R. MEDINA & ASSOC.
A R C HIT E C T S
4901 S.W.75th Avenue
Miami, Florida 33155
T 305.740.0554
F 305.740.5355
jrmainc@bellsouth.net _
REVISIONS DATE BY
B. DEPT. -10- 10-05 R.L.G.
9.
MATERIALS, APPLIANCES, DEVICES AND EQUIPMENT SHALL MEET
WITH THE REQUIREMENTS OF UNDERWRITERS' LABORATORIES AND
SHALL BE NEW AND THE LATEST STANDARD PRODUCTS OF MANUFAC-
TURERS REGULARLY ENGAGED W THE PRODUCTION OF THE ITEM.
UNLESS OTHERWISE INDICATED. LIKE ITEMS SHALL BE THE PRO-
DUCT OF A SINGLE MANUFACTURER.
10.
ALL CONDUCTORS SHALL BE COPPER AND RUN IN CONDUIT. ARE
SIZE SHALL BE THWN UNLESS OTHERWISE NOTED ON PLANS. PROVIDE
GROUND CONDUCTOR PER NEC ARTICLE 250-122.
SUgIfC
ref(
11.
LOCATION OR OULETS IN ELECTRICAL DRAWINGS IS DIAGRAMMATIC:
/)
CHECK Mj%NUFACTURER'S DRAWING FOR EXACT LOCATION OF OUTLETS.
f/rQ
OIr
12.
PROVIDE TYPEWRITTEN SCHEDULES FOR ALL PANELBOARDS.
COMPLY W/ SFBC 4504.4
13.
A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON
A/C EQUIPMENT SPECIFIED ON ORIGINAL CONTRACT DRAWINGS CON-
TRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER
AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS.
V
,< A"i 1'i s`."i I
AS WELL AS ANY FEEDER CHANCES BONO AFFECTED BY HIS CHANGE.:r;t!
CONTRACTOR SHALL MAKE ABOVE MENTIONED CHA14CES AT NO EXTRA
ufmir EQUIPM,NT s Cx a yip '
"e,I
COST. HACK CIRCUIT BREAKERS MAY BE USED IN PLACE OF FUSES. USE
AND
Ct:�.;2EC;C �W1Rti. Slj.
NON -AUTOMATIC SWITCH FOR A/C COND. DISCONNECT. (COMPLY W/NEC 110-26)
}' 2v7'T.c-
014E<<c;IJIZKFCdT
IIJI
14.
ALL SMOKE DETECTORS TO BE INTERCONNECTED ON SAME
s tY11J'`1' 13r
CKT (KITCHEN OR BATH LTG.)
15.
RANGE AND DRYER SHALL HAVE BOW NEUTRAL & GROUNDING
ARE PER NEC ARTICLE 250-140.
16.
ALL BEDROOM OU`i .ETS SHALL BE PROTECTED BY AN
'ARC -FAULT CIRCUIT INTERRUPTOR".(AF(l)
22k,
PNL
C
M M-
M-3
l J6 (CU)-3/4-
2P-125A
TRANSFER SWITCH
PNL - PNL
CA EM
■ �I
3y1, 1 #6 GRD 2-C
25
2P-12125A
/1
SEPARATELY NON -DERIVED SYSTEM
DIESEL-NEMA 3R ENCLOSURE
BLDG. FOUNDATION STEEL
JOB j: 05-074
GUERRERO GONZALEZ
(GbENGINEERS, INC.
Me w C. GuerEn% Uc, P.E.
M•ctwnical Eny. Lk. J15235
R°fol L Gonxot•z. P.E
0#06cal Er4 Lie. #11057
43W S.W. 73rd AwK^ Suits 0107A
Miami, Florid° 33153
Tel. (305) 202-3944. Fox (305) 262-8211
E-wxk PROJECT ENG64EERS.COM
U"
nl O
W
U
W
4-
U
0
()
7(3
70
r�
.lam
U
6.G..
r
0
Or
Drowings and Specifications (is irhstnenent of M R &IRS. P I NO
service are and shall rerndn the property of
the Architect and shall remain the property RESIDENCE.
of the Architect whether the project for
which they were mode is ewecuted or not.
They are not to be used in any marmer on
other projects or extensions to this project
except by agreement in wrifng and with the MR. 8. MRS. PINO
appropriate compensation to the Architect. 6864 SW 68 th ST.,
Reproduction of dvdngs and Miami, FL 33155
specifications withoutthevrittencoreentof Mr. Patricia Espinosa.
the Architect is prohibited 305.
PANELBOARDS/NOTES SCALE:3/16"=F-9'
RISER DIAGRAM DATE: 06-1-05
DRAWN: M.A.R.
E 3