07-16-013e LEGEND ELECTRICAL NOTES - INC. FIXTURE W/ A19 - 15OUJ REFLECTOR 1. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT AND CONFIRM WITH OWNER REPRESENTATIVE. EXIST. INCANDESCENT FIXTURE 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE N.E.C. AND SHALL COMPLY WITH ALL LOCAL RULES AND ORDINANCES, FO INCANDESCENT FIXTURE WALL MOUNTED 3. UNLESS OTHERWISE NOTES, MINIMUM WIRE 51ZE SHALL BE NO. 12 AWG. AND ALL CONDUCTORS SHALL B= COOPER WITH TW IN5ULATION FOR 5IZE5 NO. ro AND - EXIST. INCANDESCENT FIXTURE WALL MOUNTED SMALLER. CONDUCTORS LARGER THAN NO. ro 5HALL HAVE TYPE THUD INSULATION. ALL CONDUCTORS NO. 10 AND SMALLER MAY BE SOLID. ALL THOSE NO. a AND LARGER SHALL BE STRANDED. EQUIVALENT ALUMINUM CONDUCTOR5 CAN BE USED O RECESSED LIGHT SUB FEEDERS NO. ro OR LARGER, IF APPROVED BY LOCAL REGULATIONS. CONTRACTORS TO VERIFY. EXHAUST FAN 4. ALL RACEWAYS AND PIPES PLACED IN OR THRU ANY CONCRETE SLAB SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST CONDUIT OR PIPE OF ANY DI PRE WIRED TELEPHONE OUTLET OTHER sERvIcE. 5. ALL RACEWAYS UNDERGROUND AND/OR LARGER THAN 2 INCHES IN DIAMETER SHALL BE GALVANIZED RIGID STEEL. PVC PIPE SCH. 40 WILL BE ACCEPTABLE, IF APPROVED EXIST. PRE WIRED TELEPHONE OUTLET BY LOCAL REGULATIONS. CONTRACTOR TO VERIFY. 6. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS AND CAST ALLOY WITH RECEPTACLE DUPLEX, 15A - 125V. THREADED HUBS IN WET OR DAMP LOCATIONS. 7. DISCONNECT SWITCHES SHALL BE QUICK MAKE, QUICK BREAK, IN NEMA 1 OR 3R 77 EXIST. RECEPTACLE DUPLEX ENGLOSURE, AS REQUIRED BY EXP05URE. 8. ALL MATERIAL SHALL BE NEW AND SHALL BEAR UNDERWRITERS AND UNION LABELS �! EXISTING RECEPTACLE 120/240 V WHERE APPLICABLE. 9• ALL WORK SHALL BE PERFORMED BY A LICEN5ED ELECTRICAL CONTRACTOR IN A ® SMOKE DETECTOR WORKMAN LIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTANCE BY ENG./ARCH. MUST BE A CONDITION OF THE CONTRACT. ELECTRICIAN TOGGLE SWITCH, SINGLE POLE SHALL INDICATE ON ELECTRICAL PANEL BOARD AREAS SERVED BY EACH C.B. 10. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE EXIST. TOGGLE SWITCH, SINGLE POLE WITH PROGRESS OF CONSTRUCTION. 11. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE OF DEFECT —� EXIST. ELECTRICAL PANEL - SEE SCHEDULE FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE. HOMERUN TO PANEL — BOARD ELECTRICAL FLOOD CRITERIA LETTER AND NUMBER INDICATE PANEL AND CIRCUIT (INCL. GROUND AS PER NEC) 1 ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE FLOOD ELEVATION HATCH INDICATES No. OF WIRES, SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEVATION AND SHALL BE G - INDICATES GROUND INSTALLED WITH SEPARATE INDEPENDENT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 2. NO APPLIANCE OR APPLIANCE OUTLETS SHALL BE INSTALLED BELOW BASE FLOOD ELEVATION. 3. A/G COMP11RE65OR5 SHALL BE INSTALLED ABOVE BASE FLOOD ELEVATION. 4. MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEVATION 5. COORDINATE WITH FLORIDA POWER i LIGHT COMPANY TO LOCATE THE ELECTRICAL METER TO COMPLY WIT14 FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS, z s' LH 0 I:Ov I� aui PANEL 1 200 A"=S �G7 -Rv 1'4,!2; '�'�RP 707.1 AMPS CKT. TOT. cONCU'T Kla� POLEa NO 5_RVINCz UJI���CONDUIT <Va PO UATER SEATERO 1/2' -_— 4,5D01 2 30 2 5eDFOOM *1 12 1/2 5 0-' 4 5EGR001-1 02 - 12 1/2 --13 --' 5 _ I 2 i/2 1.5 20 L;riHTINCs 2 1�o 0—/2 O.-- BM�LL AFP�. 2 /:� - 1.5 1 =0 8 LCs ITING 12 I/2 0.G _ a -u I 8 3/4 7,200, 2 40 0 LIviNC� RM. 12 1/2 5 O r 2 i R �_eaTOR 12 1/2 1.5 3 RaNCzE 6 --------------- 10 2 50 14 A U I" 3,00� _ GIN'NCz ROOM 2' _ 5 1 20 GRY=2 10 3/ 5.0- -. ' DIN NGc ROOM = /2 5 20 1 20 - _ S;ER - /2 5 20 --� 23FAMILY Z4dZ01 FAMILY ROOI1 IZ 1/2 13 I 43 L ICsHTB 1Z I/Z 0b I 15 26 BtrIA1.L At'F'L.. lz I L3 21 KITCHEN IZ 1/2 13 1 20 28 MA8r1 =R OATH _ _ 1Z - 12 Tj - 1/2 13 -I 1 -_ 1 29 MASTER BED IZ I/2 13 1 Z0 30 GFt _ r I/1 1 19 - 31 WHIRLPOOL 10 3/4' 20M Z 30 32 __- 018NWA8 4ER 12 1/2 13 1 33 34 LIGHTS 12 1/2 1 0b I 35 _ 34 SPACE i -� 3l STAGE 3,3 � �✓ 40 sPacE "yOTE = R0I'EX 1'A? 5E uSE. N L'E'u OF cONDU T CIRCUIT ARC FAULT PROTECTION REQUIRED IN ALL BEDROOM CIRCUITS ELECTRICAL LOAD CALCULATIONS LIGHTS $ RECEPTACLES (3W X 2,=14'� S.F.) a,241 WATTS SMALL APPLIANCES 3,000 WATTS REFRIGERATOR 1,500 WATTS DISH WASHER 1,200 WATTS RANGE 8 OVEN 12,000 WATTS WATER HEATER 4,500 WATTS WASHER 1,500 WATTS DRYER 5,000 WATTS SUBTOTAL = 36Q4i WATTS FIRST 10,000 W. a 10051. . 10,000 WATTS REMAINING 2ro,94i W �@ 40% - .. 10,E i9 WATTS A/C LOAD 5,000 WATTS TOTAL = 25,719 WATTS DEMAND LOAD = 25,11g WATTS % 240 V = 101 AMPS - 1 �O _ 7 SI 6O X 40 I O �m -_(-20 20 r� 20 13 KITC� OR B t 1 OM L IGHT i I EXISTING /OVERHEAD ' ELECT. SERvIc_E (INTERCONN GTED) SMOKE t DETECTOR 120 V. LINE SIDE SWITCH LEG i OF SUJITCH SWITCH PHASE CONDUCTOR SMOKE DETECTOR COINNECTION DETAIL N.T.S. 51'10<E DETECTORS SHALL BE.• HARD WIRED (110 VOLT TYPE) TO A NON-5WITCHA15LE KITCHEN OR BATHROOM LIGHTING CIRCUIT, WITH BAtTERY BACK UP AND SHALL NOT BE CONNECTED ONTO Tki= LOAD SIDE OF A GROUND FAULT CIRCUIT INTERRUPTER LIVING ROOM (EXIST.) (E) (E) (E) DINING ROOM (EXIST.) (E) I (E) (E) 3 03/0 CU. THW IN 2' G 7x 3 -03/0 CU, THW IN 2" C iJ.. S-VISk i R- r.yJ ,Jo , 4V ej, — D j , � S O ELEC. 2 200 +.: MTR. 200 200 AMP. PANEL, D15c. SW. W/ MAIN CIRG. BRKR.'lh W/ 40 - I P SPACES t wt r t 3 -"3/0 CU. THW IN 2" C i 14 TU1 EU. -. fN 3/4' G TO CWP Y. _' MASTER BEDROOM R 25 I I ® I I (E) \ O 29 2S (2) 10'-0" DEEP GROUNDING RODS 5/a" DIAMETER SPACED i ro FT. APART 4 BOND TO FOUNDATION EXISTING ELECTRICAL RISER DIAGRAM N.T.S. 7- V " e' a- y I1 _ t I Erft,1 l; , ;I tw w =tit-�� p .a~�caiQaa..a. a4 _ —-- HOW - - S GF I 29 r WALK-U' 28 CLOSET 2 ' la�xla" LAV. >�tEN A,CGES5 ik PANEL MASTER BATH,/ GF 1 / 29 _ 25 WALK" j- BI T -2 CLOSET P1 GFI 29 T- -- 28 LAV. DO (E;) (E) \ i \` \.O O G (E -- j FAMILY ROOM DW LAvO ) 21 R 34 034 32 �O TUB �GFI KITCHEN �,� �OA'H #1 r EXIST.) 00 �, R R SI � cL 5T VE 41 LAN 34 —CLOSET— 00 �cv E) 2.1 R 3R 1 GF I 4 -- 4 OV-1 REF I 21 GFI 1 (E) -� 23 3W 1 3 R R 34 2 21 / O, (E) BEDROOM #2 (EXIST.) (E) �5 UTILITY �- 8, 20 - PAN RY 25 Wf- 3 PANEL T 9, 11 METER CU NOOK R A 34 34 30 O ELECTRICAL PLAN N 0 RT H SCALE: 1 /4" = 1'-0" 1 23 �. .ow0_J ' '. ,'� t .• ' 1s sky? L L o u a Q� v C � > X ca rd t V w tm 4-1 O (o a 3LLd: 0 cam` Etd tri Q G o2m ' OLnal I- ►+ AN 't to ko O � M 0 M z oo �Q0 4-J L Q 00 \\ C ps W 71 HEC1ED - M. _- - 12-13-2006 o E AS SH0 CD r�o - SHE=T III