07-16-012AIR - CONDITIONING NOTES 1. DUCTWORK SHALL BE 1-1/2" THICK, 3 POUNDS PER CUBIC FOOT DENSITY FIBERGLASS WITH VAPOR BARRIERS, UNLESS OTHERWISE SPECIFIED. DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS $ ACCORDING TP "ASHRAE" $ "5MACNA" STANDARDS. DUCT DIMENSIONS ARE IN INCHE5 AND CORRESPOND TO INSIDE DIMENSIONS WIDTH X HEIGHT. DUCT SYSTEM SHALL COMPLY WITH "NFPA" STD. NO. 9DA AND/OR 908. DUCTWORK AND COMPONENTS SHALL BE CLASS 1 MATERIALS IN ACCORDANCE WITH U.L. lal TESTS. 2, COORDINATE LOCATIONS, SIZES AND OPENINGS WITH OTHER TRADES ON THE JOB. A/C CONTRACTOR SHALL PROVIDE THE COMPLETE DUCT SYSTEM WITH TURNING VANES AT ALL ELBOWS, SPLITTER5 AND DAMPERS AS REQUIRED. 3. ALL FAN UNITS, MOTORS, COMPRESSORS, ETC. SHALL BE ISOLATED, AS REQUIRED TO OPERATE QUIETLY 50 THAT NO OBJECTIONABLE SOUND WILL BE HEARD IN THE HABITABLE SPACES DUE TO AIR VELOCITY, MOTOR HUM, VIBRATION OR MECHANICAL MOVEMENT, 4. A/C SYSTEM SHALL HAVE DISPOSABLE AIR FILTERS LOCATED A5 REQUIRED FOR EASY ACCESSIBILITY. 5. A/C SYSTEM SHALL BE CONTROLLED BY A THERM05TAT MOUNTED 5'-0" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. 6. ALL GRILLES E DIFFU5ER5 TO BE ALUMINUM CONSTRUCTION, DIFFUSERS SHALL HAVE HIDDEN OPPOSED BLADE DAMPERS. PROVIDE GASKETS ON ALL GRILLES 8 DIFFUSERS, "TITU5" OR "AIREGUIDE" FINISHED COLOR BY ARCHITECT. -I. UNDERCUT DOOR5 1" A.F.F. AS INDICATED. a. ALL REFRIGERANT PIPING SHALL BE COPPER "HARD DRAWN TYPE L' ACR TYPE, DEHYDRATED -1 SEALED. ALL FITTINGS SHALL BE WROUGHT COPPER. ALL JOINTS SHALL BE MADE WITH HIGH TEMPERATURE BRAZING ALLOY OF NOT LESS THAN 5% SILVER. PIPING INSULATION NOT LE55 THAN 3/4" THICK "ARMAFLEX". LIQUID s SUCTION LINES SHALL BE SIZED ACCORDING TO EQUIPMENT MANUFACTURER'S RECOMMENDATIONS FOR EQUIVALENT LENGTH OF PIPING RUN FOR CONNECTED TONNAGE. ALL PIPING ACGE55CRIE5 SHALL BE CONSTRUCTED AS SUGGESTED BY EQUIPMENT MANUFACTURER. ALL PIPING SHALL BE EVACUATED PER GOOD PIPING PRACTICE BEFORE START UP, PROVIDE FILTER / DRYER AND SIGHT CLA55 ON LIQUID LINE. 9. CONDENSING UNITS SHALL BE A MINIMUM DI5TANGE OF: THREE FEET FROM FUEL GAS METERS. TEN FEET FROM L.P. TANKS FIVE FEET FROM GLOTHE5 DRYER EXHAUST 10. GONDEN5ING UNITS LOCATION SHALL BE A5 PER MANUFACTURER'S RECOMMENDED MINIMUM CLEARANCE TO 5TRUCTURE5. BATHROOM EXHAUST BATHROOM EXHAUST DUCT SHALL BE 51-4EET METAL WITH BAGK DRAFT DAMPER VENT THRU ROOF 6" ABOVE ROOF SURFACE WITH GOOSE NEGK TERMINATION AND WITH CORROSION RESISTANT SCREEN MESH WITH 1/2" MAXIMUM MESH OPENING DRYER EXHAUST 4" ROUND MINIMUM SHEET METAL (30 GAGE MIN.) DRYER EXHAUST WITH ROOF CAP WITH GOOSENECK TERMINATION 6" ABOVE ROOF SURFACE AND WITH SMOOTH INTERIOR SURFACE WITH JOINTS RUNNING IN THE DIRECTION OF THE AIR FLOW. DRYER EXHAUST DUCT SHALL NOT BE ASSEMBLED WITH SHEET METAL 5CREW5 OR OTHER FA5TENER5 WHICH WOULD EXTEND INTO THE DUCT. DRYER EXHAUST SHALL BE EQUIPPED WITH A BACK DRAFT DAMPER EXHAUST FAN SCHEDULE EXHAUST NUTONE MODEL L550, 50 GFM 4" D IA. METAL DUCT. 0.15 AMP RATING, 110-1-60 ENCASE W/ PVC 6" U SCHEDULE 40 AIR -COOLED CONDENSING UNIT - SLAB MOUNTED N.T.S. AIR HANDLING UNIT SCHEDULE UNIT NUMBER AHU-1 MATCHING CONDENSING UNIT CU-1 UNIT LOCATION AHU CLOSET UNIT TYPE VERTICAL ENTERING AIR TEMP. (cdb/Lub) a0° / 671 MANUFACTURER RHEEM MODEL NUMBER R5HK-24J115FF EVAPORATOR CFM 1600 EXTERNAL STATIC PRES5 0.50 EVAP. FAN MOTOR H.P 1/2 AVAILBLE VOLTAGE 2001240-1-60 TOTAL HEATING CAP (KW) 10 KW 'a 240-1-60 NUMBER OF ELEMENTS 3 FILTER TYPE PERMANENT UNIT WEIGHT (L85) 125 CATALOG SENSIBLE COOL. CAP. = 30,900 BTUH 1.1 T io CALCULATED 5EN51BLE COOL. CAP, 26,419 BTUH EXH. FAN SCHEDULE EXH FAN No. EF-I EF-2 AREA SERVED BATH I BATH 2 FLOOR 18T 15T LOCATION CEILING CEILING CFM 50 50 STATIC PRESSURE 1' 1" TYPE DRIVE DIRECT DIRECT MOTCR AMPS 0.15 0.15 ELECTRIC CHARACT. 110-1-60 110-1-60 MANUFACTURER NUTONE NUTONE MODEL NUMBER L550 L550 REMAR<5 (A) ROOF CURB, (B) SAFETY 5WiTCH, C) iN51DE GR'LLE, (D) 5111RD 5CREEN, (E) EXPL05!ON PROOF MOTOR, (F) BACKDRAFT DAMPER, (G)MAGNETIC STARTER WITH REMOTE ON/OFF SWITCH, (H) a41-AL ROOF CAP UNL)tF<.0 I (4) 1/4" BOLTS HOOK I_ 6" INTO CONCRETE I TO PREVENT THEFT WITH 500 POUNDS PULL-OUT RESISTANCE EACH MIN. (TYP.) 1, CONDENSING UNIT 2. COMPRESSOR ACCESS PANEL 3. BACK - SEATED REFRIGERANT VALVE 4. REFRIGERANT SUCTION LINE WITH INSULATION 5. SIGHT GLASS WITH M015TURE INDICATOR 6. REFRIGERANT LIQUID LINE 1. CONDUIT - POWER NAD CONTROL a. REFRIGERANT GAUGE CONNECTION 9. CONDENSER COIL 10. GOIL GUARD 11, FAN GUARD 12. CONCRETE PAD 13. REFRIGERANT SUCTION LINE FLEX - CONNECTOR 14. ATTACHED COND. UNIT ALL AROUND WITH (2) Ii811 STAINLESS STEEL CABLES TO SUSTAIN 146 MPH WIND CONDENSING UNIT SCHEDULE UNIT NUMBER CU-1 UNIT LOCATION OUTSIDE UNIT WEIGHT 065) Ig5 UNIT NOMINAL CAP. (TONS) OUT5IDE MATCHING AHU NUMBER AHU-I MANUFACTURER RHEEM MODEL NUMBER RAND042JAZ CALCULATED TOTAL SENSIBLE GAIN (BTUH) 26,419 tl CALCULATED TOTAL TOTAL HEAT GAIN. (BTUH) 35,859 AMBIENT TEMPERATURE UNIT'5 MIN. SEER 13.00 AVAILABLE VOLTAGE 20a/230-1-60 UNIT'5 MIN CIRGUIT5 AMPS 26/26 UNIT15 MAX FUSE SIZE 40/40 LIQUID LINE DIAM. 5/6" SUCTION LINE DIAM. 1/a" CATALOG INFORMATION SEN. COOLING CAP. (BTUH) 30,900 CATALOG INFORMATION TOTAL COOLING CAP. (BTUH) 42,000 HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR F111RE DAMPER(5) SMOKE DAMPER(5) FIRE RATED ENCLOSURE FIRE RATED ROOF/FLOOR CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL EOX ST.) SUPPLY DUC REFRIGERANT LINES TO OUTSIDE CONDENSING UN 3/4' DIA. PVC CONDENSATE DRAIN W/3" TRAP UNION 4 G.O. PLUG TO OUTSIDE GREEN AREA ALUMINUM AHU 5UPPGRT-/- (SELF - STANDING) HT.OF STAND SHALL BE DETERMINED AT JOB -SITE. l DINING ROOM ( EXIST.) to "X10" 150 GFM (EXIST.) 6"XIO" 15O CFM (EXIST.) 'ING ROOM (EXIST.) IIx1/T II 1150 CFM (EXIST.) AHU CLOSET WITH -� 4" CLEARANCE MIN. 4"(P EXH. DUGT UP TO ROOF CAP. - CLOSET- - (EXIST.) rT� AHU DIAGRAMMATIC CLOSET DETAIL N.T.S. A H U 6"x10" - 150 GFM all (EXIST.) W/c N�A1 .) � -, TUB II 00 5TC -CLOSET- - OO (EXIST.) R-6 IN OLATiON "-CEILING 5/A PLENUM RIGID FIBERGLASS DUCT -� SPIN COLLAR WITH VOLUME DAMPER AND LOGKING QUADRANT 7 . .. •., Tel of ° • R-6 IN5ULATION (TYP.) '•� INSULATED FLEXIBLE DUCT GLA55 1 1,l' 2" i.UITH POLYETHELENE J4,-<ET.' AND STEEL WIRE •• REINFORCING PARTITION PROVIDE MODEL 551 LOW VOLTAGE TAKE -OFF DETAIL CD OVERFLOW SHUT-OFF SAFE-T-SWITCH MANUFACTURED BY SMD RESEARCH, INC. BOCA-BATON, FLA. % h" T RAG -FLOOR MASTER BEDROOM III 15 X GFM D/ 'E' STJ -- -- o KITCH N VE FLAN 6 "XIO' / 6 "X10" 150 GFM I 150 CFM (EXIST.) (EXIST.) I I W R5 RL IN ATTIC SPAC BEDROOM #1 BEDROOM #2 1 (EXIST.) ' (EXIST.) I D 4"(P ID 30 GAGE METAL DRYER EXH DUCT UP TO ROOF CAP. WH R5 4 RL A.F.G F 6 "X10" 150 CFIM UTILITY e ANTRY ATTACHED EA. COND. UNIT ALL AROUND WITH (2) I/S" STAINLESS STEEL CABLES TO 5U5TAIN 146 MPH WIND CU T7YF`.) DIFFU5ER 51ZE 45 PER \L L I MFR. SPEC'5. EXHAUST FAN DETAIL N.T.S. _ _____ SHOW 011NLK-IN ��- CLOSET °) LAV. LINEN - ASTER BATH _--- - 6 "XIO" 4`0 150 CFM UP \ 12 "X12' RETURN AIR GRILLE E.F.-2 a"Xl0" 12'0 WALK-IN - 200 GFM CLOSET B� T G L4V 12'X12' RETURN AIR GRILLE �. V"Xlo" 200 GFM R-6 INSUL.AIR D15TR15. BOX. , FAMILY ROOM a"X 10" 200 GFM NOOK 3/4" CD TERMINATE +6" AFC -; PROVIDE CD TRAP AT AHU $1 MECHANICAL PLAN SCALE: 1 /4" = 1'-0" NORTH AP. . • 'a3M3'F.NS 7 7 7 .. J ! • 7 � ,, - 3 . 0 a w F- J �Y4E=0 z j a a o w < O a 0 V O O 0 U Z Fn W W (0 Z w w m~ O a m o� U- :r u. p :) 0 Y. C~ JRAP 0 a a tfl�.w O J V. ..�0 L L L o a� V c 72 72 > GVJ W i > LA ca -2 X Lu (d N vMi S 4 _O cfl o cv) Z3 !CC� N rd 1 i Q G cfl 2 W �OLn0) Nd-Lnl0 r- r-r- a. �' O M O - M Z 00 to ® N (.0 sIV V q) Ln v 4-J r-o �� � c • W N 0 O N J rno�LL �_ /v) W � Ln i N�Ln S r- Ln .- Q 00Ln- U u rn a17 -- o t \� 0. v Y • • Mn \ : v� 0 & > Q . w v o oRawr� G.C. rHFr,k'FC C. M. OATF 12-13-2006 S'-_ALE AS SHOWN JOB NO 22-2006 SHEET m - I 6 7 _Fr_