FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, AND ALL APPLICABLE.STATE
AND LOCAL CODES.
2. ADHERE TO AND OBTAIN ALL PERMITS, LICENSES AND GOVERNMENT REQUIREMENTS.
3. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE DEPARTMENT, AND
ARCHITECT/ENGINEER.
5. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS TO BE DONE ONLY
WITH THE WRITTEN APPROVAL OF THE ARCHITECT.
6. PIPE ROUTING SHOWN SHALL BE USED AND ANY ADDITIONAL OFFSETS OR FITTINGS
REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES,
AND/OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY EXISTING
STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID ANY/ALL
OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC. FLASH AND COUNTERFLASH ROOF PENETRATIONS. (SEE FIRE RATED PIPE
PENETRATION DETAIL).
8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON -ACCESSIBLE CEILINGS AND
CHASES.
9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL EXISTING/NEW DIFFUSERS,
SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS.
10. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE
WITH N.F.P.A. 13.
11. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN
ACCORDANCE WITH N.F.P.A. 13.
12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE
FACTORY MARKED "UL" AND "FM", 175 WORKING PRESSURE.
13. ALL VALVES ON THE FIRE PROTECTION SYSTEM TO BE ELECTRICALLY SUPERVISED.
TYPE AND EXACT LOCATION OF FLOW, PRESSURE AND SUPERVISORY SWITCHES
SHALL FACTORY MARKED "UL" AND "FM", 175 WORKING PRESSURE.
14. ALL POWER WIRING SHALL BE ACCOMPLISHED UNDER THE ELECTRICAL DIVISION.
ALL CONTROL AND INTERLOCK WIRING SHALL BE ACCOMPLISHED UNDER THIS
SECTION OF THE SPECIFICATIONS IN ACCORDANCE WITH THE REQUIREMENTS IN
THE ELECTRICAL DIVISION. COORDINATE ALL ELECTRICAL ITEMS WITH ELECTRICAL
CONTRACTOR AND INSURE PROPER COORDINATION.
15. SPRINKLERS SHALL COVER THE ENTIRE AREA OF THE ROOM INCLUDING ALCOVES.
SPRAY SHALL NOT BE BLOCKED BY WALLS OR PARTITIONS.
16. ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4"
AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL
INTERSECTING SURFACE.
17. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY.
18. MAINTAIN A MINIMUM OF 18 INCHES FROM THE BOTTOM OF THE SPRINKLER
DEFLECTOR TO THE TOP OF STORAGE/FILE STORAGE.
19. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK4 FEET OR WIDER.
20. FIRE SPRINKLER SYSTEM TO BE MONITORED BY FIRE ALARM SYSTEM BY OTHERS.
21. 0 INDICATES HYDRAULIC REFERENCE NODES
LAUNDER MAIL
DROP -IN ANCHOR
3/Ni ROD COUPURD
w
3ro• ALL TI1 ROD
-A T NfS
(AAt101. OR OA. AH )
. (sI9 VTO 4 )
(.9
+
TYPICAL HANGER DETAIL
N.T.B.
PIPE SQE
RDD SRE
ME or
4N. 'w
MAX. 'C'
rAsnm
DIM.
DDI.
3/4'
3/B'
1-3/6' X 1-17/32-
DROP-N ANCHOR
Im
1-6/6'
13/16'
1-7/6'
1-1/Y
16/16'
2•
2'
1-3/16
2-3/B'
2-1/2'
1/2'
1-1/2' X 2-1/32-
DROP -IN ANCHOR
1-7/16'
2-3/4-
]'
1-3/4•
3-1/4'
2'
4'
5/N1'
1-6/6' X 2-16/32'
DROP -IN ANCHOR
2-1/4-
3-7/8•
B'
2-3/4'
4-3/4'
6'
3/4-
1-3/4- X 3-1/4'. DRP.-LAN ANC.
3-6/1V
5-1/2-
N/A
N/A
N/A
WA
ROOF FLOOR
Fire Sprinkler Piping Plan
SCALE: 1 /8"=1'-0"
RISER CLAMP (B-LINE MODEL B3373CTC OR EQUAL)
MIN t' THICK
MEDIUM DENSITY 3x3x1/4
NEOPRENE STEEL PLATES
CONCR.FLOCR (CLUE TOGETHER WITH NEOPRENE PAD
TO FORM ONE UNIT. USE CONTACT
CEMENT).
ELEVATION
No. Date Revisions By Water Supply Information
1 2/9/2009 SUBMIT FOR APPROVAL JRGN Static Pressure 55 PSI
Residual Pressure 53 PSI
Pitot Reading 42
Flow In G.p.m. 1860
Date Of Test 2/9/09
Time Of Test 12:15
Test Taken By LT M FERNANDEZ
Hydrant Location 5876 SW 68 ST
SEE FIRESTDP DETAIL
3'
PLAN VIEW 3'
NOTE: PROVIDE RISER CLAMP
BEND STRAPS AT EVERY OTHER FLOOR
LAB CONTROL VALVE WITH TAMPER SWITCH
, V v
WATER FLOW SWITCH
0 PRESSURE GAUGE
TO SPRINKLER
fl-A+ 11 8 w
DRAIN/TEST 1" DRAIN FOR 1 %" CONTROL VALVE
ASSEMBLY -� 11/" DRAIN FOR 2%" CONTROL VALVE
1/2" RISER
1 1 /4" DRAIN
LAB
ti..M v v •v•v d,v vw v V v V V" v V v V v
FIRE SPRINKLER
CONTROL VALVE
ASSEMBLY DETAIL
N.T.S.
Design Criteria
Sprinklers/ Spacing
System No.
Symbol
Qty
Size
K
Temp
Description
SIN
Design Area
Area #1
Area #2
9
1/2"
5.6
155
TYCO-QUICK RESPONSE WHITE TY-FRB SEMI REC PENDENT
TY-3231
Density
10 GPM/SQ.FT
10 GPM/SQ.FT
Design Area S.f.
225
225
Psi Req'd ® City Main
54.93
54.95
Gpm Req'd 0 City Main
306.7
250.3
Gpm Req'd 0 Basr
50.06
39.72
No. Spkr. In Dsgn. Area
9
9
Elev. 0 Highest Spkr
10'
20'
Domestic/outside Hose
100
100
9
Total This Sheet
I I
I I
I
I I
I I
D.1 D
I I I
I I I
C B A
VE IOC-04 REVM'SP
NGS N,F.PA 13 AND
LfANCF �t�TER
THESE
FOR r 004 (0 �1Gt't SYSTFti�18r}
i .G 13.'3'?.
FAC• 0 FtKE Na�O-[Fs.:. T 1(3,� TrtJ`��
BASE) I A Cdy Or t*o SD tli3'rt};
A �RVc ;A11:� 1I :=rc%P Fq'FtrOVAL
DRbtltl • �ftiiP+G�rU.
S^t•IAOP 0+
MAXIMUM DISTANCE BETWEEN HANGERS
NOMINAL PIPE
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
3-1/2"
4"
5"
6"
8"
SIZE (in.)
STEEL PIPE EXCEPT
N/A
12-0
12-0
15-0
15-0
15-0
15-0
15-0
15-0
15-0
15-0
15-0
THREADED UGHTWALL
THREADED LIGHTWALL
N/A
12-0
12-0
12-0
12-0
12-0
12-0
N/A
N/A
N/A
N/A
N/A
STEEL PIPE
COPPER TUBE
8-0
8-0
10-0
10-0
12-0
12-0
12-0
15-0
15-0
15-0
15-0
15-0
CPVC
5-6
6-0
6-6
7-0
8-0
9-0
12-0
N/A
N/A
N/A
N/A
N/A
POLYBUMENE (IPS)
N/A
1 3-9
4-7
5-0
5-11
N/A
N/A
N/A
N/A
N/A
N/A
N/A
POLYBUTYLENE (CTS)
1 2-11
1 3-4
3-11
4-5
5-5
N/A
N/A
I N/A
N/A
N/A
N/A
N/A
Project
SOMERSET CHARTER SCHOOL
5876 SW 68 ST
Fire
SM
Miami, Florida 33143
I:
'ntrnct With:
Syatam No. 1 Date: 2/9/2009
Drawn By All Fire Sprinklers Sea1ai 1/8"= V-0"
7492 N.W. 8nd Street Chackad er: All Fire Sprinklers Authority Having Jurisdiction
Medley,Florida 33126 Totd /1/S: 244
TEL:(305) 403-4455 FAX:(305) 403-4488 Contract ND. 7
State Certification # 56528000012005 09- FP-3 Of �J