1. THE PROJECT IS "NEW CONSTRUCTION'.
THE CONTRACTOR SHALL VISIT THE JOB SITE TO DETERMINE THE EXTENT OF WORK
INVOLVED WITHIN THESE DOCUMENTS OR AS SHOWN IN THE DRAWINGS. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
ALLOW FOR ANY CHANGES THAT MAY BE MADE DURING THE COMPLETION OF THE JOB.
ANY ELECTRICAL WORK THAT MAY HAVE TO BE DONE TO COMPLETE ANY PORTION OF
THE JOB OR ANY ELECTRICAL ALTERATIONS SHOWN ON ANY PLAN (INCLUDED BUT
NOT LIMITED TO ELECTRICAL DRAWINGS) SHALL BE INCLUDED IN THIS CONTRACT
WITH NO ADDITIONAL CHARGES TO THE OWNER AFTER THE CONTRACTS ARE LET.
2. ALL WORK TO BE PERFORMED AND ALL IMPLEMENTATION ASPECTS OF THE REQUIREMENTS
AWARDED,OF THESE DRAWINGS SHALL BE IN FULL ACCORDANCE WITH THE LATEST
NEC EDITION AND APPLICABLE LOCAL CODES.
3. THE CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT REQUIRED
FOR A COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS
4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS, INCLUDING REQUIRED
CONNECTORS, FITTINGS, LUGS, CONTACTORS AND OTHER HARDWARE REQUIRED TO MAKE
THE SYSTEM OPERATIONAL. THIS ALSO INCLUDES THE COORDINATION OF RECEPTACLES
TO EQUIPMENT PLUGS AND CONNECTORS.
5. REQUEST FOR SUBSTITUTION OF SPECIFIED EQUIPMENT, COMPONENTS AND MATERIALS
SHALL BE APPROVED BY THE ARCHITECT AND THE ENGINEER OF RECORD AT LEAST TEN
(10) DAYS PRIOR TO BID.
6. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT ALL DRAWINGS) REQUIREMENTS ARE
MET AND NO CHANGES ARE MADE WITHOUT THE PREVIOUS APPROVAL OF THE ARCHITECT
OR ELECTRICAL ENGINEER OF RECORD; AND THE PROPER APPLICABLE AUTHORITIES.
7. THE ARCHITECT OR ELECTRICAL ENGINEER OF RECORD SHALL BE NOTIFIED OF ANY
CONDITION NOT CONSISTENT WITH THE ELECTRICAL DEFINITION PROVIDED, CURRENT
NEC EDITION, OR APPLICABLE BUILDING CODES; WHICH WILL NOT BE REMEDIED AS A
RESULT OF THIS WORK.
8. THE ELECTRICAL CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS, COORDINATE
THE NECESSARY INSPECTIONS, AND COORDINATE WITH THE APPLICABLE UTILITY
COMPANIES, THE IMPLEMENTATION OF THIS WORK.
9. ELECTRICAL DRAWINGS ARE NOT TO SCALE. THE CONTRACTOR SHALL REFER TO ALL
ARCHITECTURAL, CEILING GRID, ELEVATIONS, DETAILS AND OTHER DRAWINGS FOR
EXACT LOCATION OF EQUIPMENT, FIXTURES OUTLETS, SWITCHES AND OTHER ELECTRICAL
COMPONENTS AND CONFIRM WITH THE ARCHITECT OR THE INTERIOR DESIGNER PRIOR
TO START WORK OF ANY POTENTIAL CONFLICT WITH OTHER EQUIPMENT, COMPONENT,
OR STRUCTURAL MEMBER. ANY NON CONFORMITY MUST BE REFERRED TO THE ARCHITECT
PRIOR TO START IMPLEMENTING THIS WORK.
10. EXCEPT AS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER. USE TYPE
"THW/THW'N' STRANDED CABLE FOR CONDUCTORS IN THE SIZES No 8 AND LARGE.
PROVIDE COLOR CODING PER N.E.C.
FOR CONNECTION TO LIGHT FIXTURES AND TRANSFORMERS. USE UQUID TIGHT
CONNECTIONS IN DAMP OR WET LOCATIONS.
11. OUTDOOR UNDERGROUND CONDUITS SHALL BE SCHEDULE-40 PVC.
12. CHECK EQUIPMENT FOR PROPER VOLTAGE, PHASE, AND AMP RATING BEFORE
CONNECTION TO CIRCUITS.
13. ALL MATERIALS SHALL BE NEW AND SHALL BEAR THE UL LABEL WHEN APPLICABLE
ALL ELECTRICAL COMPONENTS SHALL MEET THE REQUIREMENTS OF THE LATEST NEC
EDITION AND APPLICABLE LOCAL CODES, AND APPROVED FOR THE APPLICATION.
14. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF THE
POWER, CAN, DATA AND TELEPHONE COMPANIES. CONTRACTOR SHALL COORDINATE
SERVICE REQUIREMENTS WITH THE UTILITY COMPANIES IF ADDITIONAL LOADS ARE REQUIRED.
ELECTRICAL NOTES
15. ALL CIRCUITS SHALL BE CLEARLY IDENTIFIED AND SHOWN ON PANEL DIRECTORIES.
CONTRACTOR SHALL IDENTIFY ALL CIRCUITS, FEEDERS, JUNCTION BOXES AND OUTLETS
AND PROVIDE A TYPEWRITTEN DIRECTORY IN EACH PANEL BOARD.
16. CIRCUITS ON THE PLAN ARE TO DETERMINE LOAD DATA AND PANEL SIZE. THE
CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB
CONDITIONS, AND BALANCE THE JOB THROUGH -OUT.
17. ROUTING OF RACEWAYS, INTERCONNECTING OUTLETS AND HOME -RUNS IS UP TO THE
ELECTRICAL CONTRACTOR, BUT AFTER COMPLETION OF THE INSTALLATION, HE
SHALL SUBMIT TO THE OWNERS AS -BUILT DRAWINGS OF HIS WORK FOR FUTURE
RECORD.
18. CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION SYSTEM
FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENTS OF THE
FIXTURE. COORDINATE REQUIREMENTS WITH ARCHITECT.
19. PROVIDE ALL REQUIRED CONNECTIONS FOR OTHER TRADES.
20. FURNISH AND INSTALL LIGHTING FIXTURES AND LAMPS AS CALLED FOR ON THESE
PLANS, INCLUDING ALL SCREWS AND TIES TO THE STRUCTURAL MEMBERS AS REQUIRED
21. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
REQUIRED IN ARTICLE 250 OF THE NEC. ALL RACEWAYS TO HAVE EQUIPMENT
GROUND CONDUCTORS, AND WHEN CROSSING BUILDING EXPANSION JOINTS, EXPANSION
FITTINGS WITH BONDING JUMPERS SHALL BE USED.
22. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING ASSOCIATED
WITH HIS/HER INSTALLATION.
23. FIXTURES THAT ARE USED FOR TEMPORARY LIGHTING WILL NOT BE RE -USED.
24. COORDINATE ALL BOX LOCATION WITH SPACE ARCHITECTURAL FEATURES.
25. CONTRACTOR SHALL INSTALL ALL REQUIRED CONDUCTORS TO THE APPROPRIATE SERVICE
TIE-IN POINTS.
26. ALL MOUNTING HARDWARE SHALL BE BY ELECTRICAL CONTRACTOR.
27. CONTRACTORS PERFORMING EQUIPMENT INSTALLATIONS SHALL PROVIDE AND INSTALL
ALL COMPONENTS WHEN REQUIRED. ELECTRICAL CONTRACTOR IS TO INTERFACE SUCH
EQUIPMENT WITH OTHER SYSTEMS E.G. AIR CONDITIONING CONTRACTOR SHALL PROVIDE
AND INSTALL INTERFACE SMOKE DETECTOR RELAY TO FIRE ALARM.
28. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES EQUIPMENT INSTALLATION REQUI-
REMENTS AND PROVIDE ALL NECESSARY CONNECTIONS, WRING AND INSTALLATION OF
REQUIRED MOTOR STARTERS, EQUIPMENT CONTROLS AND SPECIAL PLUGS AND WRING.
29. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS, INCLUDING REQUIRED
CONNECTORS, FITTINGS, LUGS AND OTHER HARDWARE REQUIRED TO MAKE THE SYSTEM
OPERATIONAL THIS ALSO INCLUDES THE COORDINATION OF RECEPTACLES TO EQUIP-
MENT PLUGS AND CONNECTORS.
30. CONTRACTOR SHALL PROVIDE 6 SETS OF SHOP DRAWINGS SUBMITTAL FOR ALL MATERIAL
AND EQUIPMENT TO BE USED FOR APPROVAL BY THE ARCHITECT AND ENGINEER OF
RECORD.
31. ALL EQUIPMENT INSTALLATIONS, AND INTERFACE WITH OTHER SYSTEM AND CONTROLS,
SHALL BE PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURER(S) SPECIFICA-
TIONS, THE REQUIREMENTS OF THESE DRAWINGS, LATEST NEC EDITION AND APPLICABLE
LOCAL CODES. THIS INCLUDES APPLICABLE GROUNDING AND BONDING OF METAL PARTS.
P,,,'OOF PLAN
32. CONTRACTOR SHALL MAINTAIN A SET OF REPRODUCIBLE MEDIA DRAWINGS SHOWING AS
BUILT CONDITIONS AS THEY OCCUR. A COMPLETE SET OF AS -BUILT REPRODUCIBLE
DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ARCHITECT AND ENGINEER
OF RECORD PRIOR TO FINAL ACCEPTANCE OF INSTALLATION. THESE DRAWINGS SHALL
HAVE ALL INSTALLATIONS REFERENCED BY DIMENSIONS TO A SET OF REFERENCE POINT
OR POINTS.
33. CONTRACTOR SHALL FURNISH THE OWNER WITH ALL OPERATING MANUALS AND MAINTE-
NANCE INSTRUCTIONS FOR EQUIPMENT INSTALLED. MANUALS SHALL BE BOUNDED IN
THREE RING LOOSE LEAVE BINDERS AND INDEX BY PRODUCT TYPE, ALSO A SECTION
WITHIN THE MANUAL SHALL BE INDEXED WITH NAME, TELEPHONE NUMBER AND ADDRESS
OF ALL LOCAL SUPPLIERS OF ALL MATERIAL AND EQUIPMENT INSTALLED TOGETHER WITH
NAME, TELEPHONE AND ADDRESS OF ALL CONTRACTORS OF THE PROJECT. PROVIDE 3
SETS TO BE APPROVED BY ENGINEER OF RECORD.
34. ALL WORKMANSHIP AND INSTALLATION PRACTICES SHALL BE IN ACCORDANCE WITH THE
LATEST NEC EDITION, LOCAL CODE REQUIREMENTS, ESTABLISHED STANDARDS OF WORK-
MANSHIP AND WITH THE NECESSARY COOPERATION WITH OTHER TRADES, THE ARCHITECT
SHALL BE THE FINAL AUTHORITY WHEN ESTABLISHING COMPLIANCE TO THESE STANDARDS.
35. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT WORK IS PERFORMED BY PROPERLY
CERTIFIED AND LICENSE PERSONNEL; OR UNDER IMMEDIATE DIRECT SUPERVISION, IF
APPLICABLE.
36. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE FREE
FROM THE DEFECTIVE WORKMANSHIP AND MATERIALS, USUAL WEAR EXPECTED, AND
SHOULD ANY SUCH DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER
ACCEPTANCE BY THE OWNER. SUCH CONTRACTOR SHALL REPAIR AND/OR REPLACE ANY
DEFECTIVE ITEMS AND ALL DAMAGE RESULTING FROM SUCH FAILURE, AT NO EXPENSE
WHAT SO EVER TO THE OWNER.
37. "ELECTRICAL INSTALLATIONS" SHALL CONFORM TO REQUIREMENTS OF N.E.C.110-26 (A)
"CLEARANCES" AND N.E.C. 408 FOR SWITCHBOARDS AND PANEL BOARDS INCLUDING
SPACES ABOVE THE EQUIPMENT.
38. "PRIOR TO INSTALLATION OF ROUGH ELECTRIC WIRING" CHECK NAMEPLATE DATA OF
A/C EQUIPMENT, HOT WATER HEATERS, AND OTHER EQUIPMENT TO OBTAIN CORRECT
WIRE SIZES AND OVERCURRENT.
39. INTERRUPTING CAPACITY RATING OF ELECTRICAL SYSTEMS AND SERVICE EQUIPMENT
SHALL CONFORM AS SET FORTH IN N.E.C. ARTICLES 110-9.
40. ELECTRICAL CONTRACTOR IS TO COORDINATE WITH MECHANICAL AND PLUMBING
CONTRACTORS FOR THE INSTALLATION OF ANY EQUIPMENT TO BE SUPPLIED BY THEM
AND CONNECTED BY UNDER THIS CONTRACT BEFORE ANY WIRING IS TO BE MADE. IN
THE EVENT THE ELECTRICAL CONTRACTOR PROCEEDS WITHOUT THIS COORDINATION HE
AT HIS EXPENSE SHALL REPLACE ANY NON -CONFORMING WRING OR DEVICES.
ANY CHANGES FROM THIS REQUIREMENT SHALL BE APPROVED BY THE ARCHITECT AND
ELECTRICAL ENGINEER OF RECORD.
Jl.&" : I/ RI I. It -OI I
KEY NOTES
O THERMOSTAT, AHU AND CU, OR RTU TO BE FURNISHED AND INSTALLED
BY MECHANICAL CONTRACTOR. POWER AND CONTROL WIRING BY
ELECTRICAL CONTRACTOR AS PER MANUFACTURER
RECOMMENDATIONS. COORDINATE WITH MECHANICAL CONTRACTOR
FOR FINAL LOCATION.
( IF UNIT COMES WITH BREAKER, USE BREAKER AS MEAANS OF
DISCONNECT, IF NOT, INSTALL FUSED DISCONNECT WITH NEMA 3R
ENCLOSURE.
O3 THERMOSTAT AND FAN FURNISHED AND INSTALLED BY MECHANICAL
CONTRACTOR. POWER WIRING AND CONTROL WIRING BY ELECTRICAL
CONTRACTOR AS PER MANUFACTIRER RECOMMENDATIONS.
ELECTRICAL SYMBOLS LEGEND
0
JUNCTION BOX, WITH COVER. INSTALL IN CEILING ,AS SHOWN OR AS REQUIRED.
4
JUNCTION BOX, WITH COVER. INSTALL IN WALL, AS SHOWN OR AS REQUIRED.
®
2 x 4' FLUORENSCENT FIXTURE, 3 x 32 WATTS, 208 V
2 x 4' FLUORESCENT FIXTURE WITH EMERGENCY BALLAST 3 x 32 WATTS, 208V
0
4' FLUORESCENT FIXT. 2 x 32 WATTS, 208 V, WRAP AROUND WITH EMERGENCY BALLAST.
®
EXIT SIGN WITH BATTERY BACKUP
ICI
EXIT SIGN & EMERGENCY LIGHT COMBO WITH BATTERY BACKUP
I�
EMERGENCY LIGHT WITH BATTERY BACKUP.
SINGLE POLE LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS.
INSTALL 48"A.F.F.
3
THREE WAY LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS.
INSTALL 48"A.F.F.
DUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS.
INSTALL 18"A.F.F. UNLESS OTHERWISE NOTED.
DUPLEX GFI RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS.
INSTALL 48"A.F.F.
CUADRUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS.
INSTALL 18"A.F.F. UNLESS OTHERWISE NOTED.
SINGLE RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS.
INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED.
SPECIAL RECEPTACLE OUTLET, 250 VOLTS, 3-WIRE, GROUNDING TYPE, AMPS AS
SHOWN. INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED.
TELEPHONE & DATA OUTLET. INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED.
DATA OUTLET. INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED.
A.F.F.
ABOVE FINISHED FLOOR
W.P.
WEATHER RESISTANT (WEATHER PROOF EQUIPMENT)
A.F.I.
ARC FAULT PROTECTION
G.F.I.
GROUND FAULT INTERRUPTER.
HOME -RUN TO ELECTRIC PANEL.
DISCONNECT SWITCH. 2-NUMBER OF POLES; 60-FRAME SIZE; 0-NO FUSE (FUSE SIZE).
ELECTRICAL PANEL
NOTE,
FIRE ALARM PANEL REQUIRED. SEE SHOP DRAWINGS BY FIRE ALARM CONTRACTOR
UNDER SEPARATE PERMIT.
ALFJANDRO REMOS R.A.
= h=i1e-ts
IIAlejandro Remos R.A. 0011702
-18501 Pines Blvd., Suite 107
Pembroke Pines FL--33029
u Te,: (954`' 442 7122 _
_ II Fa : (954) 4427190
u -e-mail- remosbld9@a6l.com
SOMERSET CHARTER
SCHOOL
South Miami
-5876 SW 68th Street
South Miami, FL 33143
CONSULTANTS:
JEANETH ARDILA
architect
ALBERTO CHINCHILLA
architect
ALEJANDRO CABAL -CABAL
architect
MARCEL ADRIAN PEREZ
architect
-18501 Pines Blvd., Suite 107
Pembroke Pines FL 33029
STRUCTURAL ENG.:
EDUARDO GONZALEZ P.E. INC.
Structural Engineers
State of Florida CA No. 6188
J. Eduardo Gonzalez P.E.
-717 Ponce de Le6n Blvd., Suite 335
Coral Gables FL 33134
Tel: (305) 445 5100
Fax:(305) 445 6644
e-mail: eddygon@bellsouth.net
M.E.P. ENG.:
INGEMEL SA LLC.
ENGINEERING COMPANY
STATE OF FLORIDA CA No. 9113
Pedro Arias P.E. 63813
Patricia Morales P.E. 63818
-20871 Johnson Street, Suite /15
Pembroke Pines FL 33029 USA
Tel: (954) 318 2264
Fax:(954) 450 7216
e-mail: pedroa@ingemel.com
pmorales@ingemel.com
CIVIL ENG.:
Consulting Engeneering
& Science, Inc.
Nelson H. Ortiz P.E. 57556
-10700 North Kendall Drive Suite 400
Miami FL 33176
Tel: (305) 378 5555
Fax: (305) 279 4553
e-mail: nortlz@CESMIAMI.com
LANDSCAPE ARCH.:
M. L. A. GROUP INC.
Scott McClure ALA OSM95
-690 NE 13th Street Suite 105
Fort Lauderdale FL 33304
Tel: (954) 763 4071
Fax: (954) 4671688
e-mail: ndagmupinc@yahoo.com
SEAL:
P.E. 63818
REVISIONS:
Q02 / 06 / 09 As per City Remarks
Q02 / 20 / 09 As per City Remarks
I I Ownees Request
Project No:
USC13-1
Model File:
Drawn by:
J.A / M.A. / A.C.
Approved by:
A.R.
Date:
09/08/08
Scale:
As Shown
Copyright
Sheet Title
ROOF LIGHTING
& POWER PLAN,
SYMBOLS &
NOTES
Sheet Number
E=5
SOMERSET SOUTH MIAMI