09-49-056lm, R E MOS 1 5 F------ 1. THE PROJECT IS "NEW CONSTRUCTION". THE CONTRACTOR SHALL VISIT THE JOB SITE TO DETERMINE THE EXTENT OF WORK INVOLVED WITHIN THESE DOCUMENTS OR AS SHOWN IN THE DRAWINGS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND ALLOW FOR ANY CHANGES THAT MAY BE MADE DURING THE COMPLETION OF THE JOB. ANY ELECTRICAL WORK THAT MAY HAVE TO BE DONE TO COMPLETE ANY PORTION OF THE JOB OR ANY ELECTRICAL ALTERATIONS SHOWN ON ANY PLAN (INCLUDED BUT NOT UMITED TO ELECTRICAL DRAWINGS) SHALL BE INCLUDED IN THIS CONTRACT WITH NO ADDITIONAL CHARGES TO THE OWNER AFTER THE CONTRACTS ARE LET. 2. ALL WORK TO BE PERFORMED AND ALL IMPLEMENTATION ASPECTS OF THE REQUIREMENTS AWARDED,OF THESE DRAWINGS SHALL BE IN FULL ACCORDANCE WITH THE LATEST NEC EDITION AND APPLICABLE LOCAL CODES. 3. THE CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS 4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS, INCLUDING REQUIRED CONNECTORS, FITTINGS, LUGS, CONTACTORS AND OTHER HARDWARE REQUIRED TO MAKE THE SYSTEM OPERATIONAL THIS ALSO INCLUDES THE COORDINATION OF RECEPTACLES TO EQUIPMENT PLUGS AND CONNECTORS. 5. REQUEST FOR SUBSTITUTION OF SPECIFIED EQUIPMENT, COMPONENTS AND MATERIALS SHALL BE APPROVED BY THE ARCHITECT AND THE ENGINEER OF RECORD AT LEAST TEN (10) DAYS PRIOR TO BID. 6. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT ALL DRAWING(S) REQUIREMENTS ARE MET AND NO CHANGES ARE MADE WITHOUT THE PREVIOUS APPROVAL OF THE ARCHITECT OR ELECTRICAL ENGINEER OF RECORD; AND THE PROPER APPLICABLE AUTHORITIES. 7. THE ARCHITECT OR ELECTRICAL ENGINEER OF RECORD SHALL BE NOTIFIED OF ANY CONDITION NOT CONSISTENT WITH THE ELECTRICAL DEFINITION PROVIDED, CURRENT NEC EDITION, OR APPLICABLE BUILDING CODES; WHICH WILL NOT BE REMEDIED AS A RESULT OF THIS WORK. 8. THE ELECTRICAL CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS, COORDINATE THE NECESSARY INSPECTIONS, AND COORDINATE WITH THE APPUCABLE UTILITY COMPANIES, THE IMPLEMENTATION OF THIS WORK. 9. ELECTRICAL DRAWINGS ARE NOT TO SCALE. THE CONTRACTOR SHALL REFER TO ALL ARCHITECTURAL, CEILING GRID, ELEVATIONS, DETAILS AND OTHER DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, FIXTURES OUTLETS, SWITCHES AND OTHER ELECTRICAL COMPONENTS AND CONFIRM WITH THE ARCHITECT OR THE INTERIOR DESIGNER PRIOR TO START WORK OF ANY POTENTIAL CONFLICT WITH OTHER EQUIPMENT, COMPONENT, OR STRUCTURAL MEMBER. ANY NON CONFORMITY MUST BE REFERRED TO THE ARCHITECT PRIOR TO START IMPLEMENTING THIS WORK. 10. EXCEPT AS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER. USE TYPE "THW/THWN' STRANDED CABLE FOR CONDUCTORS IN THE SIZES No 8 AND LARGE. PROVIDE COLOR CODING PER N.E.C. FOR CONNECTION TO LIGHT FIXTURES AND TRANSFORMERS. USE LIQUID TIGHT CONNECTIONS IN DAMP OR WET LOCATIONS. 11. OUTDOOR UNDERGROUND CONDUITS SHALL BE SCHEDULE-40 PVC. 12. CHECK EQUIPMENT FOR PROPER VOLTAGE, PHASE, AND AMP RATING BEFORE CONNECTION TO CIRCUITS. 13. ALL MATERIALS SHALL BE NEW AND SHALL BEAR THE UL LABEL WHEN APPLICABLE ALL ELECTRICAL COMPONENTS SHALL MEET THE REQUIREMENTS OF THE LATEST NEC EDITION AND APPUCABLE LOCAL CODES, AND APPROVED FOR THE APPUCATION. 14. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF THE POWER, CAN, DATA AND TELEPHONE COMPANIES. CONTRACTOR SHALL COORDINATE SERVICE REQUIREMENTS WITH THE UTILITY COMPANIES IF ADDITIONAL LOADS ARE REQUIRED. ELECTRICAL NOTES 15. ALL CIRCUITS SHALL BE CLEARLY IDENTIFIED AND SHOWN ON PANEL DIRECTORIES. CONTRACTOR SHALL IDENTIFY ALL CIRCUITS, FEEDERS, JUNCTION BOXES AND OUTLETS AND PROVIDE A TYPEWRITTEN DIRECTORY IN EACH PANEL BOARD. 16. CIRCUITS ON THE PLAN ARE TO DETERMINE LOAD DATA AND PANEL SIZE. THE CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS, AND BALANCE THE JOB THROUGH -OUT. 17. ROUTING OF RACEWAYS, INTERCONNECTING OUTLETS AND HOME -RUNS IS UP TO THE ELECTRICAL CONTRACTOR, BUT AFTER COMPLETION OF THE INSTALLATION, HE SHALL SUBMIT TO THE OWNERS AS -BUILT DRAWINGS OF HIS WORK FOR FUTURE RECORD. 18. CONTRACTOR SHALL VERIFY THE CEIUNG FINISHES AND SUSPENSION SYSTEM FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENTS OF THE FIXTURE. COORDINATE REQUIREMENTS WITH ARCHITECT. 19. PROVIDE ALL REQUIRED CONNECTIONS FOR OTHER TRADES. 20. FURNISH AND INSTALL LIGHTING FIXTURES AND LAMPS AS CALLED FOR ON THESE PLANS, INCLUDING ALL SCREWS AND TIES TO THE STRUCTURAL MEMBERS AS REQUIRED 21. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED IN ARTICLE 250 OF THE NEC. ALL RACEWAYS TO HAVE EQUIPMENT GROUND CONDUCTORS, AND WHEN CROSSING BUILDING EXPANSION JOINTS, EXPANSION FITTINGS WITH BONDING JUMPERS SHALL BE USED. 22. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING ASSOCIATED WITH HIS/HER INSTALLATION. 23. FIXTURES THAT ARE USED FOR TEMPORARY LIGHTING WILL NOT BE RE -USED. 24. COORDINATE ALL BOX LOCATION WITH SPACE ARCHITECTURAL FEATURES. 25. CONTRACTOR SHALL INSTALL ALL REQUIRED CONDUCTORS TO THE APPROPRIATE SERVICE TIE-IN POINTS. 26. ALL MOUNTING HARDWARE SHALL BE BY ELECTRICAL CONTRACTOR. 27. CONTRACTORS PERFORMING EQUIPMENT INSTALLATIONS SHALL PROVIDE AND INSTALL ALL COMPONENTS WHEN REQUIRED. ELECTRICAL CONTRACTOR IS TO INTERFACE SUCH EQUIPMENT WITH OTHER SYSTEMS E.G. AIR CONDITIONING CONTRACTOR SHALL PROVIDE AND INSTALL INTERFACE SMOKE DETECTOR RELAY TO FIRE ALARM. 28. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES EQUIPMENT INSTALLATION REQUI- REMENTS AND PROVIDE ALL NECESSARY CONNECTIONS, WIRING AND INSTALLATION OF REQUIRED MOTOR STARTERS, EQUIPMENT CONTROLS AND SPECIAL PLUGS AND WIRING. 29. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPONENTS, INCLUDING REQUIRED CONNECTORS, FITTINGS, LUGS AND OTHER HARDWARE REQUIRED TO MAKE THE SYSTEM OPERATIONAL THIS ALSO INCLUDES THE COORDINATION OF RECEPTACLES TO EQUIP- MENT PLUGS AND CONNECTORS. 30. CONTRACTOR SHALL PROVIDE 6 SETS OF SHOP DRAWINGS SUBMITTAL FOR ALL MATERIAL AND EQUIPMENT TO BE USED FOR APPROVAL BY THE ARCHITECT AND ENGINEER OF RECORD. 31. ALL EQUIPMENT INSTALLATIONS, AND INTERFACE WITH OTHER SYSTEM AND CONTROLS, SHALL BE PERFORMED IN ACCORDANCE WITH EQUIPMENT MANUFACTURER(S) SPECIFICA- TIONS, THE REQUIREMENTS OF THESE DRAWINGS, LATEST NEC EDITION AND APPLICABLE LOCAL CODES. THIS INCLUDES APPLICABLE GROUNDING AND BONDING OF METAL PARTS. ffi P,,,OOF PLAN Nor TO x&e 32. CONTRACTOR SHALL MAINTAIN A SET OF REPRODUCIBLE MEDIA DRAWINGS SHOWING AS BUILT CONDITIONS AS THEY OCCUR. A COMPLETE SET OF AS -BUILT REPRODUCIBLE DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ARCHITECT AND ENGINEER OF RECORD PRIOR TO FINAL ACCEPTANCE OF INSTALLATION. THESE DRAWINGS SHALL HAVE ALL INSTALLATIONS REFERENCED BY DIMENSIONS TO A SET OF REFERENCE POINT OR POINTS. 33. CONTRACTOR SHALL FURNISH THE OWNER WITH ALL OPERATING MANUALS AND MAINTE- NANCE INSTRUCTIONS FOR EQUIPMENT INSTALLED. MANUALS SHALL BE BOUNDED IN THREE RING LOOSE LEAVE BINDERS AND INDEX BY PRODUCT TYPE, ALSO A SECTION WITHIN THE MANUAL SHALL BE INDEXED WITH NAME, TELEPHONE NUMBER AND ADDRESS OF ALL LOCAL SUPPLIERS OF ALL MATERIAL AND EQUIPMENT INSTALLED TOGETHER WITH NAME, TELEPHONE AND ADDRESS OF ALL CONTRACTORS OF THE PROJECT. PROVIDE 3 SETS TO BE APPROVED BY ENGINEER OF RECORD. 34. ALL WORKMANSHIP AND INSTALLATION PRACTICES SHALL BE IN ACCORDANCE LATH THE LATEST NEC EDITION, LOCAL CODE REQUIREMENTS, ESTABLISHED STANDARDS OF WORK- MANSHIP AND WITH THE NECESSARY COOPERATION WITH OTHER TRADES, THE ARCHITECT SHALL BE THE FINAL AUTHORITY WHEN ESTABLISHING COMPLIANCE TO THESE STANDARDS. 35. THE ELECTRICAL CONTRACTOR SHALL INSURE THAT WORK IS PERFORMED BY PROPERLY CERTIFIED AND LICENSE PERSONNEL; OR UNDER IMMEDIATE DIRECT SUPERVISION, IF APPLICABLE. 36. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE FREE FROM THE DEFECTIVE WORKMANSHIP AND MATERIALS, USUAL WEAR EXPECTED, AND SHOULD ANY SUCH DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY THE OWNER. SUCH CONTRACTOR SHALL REPAIR AND/OR REPLACE ANY DEFECTIVE ITEMS AND ALL DAMAGE RESULTING FROM SUCH FAILURE, AT NO EXPENSE WHAT SO EVER TO THE OWNER. 37. "ELECTRICAL INSTALLATIONS" SHALL CONFORM TO REQUIREMENTS OF N.E.C.110-26 (A) "CLEARANCES" AND N.E.C. 408 FOR SWITCHBOARDS AND PANEL BOARDS INCLUDING SPACES ABOVE THE EQUIPMENT. 38. "PRIOR TO INSTALLATION OF ROUGH ELECTRIC WIRING" CHECK NAMEPLATE DATA OF A/C EQUIPMENT, HOT WATER HEATERS, AND OTHER EQUIPMENT TO OBTAIN CORRECT WIRE SIZES AND OVERCURRENT. 39. INTERRUPTING CAPACITY RATING OF ELECTRICAL SYSTEMS AND SERVICE EQUIPMENT SHALL CONFORM AS SET FORTH IN N.E.C. ARTICLES 110-9. 40. ELECTRICAL CONTRACTOR IS TO COORDINATE WITH MECHANICAL AND PLUMBING CONTRACTORS FOR THE INSTALLATION OF ANY EQUIPMENT TO BE SUPPUED BY THEM AND CONNECTED BY UNDER THIS CONTRACT BEFORE ANY WIRING IS TO BE MADE. IN THE EVENT THE ELECTRICAL CONTRACTOR PROCEEDS WITHOUT THIS COORDINATION HE AT HIS EXPENSE SHALL REPLACE ANY NON -CONFORMING WIRING OR DEVICES. ANY CHANGES FROM THIS REQUIREMENT SHALL BE APPROVED BY THE ARCHITECT AND ELECTRICAL ENGINEER OF RECORD. KEY NOTES O THERMOSTAT, AHU AND CU, OR RTU TO BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR. POWER AND CONTROL WIRING BY ELECTRICAL CONTRACTOR AS PER MANUFACTURER RECOMMENDATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR FINAL LOCATION. Q2 IF UNIT COMES WITH BREAKER, USE BREAKER AS MEAANS OF DISCONNECT, IF NOT, INSTALL FUSED DISCONNECT WITH NEMA 3R ENCLOSURE. Q3 THERMOSTAT AND FAN FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR. POWER WIRING AND CONTROL WIRING BY ELECTRICAL CONTRACTOR AS PER MANUFACTIRER RECOMMENDATIONS. ELECTRICAL SYMBOLS LEGEND OJ JUNCTION BOX, WITH COVER. INSTALL IN CEILING ,AS SHOWN OR AS REQUIRED. 4 JUNCTION BOX, WITH COVER. INSTALL IN WALL, AS SHOWN OR AS REQUIRED. ® 2 x 4' FLUORENSCENT FIXTURE, 3 x 32 WATTS, 208 V 2 x 4' FLUORESCENT FIXTURE WITH EMERGENCY BALLAST 3 x 32 WATTS, 208V © 4' FLUORESCENT FIXT. 2 x 32 WATTS, 208 V, WRAP AROUND WITH EMERGENCY BALLAST. ® EXIT SIGN WITH BATTERY BACKUP I�1 EXIT SIGN do EMERGENCY LIGHT COMBO WITH BATTERY BACKUP U EMERGENCY LIGHT WITH BATTERY BACKUP. SINGLE POLE LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS. INSTALL 48"A.F.F. 3 THREE WAY LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS. INSTALL 48"A.F.F. DUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 18"A.F.F. UNLESS OTHERWISE NOTED. DUPLEX GFI RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 48"A.F.F. CUADRUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 18"A.F.F. UNLESS OTHERWISE NOTED. SINGLE RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS. INSTALL 18'A.F.F. UNLESS OTHERWISE INDICATED. SPECIAL RECEPTACLE OUTLET, 250 VOLTS, 3-WIRE, GROUNDING TYPE, AMPS AS SHOWN. INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED. -d TELEPHONE do DATA OUTLET. INSTALL 18" A.F.F. UNLESS OTHERWISE INDICATED. -11 DATA OUTLET. INSTALL 18"A.F.F. UNLESS OTHERWISE INDICATED. A.F.F. ABOVE FINISHED FLOOR W.P. WEATHER RESISTANT (WEATHER PROOF EQUIPMENT) A.F.I. ARC FAULT PROTECTION G.F.I. GROUND FAULT INTERRUPTER. HOME -RUN TO ELECTRIC PANEL DISCONNECT SWITCH. 2-NUMBER OF POLES; 60-FRAME SIZE; 0-NO FUSE (FUSE SIZE). ELECTRICAL PANEL NOTE: FIRE ALARM PANEL REQUIRED. SEE SHOP DRAWINGS BY FIRE ALARM CONTRACTOR UNDER SEPARATE PERMIT. SHALL � `imy ' ° Y toVff yr tier ��'i�� p??r -DADt coi IT, IT D�PA S�T� h1 c� BLDG. pB«i.41T SPK---�cTENstor WATER MplN BY i DATE ALEJANDRO REMOS R.A. architects Alejandro Ramos R.A. 0011702 -18501 Pines Blvd., Suite 107 Pembroke Pines FL 33029 Tel: (954) 442 7122 Fax:(954) 442 7190 e-mail: remosbldg@aol.com SOMERSET CHARTER SCHOOL South Miami -5876 SW 68th Street South Miami, FL 33143 CONSULTANTS: JEANETH ARDILA architect ALBERTO CHINCHILLA architect ALEJANDRO CABAL -CABAL architect MARCEL ADRIAN PEREZ architect -18501 Pines Blvd., Suite 107 Pembroke Pines FL 33029 STRUCTURAL ENG.: EDUARDO GONZALEZ P.E. INC. Structural Engineers State of Florida CA No. 6188 J. Eduardo Gonzilsz P.E. -717 Ponce de Le6n Blvd., Suite 335 Coral Gables FL 33134 Tel: (305) 445 5100 Fax:(305) 445 6644 e-mall: eddygon@bellsouth.net M.E.P. ENG.: INGEMEL SA LLC. ENGINEERING COMPANY STATE OF FLORIDA CA No. 9113 PedroArlas P.E.83813 Patricia Morales P.E. 63818 -20871 Johnson Street, Suite 115 Pembroke Pines FL 33029 USA Tel: (954) 318 2264 Fax:(954) 450 7218 e-mall: pedroa@ingemel.com pmorales@ Ingemel.00m CIVIL ENG.: Consulting Engeneering & Science, Inc. Nelson H. Ortiz P.E. 57556 -10700 North Kendall Drive Suite 400 Miami FL 33178 Tel: (305) 378 5555 Fax (305) 279 4553 e-mail: norttz@CESMIAMI.com LANDSCAPE ARCH.: M. L. A. GROUP INC. Scott McClure RLA 8868895 -690 NE 13th Street Suite 105 Fort Lauderdale FL 33304 Tel: (954) 763 4071 Fax:(954) 4671688 e-mail: rnlagroupinc@yahoo.com SEAL: P.E.63818 REVISIONS: 1Q 02/06/09 BLDG. OPT. COMMENTS n\ No: I USC13-1 Wdel File: Drawn by: J.A / M.A. / A.C. Approved by: A.R. Date: 1 09/08/08 Scale: I As Shown Copyright Sheet Title ROOF LIGHTING & POWER PLAN, SYMBOLS & NOTES Sheet Number E=5 SOMERSET SOUTH MIAMI