09-49-048GENERAL NOTES: A CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIALS, LABOR, PERMIT FEES AND INSPECTIONS FOR A COMPLETE HVAC INSTALLATION IN ACCORDANCE TO THESE DIAGRAMATICAL DRAWINGS B. MATERIAL AND WORKMANSHIP SHALL BE IN ACCORDANCE TO THE LATEST EDITION OF THE FLORIDA BUILDING CODE, AND ALL LOCAL CODES AND ORDINANCES. C. CONTRACTOR SHALL BASE HIS BID AFTER FAMILUWZNG HIMSELF WITH ALL EXISTING ASSUILT CONDITIONS. D. CONTRACTOR SHALL OBTAIN APPROVAL OF SHOP DRAWINGS, SUBMITTALS OF MATERIAL AND EQUIPMENT TO SUBSTITUTE BASIS OF DESIGN EQUIPMENT AND MATERIALS NOTED ON THESE DRAWINGS TEN DAYS PRIOR TO BID DATE. AFTER THIS DATE NO SUBSTITUTIONS SHALL BE ADMITTED. 2. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC, THEY DO NOT SHOW EVERY BEND, OFFSET, ELBOW OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES. 3. CONTRACTOR SHALL VERIFY ALL EQUIPMENT, DUCTWORK, DIFFUSERS AND GRILLES TO WORK AND FIT PROPERLY WITH ALL OTHER TRADES AND ASSURE THAT THESE ITEMS DO NOT CONFLICT WITH OTHER TRADES AND WITH ELECTRICAL FIXTURE LOCATIONS. 4. DRAWINGS ARE NOT TO BE SCALED. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE ARCHITECTURAL AND/OR STRUCTURAL DRAWINGS, AND SITE CONDITIONS SHALL GOVERN EXACT LOCATION OF MECHANICAL EQUIPMENT AND APPURTENANCES. 5. VERIFY EXACT ROUTING OF DUCTWORK AND CONDENSATE DRAINS WITH STRUCTURAL ELEMENTS. LOCATION AND SIZE OF ALL SLEEVES THROUGH STRUCTURAL ELEMENTS SHALL BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO EXECUTION. 8 CONTRACTOR SHALL TEST AND BALANCE ALL THE WAC SYSTEMS, AND ADJUST ALL CONTROLS AND EQUIPMENT FOR PROPER OPERATION. TEST S BALANCE SHALL BE DONE N ACCORDANCE WITH SECTION 13410.1 ABCA OF THE FLORIDA BUILDING CODE. 7. COORDINATE EXACT LOCATION OF ALL SUPPLY S RETURN AIR CEILING DEVICES WITH ARCHITECTURAL CEILING GRID 8 LIGHT FIXTURE LOCATIONS. 8. EQUIPMENT SHALL HAVE CAPACITIES REQUIRED TO OBTAIN A SUITABLE OPERATING BALANCE BETWEEN ASSOCIATED ITEMS OF EQUIPMENT. ALL DAMPER 8 CONTROLS SHALL BE ADJUSTED TO OBTAIN THE REQUIRED CAPACITIES UNDER ACTUAL OPERATING CONDITIONS OF EACH SYSTEM AS INSTALLED, OPERATING POWER REQUIREMENTS FOR EACH ITEM OF EQUIPMENT SHALL NOT EXCEED THE RATED MOTOR HORSEPOWER 9. CONSTRUCT DUCTWORK FROM ONE AND ONE HALF INCH FIBERGLASS DUCTBOARD (R=6.5) FOR ALL INDOOR AIR CONDITIONED SUPPLY AND RETURN DUCTWORK SHEET METAL. DUCTS SHALL BE USED FOR EXHAUST, AND NONL•ONDMONED OUTSIDE AIR INTAKE- FABRICATE, SEAL AND INSTALL PER LATEST SMACNA LOW VELOCITY DUCT MANUAL RECOMMENDATIONS. SIZES NOTED ARE CLEAR INSIDE DIMENSIONS PROVIDE AIR VOLUME EXTRACTORS, SPUTTER DAMPERS OR ADJUSTABLE TURNING VANES AT ALL BRANCH TAKE-WS AS REWIRED FOR PROPER AIR BALANCING. FLEXIBLE DUCTWORK SHALL BE THERMAFLEX MODEL MN(C, UL 191 CLASS 1 AIR DUCT OR SIMILAR. 10. COOLING SYSTEMS ARE DESIGNED FOR 751 DB INSIDE CONDITIONS WITH OUTSIDE TEMPERATURE OF 917 DS, TrF INS. HEATING IS DESIGNED TO MAINTAIN MINIMLIM INSIDE TEMPERATURES OF 77F DS WITH AN OUTSIDE TEMPERATURE OF 467 DB. 11. AIR DISTRIBUTION DEVICES SHALL BE CONSTRUCTED OF ALUMINUM, AS MANUFACTURED BY METALAIRE, OR SIMILAR ALL WITH OPPOSED BLADE DAMPER WHERE APPLICABLE AND TR TRANSITION WHERE INDICATED. ALL GRILLAGE SHALL BE PANTED OF SAME COLOR OF THE CEILING OR DOOR IN WHICH IT IS LOCATED AND ALL SCREWS SHALL BE OF THE COUNTERSUNK TYPE ALSO PANTED AS GRILLAGE. 12. PROVIDE ACCESS PANELS IN ALL WALL AND CEILING FOR ALL VALVES, DAMPERS, CONTROL DEVICES, ETC. ACCES PANELS SHALL BE MILCOR FLUSH TYPE, MINIMUM OF 245Q4 UNLESS NOTED OTHERWISE. 13 THE WORD PROVIDE' MEANS TO SUPPLY AND INSTALL 14. AIR COOLED CONDENSING UNITS TO BE AS SCHEDULED. PROVIDE EACH UNIT WITH ANTI -CYCLING DEVICE, HIGH AND LOW PRESSURE CONTROLLERS, AND FILTER DRYER 15 INSULATE REFRIGERANT SUCTION PIPE WITH 112 INCH THICK ARMPFLEX FINISH INSULATION EXPOSED TO WEATHER WiTH TWO COATS OF GLASSFAB AND MASTIC. 16. COORDINATE ALL WORK WITH OTHER TRADES INVOLVED. THIS INCLUDES WALL AND ROOF PENETRATIONS, REWIRED ELECTRICAL SERVICE AND CONTROL WIRING. PLUMBER IS TO PROVIDE A MINIMUM 1 114INCH CONDENSATE TRAP SEAL, AT EACH UNIT. 17. CONDENSATE PIPING MUST HAVE A MINIMUM PITCH OF 1hr PER FOOT AS PER FLORIDA PLUMBING CODE IF NECESSARY CONTRACTOR MUST INSTALL CONDESATE PUMP TO WARMTEE PROPER CONDESATE DISPOSAL. 18. ALL AIR CONDITIONING CONDENSATE DRAIN PIPING SHALL BE SCH 40 PVC, EXCEPT WHEN INSTALLED IN AIR PLENUMS WHERE COPPER TYPE'DWN' OR EQUIVALENT MUST BE USED. INSULATE CONDENSATE PIPING WITH 3/4, ARMPFL EX. PROVIDE TRAP WITH CLEAN OUT AND UNIONS FOR CONDENSATE PIPING. 19 INSULATION: A PIPE INSULATION: AIR CONDITIONING CONDENSATE PIPING SHALL BE INSULATED WITH 314' FIRE RATED FLEXIBLE FOAM INSULATION, FINISHED, WHERE EXPOSED B. FLAME AND SMOKE RATING: ALL INSULATION PRODUCTS AND MATERIALS USED FOR THIS PROJECT SHALL HAVE A MAXIMUM FLAME SPREAD AND SMOKE DEVELOPED RATING OF 25M RESPECTIVELY IN ACCORDANCE WITH TESTS OUTLINED IN NFPA 255. C. PROVIDE INSULATION PROTECTORS AT HANGERS FOR ALL INSULATED PIPING, GRINNEL CARPENTER 8 PETERMAN OR EQUIVALENT. 20. OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE AVAILABLE FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER THIS CONTRACT, AND PROVIDE READY ACCESSIBILITY TO DAMPERS, VALVES AND OTHER APPARATUS, INCLUDING ANY PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS. 21. THERMOSTAT SHALL HAVE A MAXIMUM HEATING MODE TEMPERATURE SETTING OF 78'F AND A MINIMUM COOLING MODE TEMPERATURE SETTING OF 70 T. IT SHALL BE ADJUSTABLE TO PROVIDE A TEMPERATURE RANGE OF UP TO 10 •F BETWEEN FULL HEATING AND FULL COOLING, HEATING AND COOLING TO BE NONOONCURREW. THERMOSTAT TO HAVE REQUIRED STAGES OF COOLING AND HEATING FOR COMPATIBILITY WiTH AIR CONDITIONING EQUIPMENT PROVIDED. ALL THERMOSTATS SHALL BE OF THE PROGRAMMABLE TYPE 22. ALL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATORS AND INSTALLED AS RECOMMENDED BY EQUIPMENT MANUFACTURER 23. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING AND VENTILATING EQUIPMENT BEFORE STARTING THEM. THESE FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER 24. ALL CONDENSING UNITS SHALL BE PROPERLY INSTALLED ACCORDING TO THE LATEST EDITION OF THE FLORIDA BUILDING CODE. 25. INSTALL REMOTE TEST STATION FOR DUCT MOUNTED SMOKE DETECTOR RTU­2 AND ERV•1. TEST STATION MUST BE MOUNTED IN A VISIBLE LOCATION AND MUST BE MOUNTED 44r A.F.F. 2& INSTALL ACCESS DOOR IN SUPPLY DUCT FOR ACCESS, CLEANING AND INSPECTION OF SMOKE DETECTOR 27. OUTDOOR AIR QUALITY PRECAUTIONS: A THE CONTRACTOR SHALL ALLOW FOR NECESSARY PRECAUTIONS DURING CONSTRUCTION AND THEREAFTER FOR THE INSTALLATION AND HANDLING OF REFRIGERANTS ALL WORK ASSOCIATED WITH THE REFRIGERATION SYSTEM AND REFRIGERATION HANDLING SHALT. BE IN ACCORDANCE WITH ASHRAE 15.2007. TIE CONTRACTOR SHALL PREPARE WRITTEN DIRECTIONS BY WHICH THE BIJBDING OWNER OR ITS REPRESENTATIVE WILL BE ABLE TO HANDLE REFRIGERANT IN A SAFE AND APPROVED MANNER 28. VERIFY ALL VOLTAGES WITH ELECTRICAL CONTRACTOR BEFORE ORDERING ANY EQUIPMENT. 29. FIRESMOKE DAMPERS, AS APPROVED BY LOCAL GOVERNING AUTHORITIES, SHALL BE INSTALLED IN ALL DUCTWORK PASSING THRU A FLOOR, ROOF, FIRE PARTITION OR FIRE WALL (PROVIDE ACCESS) REQUIRED BY BUILDING CODES 30. ALL DUCT AND PIPE PENETRATIONS OF EXISTING FIRE RATED PARTITIONS SHALL BE SEALED WITH APPROVED FIRE RATED SEALANT TO MAINTAIN THE INTEGRITY OF THE SYSTEM 31. CONTRACTOR SHALL FURNISH THE OWNER PATH ALL OPERATING MANUALS AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT INSTALLED. MANUALS SHALL BE BOUNDED IN THREE RING LOOSE LEAVE BINDERS AND INDEX BY PRODUCT TYPE ALSO A SECTION WITHIN THE MANUAL SHALL BE INDEX PATH NAME, TELEPHONE NUMBER AND ADDRESS OF ALL LOCAL SUPPLIERS OF ALL MATERIAL AND EQUIPMENT INSTALLED TOGETHER WITH NAME, TELEPHONE AND ADDRESS OF ALL CONTRACTORS OF THE PROJECT. 32. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP, AND MATERIALS, USUAL WEAR EXPECTED, AND SHOULD ANY SUCH DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE BUILDING BY THE OWNER CONTRACTOR SHALL REPAIR AND10R REPLACE ANY DEFECTIVE ITEMS AND ALL DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO EXPENSE WHATSOEVER TO THE OWNER COMPRESSOR SHALL CARRY 5 YEAR FACTORY WARRANTY. 33. CONTRACTOR SHALL PROVIDE 3 SETS OF SHOP DRAWINGS, SUBMITTALS FOR ALL MATERIAL AND EQUIPMENT TO BE USED IN THIS PROJECT FOR APPROVAL BY ARCHITECTIENGINEER 34. CONTRACTOR SHALL MAINTAIN A SET OF REPRODUCIBLE SEPIA DRAWINGS SHOWING AS BUILT CONDITIONS AS THEY OCCUR COMPLETE SET OF ELECTRONIC (CAD) AS -BUILT REPRODUCIBLE DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ARCHITECTIENGINEER PRIOR TO FINAL ACCEPTANCE OF INSTALLATION. THESE DRAWINGS SHALL HAVE ALL INSTALLATIONS REFERENCED BY DIMENSIONS TO A SET REFERENCED POINT OR POINTS. 35. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING HOURS OF WORK TIME AVAILABLE TO HIM WITH LANDLORDA ANDLORD S REPRESENTATIVE. ONE (1) COAT OF EPDXY BASED ADHESIVE BONDING AGENT BETWEEN NEW AND EXISTING EXTERIOR ESCUTCHEON PLATE ON ONE OR BOTH SIDES WHERE PIPING IS EXPOSED (TYPICAL) METAL JACKETING (WEATHERPROOF) WATERPROOF CAULK (TYPICAL) PIPE SLEEVE FOR NEW CONCRETE OR CMU WALLS OR CORE DRILL FOR EXISTING CONCRETE WALLS NEW OR EXISTING POURED CONCRETE OR NEW CMU WALL DETAIL - PIPE SLEEVE STEEL FACTORY FABRICATED 14' HIGH ROOF CURB ANCHORED TO STEEL JOIST CONC. PC -JOIST CUT OPENING IN EXISTING CMU WALL LARGER THAN SLEEVE AND FORM 8 FILL WITH EXPANSIVE TYPE GROUT EXISTING CMU WALL t ; •� • ANCHOR LUGS (MINIMUM 3 REQUIRED) PIPE SLEEVE PIPE • _ ` INSULATION (WHERE REQUIRED) �,• INTERIOR ' �•• ANCHOR LUGS 4'. •:1 (MINIMUM 3 REQUIRED) f, '� •;•. • ,, -� NOTE: 1. FOR EXTERIOR WALLS ABOVE GRADE ONLY WEATHERPROOF METAL COVER TO 11 1 II Im •X4•xwALL. AAMM OPSNM4 tW by TIM ea"TS ILV HITS 4 IIIYH�R. ROOFTOP UNIT CURB MOUNTING DETAIL NOT TO SCALE #10 TEK SCREWS - 1" LONG (c13 12 IN. ON CENTERS ON ALL FOUR SIDES NOT TO SCALE SEQUENCE OF OPERATION SPACE TEMPERATURE III SPACE HUMDi7Y CONFIGURATION HOT GAS REHEAT PACKAGE ROOFTOP UNIT: ASPACE TEMP 1 SPACE HUMIDITY OCCUPIED CONTROL (MP58Ir CONTROL OF THE TRANE HOT GAS REHEAT OX ROOFTOP UNIT IS ACCOMPLISHED THROUGH A DEDICATED STANDALONE CONTROL MODULE (MP581). ONE MP581 WILL BE INSTALLED ON EACH ROOFTOP UNIT (FrM THIS CONTROLLER UTBJZES FIVE TEMPERATURE SENSORS AND ONE HUMIDITY SENSOR THE FUNCTION OF THIS CONTROLLER IS TO MAINTAIN A PROGRAMMED SPACE AIR TEMPERATURE AND HUMIDITY. THE FIRST TEMPERATURE SENSOR (DXSUPPLY) IS MOUNTED AFTER THE DX EVAPORATOR COIL. THIS TEMPERATURE SENSOR WILL BE USED BY THE MP581 TO CONTROL THE COMPRESSORS TO MAINTAIN A 55 DEGREE (PROGRAMMABLE) DRY BULB TEMPERATURE SETPWNT IN THE COOLING MODE. ON MULTIPLE COMPRESSOR APPLICATIONS THE FIRST COMPRESSOR IS ENERGIZED AT 51 DEGREE AND THE SECOND 55. THE SECOND COMPRESSOR IS SHUT OFF AT 49 DEGREES AND THE FIRST 44. THESE SETTINGS ARE ADJUSTABLE THE NEXT TEMPERATURE SENSOR (ZONETEMP) IS FIELD MOUNTED IN THE SPACE AND WILL BE USED BY THE MP581 TO ENABLE THE COOLING OR HEATING MODE IN THE COOLING MODE THE (DXSUPPLY) SENSOR IS ACTIVE AND STAGING COMPRESSORS AS PER THE ABOVE PARAGRAPH. ONCE TEMPERATURE SETPOINT 14 REACHED AN ANALOG SIGNAL IS SENT TO THE FACE S BYPASS DAMPER ACTUATOR TBOAMPER) TO MODULATE FREE CONDENSER HEAT INTO THE AIRSTREAM TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. THE SPACE TEMPERATURE IS ADJUSTABLE BASED ON THE SENSOR SETPOINT DIAL INPUT (NNE). AFTER A 3 DEGREE DEADSAND HEATING IS ENABLED. TWO STRAP -ON TEMPERATURE SENSORS (STS-I 8 2) WILL BE USED N THE SYSTEM, STRAP -ON TEMPERATURE SENSOR 01(STS-1) WILL BE LOCATED N THE SUCTION LINE OF CIRCUIT 91. THIS TEMPERATURE SENSOR WILL DISABLE BOTH COOLING CIRCUITS WHEN THE TEMPERATURE GOES BELOW 28 DEGREES AND ENABLE THEM ABOVE 38. STRAP -ON TEMPERATURE SENSOR N2 (STS-2) WILL BE LOCATED IN LIQUID LINE OF COMPRESSOR Aft. THIS TEMPERATURE SENSOR WILL ENABLE CONTROL OF CONDENSER FAN N2 BY THE W581 WHEN THE LIQUID LINE TEMPERATURE EXCEEDS 90 DEGREES. UNDER 85 DEGREES THE FAN IS DISABLED. ON SINGLE CONDENSER FAN UNITS AVARUBLE SPEED CONTROLLER MODULATES THE SPEED OF THE FAN. THE LAST TEMPERATURE SENSOR (OASUPPLY) IS MOUNTED IN THE CONDENSER SECTION AND MONITORS THE OUTDOOR AIR TEMPERATURE. A HUMIDITY SENSOR (ZONEHUM) IS FIELD MOUNTED IN THE SPACE AND WILL BE USED BY THE MP581 TO RESET THE DXSUPPLY SET POINT DOWN IF THE SPACE HUMIDITY RAISES ABOVE THE ADJUSTABLE HUMIDITY SETPOINT. THE DXSUPPLY SETPOINT WILL STAY LOWERED UNTIL THE HUMIDITY SETPOINT IN THE SPACE IS SATISFIED, AT WHICH TIME IT WILL BE RELEASED BACK TO THE NORMAL. COOUNG SErPOINT, IF THE SPACE HUMIDITY DROPS BELOW THE HUMIDITY SETPOINT AND THE SPACE TEMP IS SATISFIED, THEN THE DXSUPPLY SETPOINT WILL BE RESET UP TOWARD THE PROGRAMMED HIGH LIMIT. WHEN HEATING IS CALLED FOR (BASED ON THE ZONETEMP TEMPERATURE), THE MPMl WILL GO INTO HEATING MODE AND THE HEATING STAGES WILL BE BROUGHT ON AS REONRED TO MAINTAIN THE ZONETEMP HEATING SET POINT (PROGRAMMABLE) THE MP581 IS PROGRAMMED TO MAINTAIN THE SPACE TEMPERATURE SET POINT (FOR HEATING AND COOLING). LOW AND HIGH LIMITS OF 68 AND 78 ARE PROGRAMMED FOR COOLING AND HEATING RESPECTIVELY, THE MPSB1 HAS ALL OF THESE FUNCTIONS PRE-PROGRAMMED, HOWEVER SINCE IT IS FULLY PROGRAMMABLE, THE SET POINTS AND SEQUENCE CAN BE MODIFIED IF REWIRED. S. FAN PROVING DEVICE: A CONTACT CLOSURE INTO THE MP581 INE WILL INDICATE TO THE MP581 PROOF OF AIRFLOW FROM A DIFFERENTIAL PRESSURE SWITCH ALLOWING EITHER COOLING OR HEATING TO OPERATE C.000UPEDAINOCCUPIED CONTROL A CONTACT CLOSURE INTO THE MP581 N-7 WALL INDICATE TO THE MP581 AN OCCUPIED MODE OF OPERATION (THE MP581 WILL OPERATE IN THE UNOCCUPIED MODE WHILE THE CONTACTS INTO IN-7 ARE OPEN). THE DRY CONTACT INPUT WILL BE WIRED FROM EITHER A TIME CLOCK OR THE BUILDING ENERGY MANAGEMENT SYSTEM. D.UN000UPIED MODE: WHEN THE MP58118 INDEXED TO THE UNOCCUPIED MODE, THE SUPPLY FAN WILL BE OFF AND THE COOLING AND HEATING STAGES WILL BE OFF. AN UNOCCUPIED SET POINT CAN BE PROGRAMMED IN THE MP581 TO BRING ON THE SUPPLY FAN AND COOLING AND/OR HEATING TO A SETBACK TEMPERATURE. E. RTU SHUTDOWN CONTROL: A DRY CONTACT OPENING ACROSS TERMINALS 16 AND 17 ON THE LTB BOARD IN THE RTU WILL PUT THE RTU IN A FIRE SHUTDOWN MODE OF OPERATION (CONTACT BY OTHERS) A MOUNTING ANGLES FASTENED TO SLEEVE AT 6" O C. (MIN 2 CONNECTIONS ON FIRE RATED WALL EACH SIDE) 114' CLEARANCE PER FOOT B BREAKAWAY CONNECTION - ANGLE SIZE a SLEEVE AS PER SMACNA STANDARDS C E D TYPE "B• FIRE DAMPER DUCT W1 UL RATING a STAMP DUCT F MANUFACTURER'S SLEEVE H FULLY HINGED CASKETED ACCESS DOOR IN DUCT- 12" X 12" UNLESS NOTED SE -LABEL FIRE 6" MAX. ON ALL SIDES o�Ea EXTERNAL INSULATION TO EXTEND OVER SLEEVE AFTER INSPECTION OF DAMPER INSTALLATION FIRE DAMPER INSTALLATION -- TYP. DETAIL NOT TO SCALE NOTES 1: ACCESS DOOR SHALL BE LOCATED ON SIDE OR BOTTOM OF DUCT AS APPROPRIATE TO ALLOW RESETTING OF DAMPER LINK. FIRE DAMPERS SHALL BE RUSKIN IBD20 STYLE AB' OR APPROVED EQUIVALENT. (A) Retaining Angles: Minimum 1)t" x 1Y22" x 0.054 (16 ga.) Retaining angles must overlap structure opening 1' minimum and cover comers of openings as shown. (B) Clearance: Ye' Per Linear Foot Both Dimensions. (C) Steel Sleeve. (D) Approved Fire Damper (courtain or blade type). (E) Secure Retaining Angles to Sleeve Only On 8' Centers With: 1. X" long Welds Or 2. Y" Botts and Nuts, Or 3. No. 10 Steel Screws, Or 4. Minimun Y1e Steel Rivets. (F) Secure Damper to Sleeve on 8" Center With: 1. )4" long Welds Or 2. Y4" Botts and Nuts, Or 3. No. 10 Steel Screws, Or 4. Minimun No' Steel Rivals. (G) Conned Dud to Sleeve. (H) Install access door. VERTICAL AND HORIZONTAL POSITION ARE SIMILAR GENERAL NOTES: 1. FIRE DAMPER SLEEVE CLEARENCE WITHIN WALL OPENING Clearance requirements for damper sleeves within a wall openinngs are based on Ya" per foot of width (or height) unless otherwise stated In the listing of the assembly. The sleeve may rest on the bottom of the opening, and need not be centered. (Fractional dimensions shall be taken as the next largest foot). The sleeve is retained in the wall opening by the use of steel retaining angles (A). These must overlap the edge of the framing by a minimum of one (1) Inch over and b'e'yond an material In the opening. This means that the minimum width of the retaining angle would be 1 gyp" ( good practice calls for an additional safety factor by making the angle In this case 1 Ys" wide). The dimensions required for the opening shall be those remaining after the opening has been framed and ere resistive materials provided where required. The fire resistive material shall be equal to the requirements for fire resistive material used in the constructed wan so that a continuous rating exists at the wall penetration. The contractor erecting the wall Is responsible for providing the fire resistive material and ooned size openings to achieve the required clearance. 2. MANUFACTURERS' INSTALLATIONS DETAILS The fire damper manufacturers' installation details and Instruction as tested and approved by UL must be used In neu of the above details where applicable. HANGERS MUST NOT DEFORM DUCT SHAPE _uzurro one VIDIM SCREWS SCREWSLFHANGER E BAND - OMITTED ONE HALF -ROUND MAY BE USED LOOPS IF DUCT SHAPE IS MAINTAINED LOAD RATED FASTENERS BAND OF SA AS HANGER 24" DIA. 50' DIA, MAX STRAP HANGERS MAX UPPER AND LOWER HANGER ATTACHMENTS AND DEVICES NOT TO SCALE STRAPS STRAP OR ANGLE STRAP HANGER HANGER STRAPS BAND OF SAME SIZE AS HANGER STRAP OMITTED IF HANGER MIN. LOOPS TRAPEZE HANGER ROD STRAPS SIZE BOLT(S) FOR LOAD NOTES: O STRAPS ARE GALVANIZED STEEL, RODS ARE UNCOATED OR GALVANIZED STEEL Q SIZE BOLTS AND HANGERS IN ACCORDANCE TO SMACNA DUCT CONSTRUCTION STANDARS. LOAD RATED FASTENERS 36' DIA. MAX. 24" DIA. MAX. ROUND DUCTS MINIMUM HANGER SIZES FOR ROUND DUCT Dia. Maximum Wire Dia. Rod Strap Spacing 1010 17 One 12 ga. 1/4" 1' x 22 ga. 11..18.01 1'•18"0 17 112,.. or One 8 ga. RECTANGULAR DUCT HANGERS MINIMUM SIZE MAXIMUM PAIR AT 8 FT SPACING PAIR AT 5 FT SPACING PAIR AT 4 FT SPACING HALF OF STRAP WIRE / ROD STRAP WIRE / ROD STRAP WIRE / ROD DUCT PERIMETER P2.30" 1' x 22 ga. 10 ga. 1' x 22 ga. 12 ga. 11 x 22 ga. 12 ga. P2.72• 1' x 20 ga. 1 /4" 1 • x 22 ga. 1 /4" x 22 ga. F1, DUCT HANGERS DETAIL NOT TO SCALE SUPPLY TRUNK STEEL HANGERS OR META MAN .!` TRAP TO STRUCTURE TYPICAL TRANSITION MAX. 20' ANGLE VOLUME DAMPER W/ LOCKING DEVICE (LAW PRESSURE ONLY) STRUCTURAL CHANNEL � \I/ 45' T�DIT SHEET METAL BRAID( DUCT BRANCH DUCT TAKE -OFF DETAIL MN. 2 HINGES AND 2 LATCHES 1 DKCT1CN OF I I CZ= r AIR PRESSURE DUCT MOUNTED ACCESS DOOR NOT TO SCALE NOT TO SCALE 3/8' X 2 X3/4' RED HEAD BOLTS MATH 2-1/2- MINIMUM EMBEDMENT (MECHANICAL CONTRACTOR TO COORDINATE THIS TYPE OF ANCHORING WITH STRUCTURAL ENGINEER PRIOR TO ANY WORK) CONCRETE SLAB 4 d ° A" ° ®. SUPPLY OPENING STEEL CHANNEL MINIMUM OF 12 GAUGE AHU SUPPORT HANGING DETAIL ANCHORING DETAILS FOR UNIT MOUNTING I' THREADED ROD VIBRATION ISOLATOR (TYP.) AT EACH MOUNTING POINT STEEL ANGLE - ANGLE CUP SECURE TO DRAIN PAN ° 1/2- HANGER ROD (TYP OF 4) SPRING ISOLATOR BOLT MATH WASHER AND NUT NOT TO SCALE -AIR HANDLING UNIT (MOM AS HIGH TIONTION LM CONDENSATE DRAMA LINE AND TRAP (SEE PLBG. DWGS.) AUXILIARY DRAIN PAN NOTE. DRAIN PAN SHALL BE A MINIMUM OF 1-1/2" DEEP AND 3 INCHES LARGER THAN THE UNIT IN WIDTH AND LENIGHT ON ALL SIDES AND SHALL BE CONSTRUCTED OF NOT LESS THAN 24 GAUGE GALVANIZED SHEET METAL WATERTIGHT OF CORROSION RESISTANT MATERIAL TYPICAL AIR HANDLING UNIT MOUNTING DETAIL NOT TO SCALE ANCHOR CONCRETE ANCHORS NOT TO SCALE UNION (TYP) PERFORATED CAP -FLOAT SWTCH WiRED IN SERIES MATH T'STAT CIRCUIT TO SHUT OFF SLOPE AUXILIARY DRAIN PAN (GALVANIZED UNIT IN CASE OF AN OVERFILL TO 1/8' / FT SHEET 18 GA.) 1 1/2- DEEP AND 3- DRAIN PAN. LARGER THAN THE UNIT IN WIDTH dt LENGTH. P-TRAP (3- WATER SEAL) NOTE: INSULATE DRAIN PAN WITH 1/2' THICK FIBERGLASS BLANKET WRATH VAPOR BARRIER OR SHEET FOAMED PLASTIC INSULATION WMTH APPROVED FIRE RATING ON OUTSIDE SURFACE ONLY AHU UNIT DRAIN PAN AND CONDENSATE TRAP DETAIL NOT TO SCALE *LREM0$1 AL=E,lANDRO REMOS R.A. S.r-cNt-Acts Alejandro Remos R"A. 0011702 -18501 Pines Blvd., Suite 107 Pel-r�a oke Pines �:L 33029 T�)I: (954) 4427122 - Fw(95A) 4427190 e-niail: rerrosbldg(Oaol.com SOMERSET CHARTER SCHOOL South Miami -5876 SW 68th Street South Miami, FL 33143 CONSULTANTS: JEANETH ARDILA architect ALBERTO CHINCHILLA architect ALEJANDRO CABAL -CABAL architect MARCEL ADRIAN PEREZ architect -18501 Pines Blvd., Suite 107 Pembroke Pines FL 33029 STRUCTURAL ENG.: EDUARDO GONZALEZ P.E. INC. Structural Engineers State of Florida CA No. 6188 J. Eduardo Gomilez P.E. .717 Ponce de Latin Blvd., Suite 335 Coral Gables FL 33134 Tel: (305) 445 5100 Fax:(305) 445 6644 e-rtlaB: eddygon@bellsouth.net M.E.P. ENG.: INGEMEL SA LLC. ENGINEERING COMPANY STATE OF FLORIDA CA No. 0113 Pedro Arias P.E. SM13 Patriots Morelos P.L 63818 -20871 Johnson Street, Suite 115 Pembroke Pines FL 33029 USA Tel: (954) 318 2264 Fex:(954) 450 7218 e-mail: pedroa@ingemel.com pmorales@ingemei.com CIVIL ENG.: Consulting Engineering & Science, Inc. Nelson H. Ortiz P.E. 57556 -10700 North Kendall (rive Suite 400 Mlaml FL 33178 Tel: (3D5) 378 5555 Fax: (305) 279 4553 e-mil: nordz@CESMIAMI.com LANDSCAPE ARCH.: M. L. A. GROUP INC. Scott McClure RLA 6666M -690 NE 13th Street Suite 105 Fort Lauderdale FL 33304 Tel: (954) 783 4071 Fax:(954) 4671688 e-mall: mlagroupinc@yahoo.com SEAL: yt dq V L_ • �C P.E. 63818 REVISIONS: Project No: USC13-1 Model File: Drawn by: A.R. Approved by: P.M.M Date: 09/08/08 Scale: As Shown Copyright Sheet,Title MECHANICAL PLAN se NOTES & DETAILS Sheet Number M=5 SOMERSET SOUTH MIAMI V\1