17-548-02ATTIC ATTIC
FLAT ROOF
®" ELEV
ST.
OPEN TO BELOW OPEN TO BELOW MEZZ.
STAGE AUDITORIUM o =
wy f�~
O
om
CORRIDOR
BELOW
ATTIC OPEN TO BELOW
FIRE ALARM THIRD FLOOR PLAN (NO WORK ON THIS FLOOR)
scale: 1/8" = V - 0"
\ �IEnm Rm{
pi
O KnSIC R�1 \ \
15 1
W \yNl
V SIPPLff TEACHER'S TEACHER'S TEACHER'S
OFFICE OFFICE/ OFFICE
OPEN CORRIDOR R. / "Cl
RES REST
TEACHER'S TEACHER'S TEACHER'S
OFFICE OFFICE OFFICE
DRESSING AREA
STUDENT LOUNGE r
•. I
STORAGE �I
.� �
r-
I � I
FLOOR LEVEL STAGE
®a 1
CLOSET U
VEST. Hj
WOMEN ALL -0 LOBBY CLASSROOM '
STORAGE MEN ® ')
(+g' OPEN CORRIDOR ` ON
•v y,� / SCOPE OF WORK
FIRE ALARM SECOND FLOOR PLAN
scale: 1 /8" = V - 0"
TFffflTW_ j.
Axtroa
6
Hn !
CLASSROOM
I
/
Z.
i
I I
OPEN CORRI R CLASS�OOM
/ 0.
r••straa
CLASSROOM CLASSROOM CLASSROOM CLASSROOM
�. WtlwNcnW' V.
TOILET p i®®®®® e®I
Cu /
DRESS.
DANCE CLASSROOM DANCE CLASSROOM I e
BELL
•1 OFFICE ( CLASSROOM
OPEN CORRIDOR FACP
POC SCOPE OF WORK
U
FIRE ALARM FIRST FLOOR PLAN
scale: 1 /8" = 1' - 0"
PIV AND B.F.P. VALVES (N.T.S.)
BATTERY CALCULATION - FACP - FIRE LITE M59200
Device Type
Qty
Standby / Device
(Amp)
Alarm / Device
(Amp)
Total Standby
Current (Amp)
Total Alarm Current
(Amp)
Main Board
1
0,08000
0.16800
01080000
0,168000
LIDACT-F
1
0.04000
0.07500
0,040000
0.075000
5D350 Smoke Detector
3
0.00030
0.000900
BG- 12LX Pull Station
19
0.00020
0,003800
CRF-300 Control Relay
7
0.00027
0.001890
MMF-301 Mmitor Module
13 1
0,00038
0.004940
D 1
0,00000
0.000000
SD355 Smoke Detector
1
0,00030
0.000300
0
0100000
0.000000
ALL Addressable devices
1
0.20000
0.20000
NAC # 1
1
0,0000
0.000000
NAC # 2
1
0.0000
0.000000
NAC # 3
1
0.0000
0,000000
NAC # 4
1
1
0.0000
0,000000
Totals
0.131830
0,443000
A/H Required Standby
Time (24 Hours)
3.163920
A/H Required Alarm
Time (5 Minutes)
0.037212
Sub Total Standby /
Alarm (Amp/ Mrs)
3,201132
Multiply by the
deratmg Factor (I.2)
3.84
USE BATTERY SIZE
4.0 A/H
BATTERY CALCULATION - FIRE LITE FCP5-24F58 - POWER SUPPLY # I
Device Type
Qty.
Standby/ Device
(Amp)
Alarm / Device
(Amp)
Total Standby
Current (Amp)
Total Alarm Current
(Amp)
Main board
1
0.065
0.145
0,065000
0.145000
Power Supervision Relay
0
0.025
0.025
0.0000
0.000000
S 1 224MC (75) Strobe
6
0.160
0,960000
P 1224MC (75) Horn Strobe
25
0,217
5,425000
P 1224MC (I 1 O) Horn Strobe
2
0.266
0,532000
Totals
0.065000
7.062000
A/H required Standby
Time (24 Hours)
1,560000
A/H required Alarm
Time (5 Minutes)
0,593208
Sub Total Standby /
Alarm (Amp / Hrs)
2,1532
Multiply by the
Derating factor (1.2)
2 58
USE BATTERY SIZE
4.0 A/H
r
• • ••• ••• ••• •
BATTERY CALCULATION - FIRE LITE FCPS-241`58 - POWER SUPPLY #2
Device Type
oty.
Standby / Device
(Amp)
Alarm / Device
(Amp)
Total Standby
Current (Amp)
Total Alarm Current
(Amp)
Main Board
1
0,065
0,145
0,065000
0.145000
Power Supervision Relay
0
0.025
0.025
010000
0.000000
S 1 224MC (75) Strobe
1
0.160
0160000
PI 224MC (75) Horn Strobe
16
0.217
3.472000
Totals
0.065000
3,777000
A/H required Standby
Time (24 Hours)
1,560000
A/H required Alarm
Time (5 Minutes)
0,317268
Sub Total Standby /
Alarm (Amp/ hrs)
1,8773
Multiply by the
Deratmg factor (1.2)
2.25
USE BATTERY SIZE
4.0 A/H
BATTERY CALCULATION - FIRE LITE FCP5-24F58 - POWER SUPPLY #3
Device Type
Qty.
Standby/ Device
(Amp)
Alarm / Device
(Amp)
Total Standby
Current (Amp)
Total Alarm Current
(Amp)
Main Board
1
0.065
0.145
0.065000
0,145000
Power 5upervi5ion Relay
0
0.025
0,025
010000
0.000000
SR (15) Strobe
5
0.066
0.330000
SR (75) Strobe
7
0,158
11106000
PR/ P2RK (75) Horn Strobe
6
0.176
1.056000
Totals
0.065000
2.637000
A/H required Standby
Time (24 Hours)
1,560000
A/H required Alarm
Time (5 Minutes)
0.221508
Sub Total Standby /
Alarm (Amp / Hrs)
1J815
Multiply by the
Deratmg factor (1.2)
2,14
USE BATTERY SIZE
4.0 A/H
PS- I - VOLTAGE DROP CALCULATION - FIRE LITE - FCP5-241`S8 Vd= 2 x D(Ft) x DC Re515t(Ohm/ft) x I(Amp)
DeCircuit 5cr ptlon
NAC I
MaximumLoad
Current
2.425
Volt(Voll 5) nge
-7-6- 33
(AWG)e
14
DC(Ohsm/Ft� ce
0.00307
DI(tFat)ce
220
�oatalge
20.4
Voltage Drop
3.275690
IznVoltage
17.
NAC 2
3.0
2,539
16 - 33
14
0.00307
240
20.4
3,741470
16,66
NAC 3
3.0
1,953
16 - 33
14
0.00307
270
20,4
3,237683
17.16
-20,40
NAC 4
3.0
0.000
16 - 33
14
0,00307
0
e.U.4
0,0000 0
TOTALS
8.0
6,917
P5-2 - VOLTAGE DROP CALCULATION - FIRE LITE - FCP5-24F58 Vd= 2 x D(Pt) x DC Re5i5t(Ohm/ft) x I(Amp)
Circuit De5cr ption
NAC I
Maximum mpLoad
3.0
Cur(Amp) ad
1,736
Volt(VOlt5)
6 - 3
(AWG)e
14
DC(Ohsr /Ft) ce
OA0307
D1 �Ft)ce
160
Voltage rtincj
2014
Voltage Drop
1. 05446
Voltage
.69
NAC 2
3.0
1,896
16 - 33
14
0,00307
170
20,4
1979045
18,42
NAC 3
3.0
01000
16 - 33
14
0,00307
0
20,4
0.000000
20.40
NAC 4
3.0
0.000
16 - 33
14
0.00307
0
N.4
0,00 000
20,40
TOTALS
810
3,632
P5-3 - VOLTAGE DROP CALCULATION - FIRE LITE - FCPS-241`58 Vd= 2 x D(Ft) x DC Re515t(Ohm/ft) x I(Amp)
Circuit
De5cr ptlon
NAC 1
Maxl(AmmpLoad
3.0
Current
0.624
Volt(Volt5)cje
1 - 33
(AAWG)e
1
DC(Ohsm/Ft� ce
. 0307
DI(tFat)ce
130
StartVoltalng ge
4
Voltage Drop
0, 80 7
iricj
Voltage
19.90
NAC 2
3.0
01400
16 - 33
14
0.00307
80
20.4
OS 6480
20.20
NAC 3
3,0
0A24
16 - 33
4
,00307
130
20.4
0.498077
19.90
NAC 4
3.0
0.844
16 - 33
14
0,00307
160
20.4
0,829146
19,57
TOTALS
8,0
492
SCOPE OF WORK
SCOPE OF WORK
APPROVED
MIAMI-DADE COUNTY FIRE DEPARTMENT
%
BLDG. PERMIT FIREALARM -
/
FIRE SUPPRESSION_ WATER MAIN DO.
FIRE ALARM SYSTEM TO BE
INSTALLED IN ACCORDANCE
WITH NFPA 72: 70; 101
II = S SECURITY SYSTEMS
7963 N.W. 14th STREET
DORAL, FLORIDA 33126
TEL : 305.477.9640
FAX: 305.477.1083
w .WSEFS.com
LICENSE #: EC-0001652
NOTIFIFFe
by Honeywell+
no FM
APPROVED
ENGINEERING:
Carlos Rodriguez, P.E.
LIC. #65687
8101 S.W. 104th STREET
MIAMI, FLORIDA 33156
PHONE: (786) 390-8213
Z
OA
cri
O
O
Wz�x
Q
N
cci
z
U
N
'o
a
Revisions:
A
A
ZL
drawing by: L.C.
design by: WSE
date: 01.05.2017
project k 17-0105
scale: as shown
FIRE ALARM
SYSTEM
FA=2
sheet 2 of 4