02-509-15550 I PAC No.4
ROOF
= C C C C
6TH FL,
C C C C
5TH FL,
C C C C
4TH FL.
C C C C
3RD FL.
C C C C
2ND FL.
1 ST FL
ROOF
TYPICAL CONNECTION
FOR ALL UNITS
3#4 & 1#8 (GND)
CU 1 -1/4 -
PHOTOCELL
3#3/0 &
1#10 GND 2"
(2)SETS OF 3#3/0 & 1#3/0 2"
EACH SET TO MAIN CKT. BKR.
No. 2 AT METER ROOM No.3
SERVICE ENTRANCE
RATED FIRE PUMP
CONTROLLER
METER CENTER 4
TO MAIN CKT. BKR.
No.6 AT METER
ROOM No.3
A A C2 C2 A A E E C C
6TH FL.
A
5TH FL.
A
4TH FL.
A
3RD FL.
A
2ND FL.
1 ST FL
A C2 C2 A A E E C C
A C2 C2 A A E E C C
A C2 C2 A A E E C C
A C2 C2 A A E E C C
TYPICAL CONNECTION
FOR ALL UNITS
A2PARTIAL "C" ELECTRICAL RISER DIAGRANkv.T.S
- -
(ELECTRICAL ROOM No.3
PAC
0 No.5
MAIN
No. 6
OF 6
■ 0
O
TAP 'v'
Box • O
.n.
DOM. WTR. PUMP
FIRE
PUMP
TO MDP (3)SETS OF 3#600 MCM
& 1#4/0 THWN ALUM & 1#2/0
CU GND 4" PVC EACH SET
3#6 & 1#10
THHN CU GND
1" PVC
PAC
0 I No.3
3#6 & 1#8 (GND)
CU 1"
C/T CABINET CALCULATION
LOAD DESCRIPTION
LOAD AMPS
L1
L2
L3
NEUT
(2)60HP HYDRAULIC ELEV.
354
354
354
0
PANEL HC
440
440
440
133
PANEL HG
313
313
313
178
TOTAL LOAD AMPS
1107
1107
1107
311
MAIN
No. 5
OF 6
ODI0
n
C/T
■ ■ ■ ■ L
HM HL HC MAIN MAIN MAIN
No.4 No.3 No.2 ss
OF 6 OF 6 OF 6
® ss ss ss
PHOTOCELL
(2)SETS OF 3#500 MCM THWN ALUM. &
1 #350 MCM THWN CU 4" PVC EACH SET
OR (2)SETS OF 4#350 MCM THWN CU 4"
PVC EACH SET
ELEC. CALCULATIONS FOR
METER CENTER 4
RM #4 37 APARTMENTS
( 5-13,32—C UNITS)
JOCKEY
PUMP
RETAIL STORE
—TO PAD MTD. TRANSFORMER TfP. OF 7
3#400 MCM THWN ALUM. &
1#2 THWN CU 4" PVC OR
3#300 MCM THWN CU &
1#2 THWN CU 4" PVC
3#12 & 1#12
THHN CU GND
1/2" PVC
3#1 & 1#6 (GND)
CU 1-1/2"
MAIN
No. 1 ■
OF 6
F ■
■
MDP
(2)SETS OF 3#3/0 & 1 #3/0 2"
EACH SET TO PANEL "HG" AT
ELECTRICAL ROOM No.4
ELEC. NEUTRAL CALCULATIONS
FOR METER CENTER
RM #4 37 APARTMENTS
KW
RANGES
296
AIR CONDITIONING
191
DRYERS
185
WATER HEATERS
167
DISHWASHERS
44
GARBAGE DISPOSALS
26
REFRIGERATORS
26
WASHERS
56
SMALL APPLIANCES
111
LIGHT & RECEPTACLES
105
TOTAL WITHOUT DEMAND
1207
NEC TABLE 220-32
FURTHER DEMAND NEC 220-22
1207 x 29% x 1000=
972 AMPS
360
NEXT 486 ® 70%
JOCKEY
PUMP
RETAIL STORE
—TO PAD MTD. TRANSFORMER TfP. OF 7
3#400 MCM THWN ALUM. &
1#2 THWN CU 4" PVC OR
3#300 MCM THWN CU &
1#2 THWN CU 4" PVC
3#12 & 1#12
THHN CU GND
1/2" PVC
3#1 & 1#6 (GND)
CU 1-1/2"
MAIN
No. 1 ■
OF 6
F ■
■
MDP
(2)SETS OF 3#3/0 & 1 #3/0 2"
EACH SET TO PANEL "HG" AT
ELECTRICAL ROOM No.4
ELEC. NEUTRAL CALCULATIONS
FOR METER CENTER
RM #4 37 APARTMENTS
BY
LTS & RECEPT., SMALL APPL, WASHER
(272 KW)
RANGES
240
JKW
3 KW ® 100%
3
NEXT 117 KW ® 35%
41
NEXT 152 KW ® 25%
38
REFRIG.,DISHWASHER,
GARBAGE DISPOSALS
GARB. DISP. ® 100%
96
RANGES: 15 + 37 x 70%
36
DRYERS: 47.17 x 70%
33
TOTAL KW
247
247,000 +360 = 686 AMPS
TOTAL WITHOUT DEMAND
FURTHER DEMAND NEC 220-22
NEC TABLE 220-32
1st 200 AMPS ® 100%
200
NEXT 486 ® 70%
340
TOTAL AMPS NEUTRAL
540
ELEC. NEUTRAL CALCULATIONS
RM #3 FOR METER CENTER
35 APARTMENTS
BY
LTS & RECEPT., SMALL APPL, WASHER
(227KW)
RANGES
240
xw
3 KW ® 100%
3
NEXT 117 KW ® 35%
41
NEXT 107 KW ® 25%
27
REFRIG.,DISHWASHER,
GARBAGE DISPOSALS
GARB. DISP. ® 100%
92
RANGES: 15 + 35 x 70%
35
DRYERS: 44.6 x 70%
31
TOTAL KW
229
229,000 +360 = 636 AMPS
TOTAL WITHOUT DEMAND
FURTHER DEMAND NEC 220-22
NEC TABLE 220-32
1st 200 AMPS ® 100%
200
NEXT 436 ® 70%
305
TOTAL AMPS NEUTRAL
540
ELEC. CALCULATIONS FOR
RM #3 METER CENTER 1
30 APARTMENTS
( 5—A,5—B,15—C,5—E UNITS)
BY
RM #3 METER CENTER 3
KW
RANGES
240
AIR CONDITIONING
141
DRYERS
150
WATER HEATERS
120
DISHWASHERS
36
GARBAGE DISPOSALS
21
REFRIGERATORS
21
WASHERS
45
SMALL APPLIANCES
90
LIGHT & RECEPTACLES
73
TOTAL WITHOUT DEMAND
937
NEC TABLE 220-32
108
937 x 33% x 1000 = 858 AMPS
360
TOTAL WITHOUT DEMAND
ELEC. CALCULATIONS FOR
BY
RM #3 METER CENTER 3
1
36 APARTMENTS
2
( 1—A,12—B,12—C,11—E
UNITS)
400A, 3P, 208V, DISC. SW., W/RK5 350A FUSES INSIDE ELEV.
MACH. RM.
KW
RANGES
288
AIR CONDITIONING
161
DRYERS
180
WATER HEATERS
144
DISHWASHERS
43
GARBAGE DISPOSALS
25
REFRIGERATORS
25
WASHERS
54
SMALL APPLIANCES
108
LIGHT & RECEPTACLES
82
TOTAL WITHOUT DEMAND
1110
NEC TABLE 220-32
O
1110 x 30% x 1000 = 925
AMPS
360
.O
2" EMPTY PVC
Q PARTIAL "D" ELECTRICAL RISER DIAGRAK.T.S
ELECTRICAL ROOM No.4
ELECTRICAL RISER DIAGRAM EQUIPMENT SCHEDULE
(ALL EQUIPMENT TO BE SIEMENS OR EQUAL)
BY
DESCRIPTION
1
HOUSE METER, PROVIDE AUXILIARY LUGS
2
400A, 3P, 208V, SHUNT TRIP OPERATED. ELEVATOR MAIN CKT.
BKR. 42KAIC
3
400A, 3P, 208V, DISC. SW., W/RK5 350A FUSES INSIDE ELEV.
MACH. RM.
4
SURGE PROTECTION
5
200A, 208V, NEMA 3R, NF DISCONNECT SWITCH
6
SPST TIME SW. FOR CKT. HC2
7
1000A, 3P, 120/208V, TAP BOX
8
METER CENTER WMM64U W/100A, 2P, 22 KAIC, BRANCH BKRS.
FOR TYPE A & E UNITS
9
METER CENTER WMM64U W/125A, 2P, 22 KAIC, BRANCH BKRS.
10
SPST TIME SW. CONNECTED TO LIGHTING CONTACTOR AND
PHOTOCELL
11
6PST LIGHTING CONTACTOR CONNECTED TO TIME SWITCH AND
PHOTOCELL FOR CKTS. HD5/7, HD9/11, HD13 & HD15
(3)SETS OF 3#600 MCM & 1 #4/0
THHN ALUM. 3-1/2" EACH SET
(4)SETS OF 3#500 MCM THWN ALUM. & 1#4/0 THWN
CU 4" PVC EACH SET OR (3)SETS OF 3#600 MCM
THWN CU & 1#4/0 THWN CU 4" PVC EACH SET
ELEV.
MACH.
ROOM
;;P Fa)
ELEC. NEUTRAL CALCULATIONS
FOR METER CENTER
RM #3 30 APARTMENTS
BY
METER CENTER 2
(208KW)
METER CENTER 1
0
JS17L
3 KW ® 100%
3
NEXT 117 KW ® 35%
41
0..0. 0. 0.0.O0 TAP
TAP
•0..0OO..0
•0.O
•
0-0-0-0-0-0-
•0.0.0.0• TAP
METER 0.0.0.0.0.0• BOX
BOX
•O.O.O
•0.O
0.0-6-0-0-0-
BOX
CENTER 3 0.0.0.0.0.0•
WASHERS
0 . 0 . 0
•5.0
•
0.0.0.0.0.0-
•0.0.0.0•O
••
O.0
•O.
O
O.O.
.O.O•
360
.O
OO.O•O
•
-
do"jo.•OO
•O.O..•
00
-O
0
0.
•O.O.•.O.O.100"
:15 c -T -
w
-
G cr
�
088888
Z
88888
0
00
00000
TO METER CENTER AT ELECTRICAL ROOM
No.4
(3)SETS OF 3#600
MCM &
1#4/0 THWN
ALUM
& 1#2/0 CU GND
4" PVC
EACH SET
(4)SETS OF 3#500 MCM THWN ALUM. & 1#4/0 THWN
CU 4" PVC EACH SET OR (3)SETS OF 3#600 MCM
THWN CU & 1#4/0 THWN CU 4" PVC EACH SET
ELEV.
MACH.
ROOM
;;P Fa)
ELEC. NEUTRAL CALCULATIONS
FOR METER CENTER
RM #3 30 APARTMENTS
BY
LTS & RECEPT., SMALL APPL, WASHER
(208KW)
35 APARTMENTS
JS17L
3 KW ® 100%
3
NEXT 117 KW ® 35%
41
NEXT 88 KW ® 25%
22
REFRIG.,DISHWASHER,
DRYERS
GARB. DISP. ® 100%
78
RANGES: 15 + 30 x 70%
31
DRYERS: 39 x 70%
27
TOTAL KW
202
202,000 + 360 = 561 AMPS
WASHERS
FURTHER DEMAND NEC 220-22
SMALL APPLIANCES
1st 200 AMPS ® 100%
200
NEXT 361 ® 70%
253
TOTAL AMPS NEUTRAL
453
ELEC. NEUTRAL CALCULATIONS
FOR METER CENTER
RM #3 36 APARTMENTS
BY
LTS & RECEPT., SMALL APPL., WASHER
(244KW)
35 APARTMENTS
xw
3 KW ® 100%
3
NEXT 117 KW ® 35%
41
NEXT 124 KW ® 25%
31
REFRIG.,DISHWASHER,
DRYERS
GARB. DISP. ® 100%
93
RANGES: 15 + 35 x 70%
35
DRYERS: 46 x 70%
32
TOTAL KW
235
235,000 + 360 = 653 AMPS
WASHERS
FURTHER DEMAND NEC 220-22
SMALL APPLIANCES
1 st 200 AMPS ® 100%
200
NEXT 453 ® 70%
317
TOTAL AMPS NEUTRAL
517
EC. CALCULATIONS FOR
ELECRM .
BY
METER CENTER 2
35 APARTMENTS
( 22—A,1—C,11—C2,1—E
UNITS)
07-29-02
KW
RANGES
280
AIR CONDITIONING
150
DRYERS
175
WATER HEATERS
107
DISHWASHERS
42
GARBAGE DISPOSALS
25
REFRIGERATORS
25
WASHERS
53
SMALL APPLIANCES
105
LIGHT & RECEPTACLES
69
TOTAL WITHOUT DEMAND
1031
NEC TABLE 220-32
1031 x 30% x 1000 =
859
AMPS
360
B B C C A C B E
B B C C A C B E
B B C C A C B E
B B C C A C B E
B B C C A E
120/208, 3P
PAD MOUNTED
TRANSFORMER BY
POWER COMPANY
3#4/0 & 1#3 GND CU 2" PVC
(8)SETS OF 3#600 MCM THWN ALUM. &
REVISIONS
BY
02-28-02
ISSUE FOR PERMIT
07-29-02
2 BLDG. DEPT. CORD.
VJ
Z
W
Ld
l '••� C 0 _
a. - L]
0W w=
-
�� _Q�
Q
-
-O
:15 c -T -
w
-
G cr
�
-
Z
vJ
1 #4/0 THWN CU 4" PVC EACH SET OR DRAWN
(6)SETS OF 3#600 MCM THWN CU & CHECKED
1 #4/0 THWN CU 4" PVC DATE 02-28-02
ERNESTO R. TORRES SCALE
PE# 0049958 E.E. JOB NO. 02013
EB0003862 SHEET
FLORIDA ENGINEERING SERVICES
MECHANICAL AND ELECTRICAL
(2)SETS OF 3#500 MCM THWN ALUM. & ENGINEERS
1 #350 MCM THWN CU 4" PVC EACH ,.SE'J,' .'
OR (2)SETS OF 4#350 MCM
PVC EACH SET •
'i' �' `� ; � '• 34 N.W. 168TH STREET
=�', '• =NORTH MIAMI BEACH, FL 33169
• : TELEPHONE: (305) 653-0212
•'� ' FAX: (305) 653-0232 O F SHEETS