02-509-126GENERAL AIR CONDITIONING NOTES 1. ALL WORK SHALL CONFORM WITH ALL LOCAL, STATE, FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE AIR CONDITIONING SYSTEM. IF WORK AS LAID OUT, INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES, BUILDING CODES AND REGULATIONS, THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT/ENGINEER BEFORE SUBMITTING A BID. THE ARCHITECT/ENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED. 2. THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK, CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN MAXIMUM HEADROOM, AND SPACE CONDITIONS AT ALL POINTS. WHERE HEAD ROOM, OR SPACE CONDITIONS APPEAR INADEQUATE, ARCHITECT/ENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION. THIS CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OF FOR PROPER EXECUTION OF THE WORK. 3. EXAMINE ALL DRAWINGS CAREFULLY PRIOR TO SUBMITTING A BID. CONTRACTOR WILL BE REQUIRED TO FURNISH, INSTALL AND/OR CONNECT WITH APPROPRIATE SERVICES ALL AIR CONDITIONING ITEMS SHOWN ON ANY OF THE ARCHITECTURAL, PLUMBING, ELECTRICAL AND SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO THE OWNER. IF DISCREPANCIES, CONFLICTS, INTERFERENCES OR OMISSIONS OCCUR BETWEEN DRAWINGS, NOTIFY IN WRITING THE ARCHITECT/ENGINEER IN AMPLE TIME TO PERMIT REVISIONS BEFORE THE BIDS ARE SUBMITTED. 4. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER. THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS, WHICH, IN HIS OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE. REMOVAL AND IN WRITING, AT THE SOLE EXPENSE OF CONTRACTOR. 5. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO RECEIVE HIS WORK. THIS CONTRACTOR SHALL REMOVE AND REPLACE, AT HIS EXPENSE, ALL AIR CONDITIONING WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRADES. 6. THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE, FEES, PERMITS ASSOCIATION DUES, ROYALTIES, AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK. HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BYLAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS, RULES OR ORDINANCES. 7. THE WORD "AIR CONDITIONING" MEANS HEATING, VENTILATION, AIR CONDITIONING, DUCTWORK, PIPING, REFRIGERANT LINES, CONTROLS, SMOKE AND FIRE DAMPERS ETC. 8. PROVIDE MEANS "FURNISH AND INSTALL". 9. DO A COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE. 10. SHOP DRAWINGS: THIS CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL. 11. AT COMPLETION OF JOB THE HVAC CONTRACTOR SHALL GIVE THE OWNER AN AS -BUILT SET OF REPRODUCIBLE SEPIAS SHOWING THE EXACT INSTALLATION. 12. WITHIN THE APARTMENTS, STORAGE ROOMS, AND LOBBY FLOOR AREAS, THE HVAC CONTRACTOR SHALL TEST AND BALANCE THE AIR QUANTITIES SHOWN ON THE PLANS. PROVIDE T & B REPORTS IN ACCORDANCE WITH AIR BALANCE COUNCIL STANDARDS, SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER. THE PRIMARY AIR SYSTEMS, SERVING THE CORRIDOR A/C, VENTILATION AND LIFE SAFETY SHALL BE TEST AND BALANCED BY AN INDEPENDENT TEST AND BALANCE FIRM HIRED BY THE BUILDING DEVELOPER. THE HVAC CONTRACTOR SHALL INCLUDE THE COST OF PULLEY AND BELT CHANGES, AND PROVIDE TEST AND BALANCE FIRM WITH SHOP DRAWINGS ON ALL EQUIPMENT, PIPING AND DUCTWORK. DURING CONSTRUCTION, THE HVAC CONTRACTOR, THE HVAC CONTRACTOR SHALL ENSURE AND CONFIRM ADEQUATE SERVICE AND ACCESS CLEARANCES FOR ALL DAMPERS, MOTORS, ETC. 13. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. 14. THE HVAC CONTRACTOR SHALL WARRANT ALL WORKMANSHIP AND MATERIALS FOR ONE YEAR FROM THE DATE OF FINAL WORK ACCEPTANCE BY OWNER. ANY BREAKDOWN OCCURRING IN FIRST YEAR SHALL BE REPAIRED AT NO EXPENSE TO THE OWNER. THE COMPRESSOR (S) SHALL HAVE A FIVE YEAR WARRANTY. 15. MOUNT ALL EQUIPMENT FOR WIND LOADS AND MOUNTING HEIGHTS AS REQUIRED BY LOCAL CODES. 16. MATERIALS A. AIR CONDITIONING RIGID DUCTWORK SHALL BE CONSTRUCTED OF 1" THICK R=4.2 STANDARD DUTY FIBERGLASS BOARD FLAMEPROOF REINFORCED ALUMINUM FACED COVER IN ACCORDANCE WITH S.M.A.C.N.A. AS MANUFACTURED BY Owens-Corning. DUCTWORK SHALL BE FABRICATED AND INSTALLED ACCORDING WITH MANUFACTURER'S INSTRUCTIONS. INSTALL AIR VOLUME EXTRACTORS AT EACH DUCT TAP. B. FLEXIBLE DUCTWORK SHALL BE CLASS I AIR DUCT, U.L. 181 LISTED AS MANUFACTURED BY ATCO FLEXAIRE OR APPROVED EQUAL AND OF R=4.2. INSTALL PER LATEST S.M.A.C.N.A. STANDARDS AND MANUFACTURER'S RECOMMENDATIONS. FLEXIBLE DUCTS SHALL BE CONFIGURED AND SUPPORTED SO AS TO PREVENT THE USE OF EXCESS DUCT MATERIAL, PREVENT DUCT DISLOCATION OR DAMAGE, AND PREVENT THE CONSTRICTION OF THE DUCT BELOW THE RATED DUCT DIAMETER IN ACCORDANCE WITH THE FOLLOWING REQUIREMENTS: 1. DUCTS SHALL BE INSTALLED FULLY EXTENDED. THE TOTAL EXTENDED LENGTH OF DUCT MATERIAL SHALL NOT EXCEED 5 PERCENT OF THE MINIMUM REQUIRED LENGTH FOR THAT RUN. 2. BENDS SHALL MAINTAIN A CENTERLINE RADIUS OF NOT LESS THAN ONE DUCT DIAMETER. 3. TERMINAL DEVICES SHALL BE SUPPORTED INDEPENDENTLY OF THE FLEXIBLE DUCT. 4. HORIZONTAL DUCT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FEET. DUCT SAG BETWEEN SUPPORTS SHALL NOT EXCEED 1/2 INCH PER FOOT OF LENGTH. SUPPORTS SHALL BE PROVIDED WITHIN 1.5 FEET OF INTERMEDIATE FITTINGS AND BETWEEN INTERMEDIATE FITTINGS AND BENDS. CEILING JOISTS AND RIGID DUCT OR EQUIPMENT MAY BE CONSIDERED TO BE SUPPORTS. 5. VERTICAL DUCT SHALL BE STABILIZED WITH SUPPORT STRAPS AT INTERVALS NOT GREATER THAN 6 FEET. 6. HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT MANUFACTURER'S RECOMMENDATIONS AND SHALL BE NOT LESS THAN 1-1/2 INCHES WIDE AND SHALL BE OF SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL DUCT DIAMETER. C. CONDITIONED AIR DUCTWORK SERVING PRIMARY AIR SYSTEM SHALL BE GALVANIZED SHEET METAL WITH 1" THICK, 3LB DENSITY EXTERNAL INSULATION / SOUND LINING. D. DRYER EXHAUST DUCTWORK SHALL BE 26 GAGE ROUND SHEETMETAL SNAP LOCK PIPE OR EQUAL. DRYER EXHAUST DUCTWORK SHALL BE INSTALLED IN STRAIGHT LINE FASHION AND IN COORDINATION WITH OTHER TRADES IN ORDER TO AVOID TRAPS AND DIPS IN THE DUCTWORK. E. TOILET EXHAUST DUCTWORK SHALL BE 26 GAGE GALVANIZED SHEET METALDUCT INSTALLED IN ACCORDANCE WITH THE LATEST SMACNA AND ASHRAE STANDARDS AND MANUFACTURERS RECOMMENDATIONS. F. ALL AIR DEVICES SHALL BE OF ALUMINUM CONSTRUCTION, TITUS, and METALAIRE OR AS APPROVED BY ENGINEER. G. FILTERS SHALL BE OF DISPOSABLE TYPE AND HAVE CLEAN PRESSURE DROP OF 0.15" PROVIDE TWO SETS, ONE DURING CONSTRUCTION AND ONE FOR USE AFTER OCCUPANCY. H. FIRE DAMPERS SHALL BE STYLE "B", U.L. LISTED, 265 F FUSIBLE LINK NCA MODEL V/HB-S-95 OR APPROVED EQUAL AND SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. I. FIRE/SMOKE DAMPERS SHALL BE NCA MODEL FSD-3V-S-57 OR APPROVED EQUAL, CLASS II LEAKAGE, U.L. 5555 LISTED ELECTRIC ACTUATOR, AND 265-F FUSIBLE LINK. J. CONTROL DAMPERS IN OUTSIDE AIR, RETURN AIR DUCTWORK SHALL BE NCA SCD -3V-57 WITH LIMIT STOP SWITCH FOR NORMAL OUTSIDE AIR INTAKE PURPOSES. K. LOUVERS SHALL BE EXTRUDED ALUMINUM, WITH BIRDSCREEN RUSKIN MODEL ELF6375DXD OR EQUAL. L. REFRIGERANT PIPING SHALL BE TYPE "L" COPPER SIZED AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS SHOWING ALL INSTALLATION DETAILS, SUCTION LINES SHALL BE INSULATED WITH 1/2" ARMAFLEX, SUCTION LINES IN EXPOSED AREAS SHALL BE INSULATED WITH ARMAFLEX SUITABLE FOR OUTDOORS INSTALLATION AND SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS. FAN SCHEDULE UNIT NUMBER AC -1 AC -2 AC -3 AC -4 AC -5 AC -6 AC -6A AC -7 AC -7A AC -8 AHU-3 MANUFACTURER FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. FIRST CO. U MODEL 18SPU-4 18SPU-5 18SPU-6 18SPU-8 24SPU-4 24SPU-5 24SPU-5 24SPU-6 24SPU-6 24SPU-8 Q TOTAL CFM SPEED 0.3 S.P. 635/HIGH 635/HIGH 2000 700 CFM 800 ~ 0 A C.F.M. 0 200 300 100 I- 100 100 635/HIGH 635/HIGH 700/LOW 700/LOW 890/HIGH 760/MEDIUM 890/HIGH 890/HIGH SENSIBLE COOLING CAPACITY MBTUH COOLING CAP SENS TOTAL - BTUH 14170/18900 14170/18900 14170/18900 14170/18900 17850/23800 17850/23800 17850/23800 17850/23800 17850/23800 17850/23800 41.3 UNIT F.L.A. COOLING HEATING 10.6/16.2 10.6/19.9 10.6/23.9 10.6/30.9 14.4/17.3 14.4/21.4 14.4/21.4 14.4/24.4 14.4/24.4 14.4/31.4 17000 FUSE SIZE - AMPS 25 MCP 25 MCP 30 MCP 40 MCP 25 MCP 30 MCP 30 MCP 35 MCP 35 MCP = BLOWER MOTOR H.P. 1/6 1/4 1/2 1/8 ® 240 V 1/2 1/8 ® 240 V 1/6 C UNIT CIRCUIT AMPACITY AMPS 125.0 MCA 45 MCP 53.0 MCA VOLTAGE 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 Ld ENERGY EFFICIENCY RATIO - E.E.R. 9.6 EER 9.6 EER 9.6 EER 9.6 EER 8.7 EER 8.7 EER 8.7 EER 8.7 EER 8.7 EER 8.7 EER UNIT CU -1 HEATER BTUH KW 10200 4 12800 5 15350 6 CU -3 CU -6 CU -7 - ELECTRIC kW 240/208 - 7/5.3 � 5/3.5 ® 208V 10 KW 5/3.5 0 208V 20500 8 10200 4 12800 5 12800 5 15350 6 15350 6 20500 8 34130 WEIGHT 230 230 230 230 230 230 230 230 230 230 J Q QUANTITY SEE DWGS - - - - - - - - _ _ UNIT NUMBER CU -1 (1.5 TONS) CU -2 CU -3 CU -4 (1.5 TONS) CU -3 CU -6 (1.5 TONS) CU -7 ACCESSORIES: MANUFACTURER RHEEM RHEEM RHEEM Q W ACCESSORIES 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 RAKA-024JA7 NOMINAL TONS 1.5 3.0 5.0 1.5 5.0 1.5 2.0 4. 100% OUTSIDE AIR HOOD No OF COMPRESSORS 1 = 1 1 1 1 1 F= R.L.A. EACH 9.5 16.5 28.9 B1 -TOP - B2 TOP 1 UA-TYP - C2-TYP B-TYP B1-TYP B2-TYP A -TOP C2 -TOP C1-TYP B -TOP C-TYP - C1 -TOP C -TOP - D -TOP (n W SERVING UNIT MODEL E-TYP - E -TOP 95.0 175 50 175 50 61 z C-3 - D-TYP D1-TYP - D1 -TOP _ 1 1 1 1 N F.L.A. EACH 0.9 1.3 2.0 0.9 2.0 0.9 0.9 i? VOLTAGE 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 Z I- ACCESSORIES/NOTES 60 25 60 25 25 1 1. (RS) = REAR MOUNT WALL SLEEVE (43-3/4" X 21-3/8" X 25). SEE DWGS. O UNIT WEIGHT 135 180 250 135 250 135 [if 2. (SS) = SIDE MOUNT WALL SLEEVE (43-3/4" X 21-3/8" X 31). SEE DWGS. SYSTEM E.E.R. S.E.E.R. 10.0 10.0 3. EXTERIOR WALL ARCHITECTURAL LOUVER (44" X 22"). 10.0 10.0 10.0 10.0 LIQUID LINE IN 1/4" - 5/16" * 5/16" 3/8" - 1/2" * 1/4" - 5/16" * 3/8" - 1/2" * 4. HEAT/COOL WALL THERMOSTAT. (SEE ENERGY CARD) 1/4" * SUCTION LINE IN 5/8" - 7/8" * 7/8" Q 5/8" - 7/8" * 1/8" - 1 3/8" 5/8" - 7/8" * 3/4" * PROGRAMMABLE THERMOSTAT ON TOP MODEL UNITS A, B. B2, C. C2, E. EXERCISE BILLIARD ROOM CLUB ROOM INTERNET CAFE LOBBY 5. RETURN AIR PANELS IF INDICATED IN PLANS CONF/BUSINESS R ACCESSORIES: * MCP= MAXIMUM CIRCUIT PROTECTION NON-COMBUSTIBLE FLOOR STANDS FOR ALL AHU'S 2- SINGLE STAGE HEAT/COOL THERMOSTAT FAN SCHEDULE SPLIT SYSTEM SCHEDULE PAC -1-2-3 PAC -4 2 RTU -1 2 H.P. MANUFACTURER UNIT NUMBER AHU-1 1.5 TONS AHU-2 AHU-3 FCU -4 1.5 TONS AHU-5 FCU -6 1.5 TONS AHU-7 PCA271 MANUFACTURER RHEEM RHEEM RHEEM FIRST COMPANY RHEEM FIRST COMPANY RHEEM 1500 MODEL NUMBER RBHC-14JOOSNFD RBHC-17J11SNFD RBHC-24J11SNFD 19HX-E RBHC-24J11SNFD 19HX-E RBHC- 1 4J07NFG 92/79 TOTAL C.F.M. 600 CFM 1200 2000 700 CFM 2000 700 CFM 800 ~ 0 A C.F.M. 0 200 300 100 250 100 100 P NOMINAL TONS - - - 1.5 TONS 2.0 TONS U SENSIBLE COOLING CAPACITY MBTUH ENT. AIR TEMP •F 80/67 80/67 80/67 75/63 80/67 75/63 80/67 c� SENSIBLE COOLING CAP. MBH 13100 25.0 41.3 13300 41.3 13300 17.0 1.0 TOTAL COOLING CAP. MBH 17900 34.4 57.5 17000 57.5 17000 23.4 z EXT. STATIC PRESS. IN. H2O 0.4 0.5 0.5 0.15 0.5 0.15 0.4 = BLOWER MOTOR H.P. 1/6 1/4 1/2 1/8 ® 240 V 1/2 1/8 ® 240 V 1/6 C UNIT CIRCUIT AMPACITY AMPS 125.0 MCA 77.0 MCA 53.0 MCA 14 MCA 19 MCA H MAXIMUM FUSE SIZE AMPS VOLTAGE 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 Q UNIT WEIGHT LBS. 90 100 125 90 125 90 80 11.0 EER MATCHING CONDENSING UNIT CU -1 CU -2 CU -3 CU -4 CU -3 CU -6 CU -7 - ELECTRIC kW 240/208 - 7/5.3 10 KW 5/3.5 ® 208V 10 KW 5/3.5 0 208V 5.3 CEILING HEATER BTUH - 18100 34130 17065/12800 34130 17065/12800 14730 STAGE 1 1 1 1 1 1 1 SEE DWG SEE DWG SEE DWG SEE DWG VOLTAGE - 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 SEE BELOW UNIT NUMBER CU -1 (1.5 TONS) CU -2 CU -3 CU -4 (1.5 TONS) CU -3 CU -6 (1.5 TONS) CU -7 ACCESSORIES: MANUFACTURER RHEEM RHEEM RHEEM RHEEM RHEEM RHEEM RHEEM RAILS. (ISO -CURB) MODEL NUMBER RAKA-018JAZ RAKA-037JAZ RAKA-060JAZ RAKA-018JAZ RAKA-060JAZ RAKA-018JAZ RAKA-024JA7 NOMINAL TONS 1.5 3.0 5.0 1.5 5.0 1.5 2.0 4. 100% OUTSIDE AIR HOOD No OF COMPRESSORS 1 1 1 1 1 1 1 F= R.L.A. EACH 9.5 16.5 28.9 9.5 28.9 9.5 12.2 7. PHOTOELECTRIC TYPE SMOKE DETECTOR ON MAIN SUPPLY AIR DUCT. � L.R.A. EACH 50 95.0 175 50 175 50 61 z No. CONDENSER FANS 1 1 1 1 1 1 1 N F.L.A. EACH 0.9 1.3 2.0 0.9 2.0 0.9 0.9 i? VOLTAGE 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 Z MAX. BREAKER SIZE 25 35 60 25 60 25 25 O UNIT WEIGHT 135 180 250 135 250 135 150 v SYSTEM E.E.R. S.E.E.R. 10.0 10.0 10.0 10.0 10.0 10.0 10.0 LIQUID LINE IN 1/4" - 5/16" * 5/16" 3/8" - 1/2" * 1/4" - 5/16" * 3/8" - 1/2" * 1/4" - 5/16" * 1/4" * SUCTION LINE IN 5/8" - 7/8" * 7/8" 1/8" - 1 3/8" 5/8" - 7/8" * 1/8" - 1 3/8" 5/8" - 7/8" * 3/4" * AREA SERVED TRASH ROOM LEASING EXERCISE BILLIARD ROOM CLUB ROOM INTERNET CAFE LOBBY CONF/BUSINESS R ACCESSORIES: 1- NON-COMBUSTIBLE FLOOR STANDS FOR ALL AHU'S 2- SINGLE STAGE HEAT/COOL THERMOSTAT 3- FACTORY MOUNTED CIRCUIT BREAKER IN FRONT OF ALL AIR HANDLING UNITS. 4- CLEAR WEATHER PROOF I.D. ON ALL CU'S INDICATING WHICH UNIT SERVES. 5- * SIZE REF. LINES AS PER MANUFACTURER'S RECOMMENDATIONS, INSULATE SUCTION LINES WITH 3/4" SLIP ON ARMAFLEX APPROVED FOR OUTDOOR USE. 6- PROVIDE LONG LINES ACCESSORIES SUCH AS HARD SHUT OFF TXV, CRANKCASE HEATER ETC, WHEN RECOMMENDED BY MANUFACTURER. 7- ENGINEERED GALVANIZED STEEL OR ALUMINUM CU -STAND W/DARE COUNTY PRODUCT APPROVAL. FAN SCHEDULE UNIT NUMBER PAC -1-2-3 PAC -4 PAC -5 RTU -1 RTU -2 H.P. MANUFACTURER ADDISON ADDISON ADDISON RHEEM RHEEM R MODEL NUMBER PCA271 PCA201 PCA141 RSKA-018JK RSKA-024JK 0 0 TOTAL C.F.M. OA C.F.M. 3000 2500 1500 600/75 OA 800/100 OA F OUTSIDE DESIGN TEMP DB WB(OF) 92/79 92/79 92/79 92/79 92/79 T INSIDE DESIGN TEMP. DB WB °F - - 120-1-60 DIRECT 2.5 0 ENTERING AIR TEMP. DB WB(OF) 92/79 92/79 92/79 92/79 92/79 P NOMINAL TONS - - - 1.5 TONS 2.0 TONS U SENSIBLE COOLING CAPACITY MBTUH 120.8 92.3 56.9 12000 16700 N TOTAL COOLING CAPACITY MBTUH 255.9 192.2 119.5 17000 24000 1 EXTERNAL STATIC PRESSURE IN H2O 1.0 1.0 1.0 0.4 0.4 T EVAPORATOR FAN HP F.L.A. 1 4.6 3.6 2.8 1/4 1.3 1/4 1.3 CONDENSER FAN HP F.L.A. 2 1.0 6.2 2 1.0/6.2 1.0 6.2 1/15 0.5 1/15 0.5 S COMPRESSOR F.L.A. 86.0 48.2 34.6 9.6 13.5 C UNIT CIRCUIT AMPACITY AMPS 125.0 MCA 77.0 MCA 53.0 MCA 14 MCA 19 MCA H MAXIMUM FUSE SIZE AMPS 200 110 80 20 25 E VOLTAGE 208-3-60 208-3-60 208-3-60 208-1-60 208-1-60 U ENERGY EFFICIENCY RATIO 9.6 EER 11.0 EER 9.98 EER 10.0 SEER 10.0 SEER L HEATER kW BTUH 20/68.2 15/51.2 20/34.1 - - E HEATER STAGES kW PER STAGE 2/10 1/15 1/10 - - CEILING FILTERS 2" T A 2" T A 2" T A 120-1-60 DIRECT 3.3 OPERATING WEIGHT 1870 1870 1120 325 330 CEILING FAN QUANTITY SEE DWG SEE DWG SEE DWG SEE DWG SEE DWG ACCESSORIES SEE BELOW SEE BELOW SEE BELOW SEE BELOW SEE BELOW 2. WALL COLLAR 4. FACTORY ROOF CURB 7. WEATHER HOOD AREA SERVED PA SHAFTS PA SHAFTS PA SHAFTS SEE DWGS. SEE DWGS. ACCESSORIES: 1. FACTORY ROOF CURB W/ VIBRATION ISOLATION RAILS. (ISO -CURB) 2. 6 ROW EVAP COIL 3. HOT GAS BY-PASS AND HOT GAS REHEAT 4. 100% OUTSIDE AIR HOOD 5. PHENOLIC COATING ON EVAP COIL AND CONDENSER COIL 6. ALL CONTROLS REQUIRED FOR PROPER OPERATION 7. PHOTOELECTRIC TYPE SMOKE DETECTOR ON MAIN SUPPLY AIR DUCT. 8. OUTSIDE AIR FILTER RACK W/ 2" 30% FILTERS. 9. HORIZONTAL BLOWER DISCHARGE. 10. SINGLE POINT POWER CONNECTION. 11. SEACOAST CORROSION PROTECTION PACKAGE FAN SCHEDULE FAN NO. MANUFACTURER MODEL # FAN TYPE FLEXIBLE DUCT, CLASS I, R=4.2 © H.P. R.P.M. VOLTS DRIVE SONES LOCATION SERVICE ACCESSORIES EF -1 BROAN 671 CEILING FAN 70 - - - 120-1-60 DIRECT 3 DRAWINGS SEE TOILET EXH. 1 EF -2 BROAN 684 CENT/ 80 - - - 120-1-60 DIRECT 2.5 SEE TOILET EXH. 1 CD CEILING DIFFUSER CFM CEILING FAN CG CEILING GRILLE CU CONDENSING UNIT EF EXHAUST FAN EG DRAWINGS FD FIRE DAMPER EF -3 GREENHECK SQ -80D INLINE 350 0.25 1/12 1550 120-1-60 DIRECT 7.4 1ST FLOOR PUMP ROOM r0 V I 1 ST FLOOR EF -4 GREENHECK G -065-D VERTICAL 230 0.125 1/30 1550 120-1-60 DIRECT 4.6 AT ROOF COMMERCIAL 1-4-6 EF -5 N DT LIST D EF -6 GREENHECK SE1-12-432-B6 SIDEWALL 500 0.25 1/6 1160 120-1-60 DIRECT 5.1 MAIN ELEC RM EXH. 6,7 EF -7 GREENHECK SP -9 CEILING 150 0.2 204 W 1050 120-1-60 DIRECT 3.3 SEE TOILET EXH. 1 CEILING FAN DRAWINGS ACCESSORIES: 3. OSHA MOTOR & FAN 5. SPEED CONTROLLER 1. BACKDRAFT DAMPER GUARDS 6. BIRDSCREEN 2. WALL COLLAR 4. FACTORY ROOF CURB 7. WEATHER HOOD AIR DISTRIBUTION SCHEDULE LEGEND DESCRIPTION RIGID DUCTWORK, R=4.2 MODEL NUMBER FLEXIBLE DUCT, CLASS I, R=4.2 © CEILING GRILLE W/ O.B.D. CEILING GRILLE THROW PATTERN AS SHOWN ON DRAWING. 30OF SERIES ALUMINUM SIDEWALL REGISTER W/ O.B.D. I� u THROW PATTERN AS SHOWN ON DRAWING. ® CEILING DIFFUSER W/ O.B.D. WITH O.B.D. THROW PATTERN AS SHOWN ON DRAWINGS. © EXHAUST REGISTER/GRILLE 350F RETURN AIR REGISTER/GRILLE - O.A.L. INTAKE OR EXHAUST LOUVER U A FIRE DAMPER W/ ACCESS DOOR - - COMBINATION FIRE/SMOKE DAMPER E.A.L. W/ ACCESS DOOR O HEAT/COOL THERMOSTAT SD SMOKE DETECTOR - - - - REFRIGERANT PIPING TITUS SEE SPLIT SYSTEM SCHEDULE FOR SIZES AHU AIR HANDLING UNIT CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CU CONDENSING UNIT EF EXHAUST FAN EG EXHAUST GRILLE FD FIRE DAMPER FSD FIRE SMOKE DAMPER (MCD) MOTORIZED CONTROL DAMPER (MVD) O.A. MANUAL VOLUME DAMPER RAG RETURN AIR GRILLE SR SIDEWALL REGISTER SD SMOKE DETECTOR AIR DISTRIBUTION SCHEDULE SYMBOL DESCRIPTION MANUFACTURER MODEL NUMBER MATERIAL REMARKS CG CEILING GRILLE TITUS 30OF SERIES ALUMINUM W/ O.B.D. SR SIDEWALL TITUS 300E SERIES ALUMINUM WITH O.B.D. RAG RETURN AIR GRILLE TITUS 350F ALUMINUM - O.A.L. 0/A INTAKE LOUVER RUSKIN ELF6375DXD ALUMINUM W/ D.C.PRODUCT APPROVAL E.A.L. EXHAUST AIR LOUVER RUSKIN ELF6375DXD ALUMINUM NI D.C. PRODUCT APPROVAL CD CEILING DIFFUSER TITUS TDCA-AA ALUMINUM W/ O.B.D. GENERAL AND HVAC CONTRACTOR TO COORDINATE FINISH AND COLOR OF ALL AIR DISTRIBUTION PRODUCTS PRIOR TO ORDERING. PROJECT HVAC DESIGN REQUIREMENTS DUCT SMOKE DETECTOR YES NO FIRE DAMPER(S) ISSUE FOR PERMIT SMOKE DAMPERS QBLDG. 2 07-29-02 FIRE RATED ENCLOSURE 07-29-02 FIRE RATED ROOF/ CEILING ASSEMBLY 2 BLDG. DEPT. CORD. FIRE STOPPING SMOKE CONTROL HVAC SYSTEM REQUIREMENTS AS PER S.F.B.C. 4901.4(C) ALBERT SHUB PE# 0043414 M.E. FLORIDA EB0003862 •' •. FLORIDA ENGINEERING SERVICES �, •A i; MECHANICAL AND ELECTRICAL ENGINEERS 34 N.W. 168TH STREET NORTH MIAMI BEACH, FL. 33169 TELEPHONE: (305) 653-0212 FAX: (305) 653-0232 REVISIONS BY 02-28-02 ISSUE FOR PERMIT DEPT. COORD QBLDG. 2 07-29-02 07-29-02 2 BLDG. DEPT. CORD. ,108-12-02 V z LI z1 L3 n nQ L� 0-1-- QLL.- Q W- c == 0>=�`> LL-W_QQ - -0 - Ct ,> Q �^ _ J Q W p r0 V I b:-,► CHECKED DATE 02-28-02 SCALE JOB NO. 02013 SHEET Y AC -17 OF SHEETS