12-1372-086
ELECTRICAL LOAD CALCULATION A.- GENERAL LIGHTING LOAD 3,348 S.F.'', m 3W/SF = 10,044 WATTS B.- (2) SMALL APLIANCE CIRCUITS X 1,500 = 3,000 WATTS C.- FIXED APPLIANCES: RANGE ---------------- 12,000 REFRIGERATOR------------ 1,000 DISHWASHER --------------- 800 WASHER ------------------- 1,500 DRYER -------------------- 5,000 INSTANT W/H----------- 12,000 DOOR OPENER'S ----------- 800 HOOD --------------------- 600 MICROWAVE ----------------600 JACUZZI ------------------- 1,500 CONNECTED LOAD LESS A/C = 48,844 WATTS 10,000 W a 100 90 = 10,000 WATTS REST Ws 40 51. = 15,538 WATTS (A/C (OR HEATING) 6 100 9. = 20000 WATTS DEMAND, LOAD = 45,538 / 240 WATTS = 189.14 AMPS m 240/120 V. SERVICE SIzE = 200 AMPS. C.- NEUTRAL LOAD LIGHTING, SMALL APPLIANCE 4 WASHER 14,544 WATTS F I RST 3,000 W 100 9- = 3,000 WATTS REST W m 35 io = 4,040 WATTS RANGE X -10 qo = 5,600 WATTS DRYER X -10 qo = 3,500 WATTS REFRIGERATOR = 1,000 WATTS DISHWASHER = 1,000 WATTS TOTAL NEUTRAL WATTS = 18,140 WATTS = 7558 AMPS. ELECTRICAL NOTES 1. CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT FOR COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS. 2. COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE 3. PROVIDE', EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM. 4. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTACT. 5. PROVIDETEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER TRADES. 6. NO APPI 'IANCES OUTLES SHALL BE INSTALLED BELOW BASE FLOOD ELEV. 7. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING ARCHITECTURAL FEATURES. 8. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING: CONDITION5. (B. A/C COMPRESSOR SHALL BE INSTALLED ABOVE BASE FLOOD ELEV. 10. OUTDOOR CONDUITS SHALL 13E SCHEDULE 40 PVC. MINIMUM COVER SHALL BE 24'. 11. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR. 12. ELECTRICAL OUTLETS BELOW BASE ELEV. SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEV AND SHALL BE INSTALLED (S3=PARATE) AS INDEPENPANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 13. MAIN CIRCUIT BW PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV. 14. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT METER TO COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 15. ALL OUTLETS AND SWITCHES WILL BE DECORA TYPE 16. ELECTRICAL CONTRACTOR TO CLEAN UP TO MAINTAIN .1013 SITE CLEAN REGARLESS HIS JOB, ELECTRICAL NOTES. 1) ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE ELEVATION SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEVATION AND SHALL BE INSTALLED (SEPARATE) AS INDEPENDANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 2) NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED BELLOW SASE FLOOD ELEVATION. 3) A/C COMPRESSORS SHALL BE INSTALLED ABO` F BASE FLOOD ELEVATION. 4) MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEVATION. 5) IT REQUIRED THAT YOU CONFER WITH FLORIDA POWER 4 LIGHT TO LOCATED THE ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 2 in. MIN. SMOKE DETECTOR NOTE: 1) SMOKE DETECTOR SYSTEM TO BE INSTALLED IN ACCORDANCE W/NFP4 72/99 2) SMOKE DETECTOR SHALL BE NOT BE CLOSER THAN 3' FROM AIR REGISTER 4, BATH DOOR AND 20' FROM COOKING APPLIANCES GROUNDING ELECTRODE CONDUCTOR BOLTED -TYPE 0 CONNECTION DEVICE 0 OR EXOTHERMIC WELD. 0 GROUNDING 0 NONMETALLIC ELECTRODE PROTECTIVE SLEEVE. • CONCRETE FOUNDATION No. 4 AWG OR LARGER BAF - ` • ' '' • • COPPER CONDUCTOR OR S f • REINFORCING BAR OR ROD 4LESS THAN 1/2 -[NCH D IAMETI 20 FT MIN. DIRECT CONT WITH EARTH. SERVICE BY - POWER COMP. ELECTRICAL TYPI= SERVICE VOLTAGE MOUNTING SQUARE 'D' or APPROVED EQUAL RESIDENCE 240/120 V I m - 3W., SUSPACE F,4N E L NEMA 3R MAIN SUS NEUTRAL MAINS AIC 200 AMPS 200 AMPS 200 AMPS 10,000 AMPS M � TOTAL COND AMPS POLE WIRE REMARKS CKT. CKT. REMARKS WIRE CON TOTAL OLES AMPS :z V.A. SIZE+ 0 NO. NO. SIZE+ vfi. 60 2 10000 1' 6 A/C: AHU-1 f 1 2 U" 2 10 3/4' 5,000 2 30 �0 3 4 O mo=o CL 30 2 5000 3/4' 10 DRYI=R 5 6 CU " 1 10 3/4' r✓ -,000 2 30 () 1 a .E W a!f 50 2 12000 I' 6 RANGE9 10 REFRIGERATOR 12 1/2' 1000 1 20 Z3 11 12 A/C AHU. " 2 6 1' 10000 2 60 20 1 1500 1/2' 12 WASHER 13 14 U LLJ � J (D 20 1 1500 1/2' 12 SMALL APDL, 15 16A GFI RECP. OUTSIDE 12 1/2' 1 600 1 20 W �— 168 GFI RECP. OUTSIDE 12 1/2' 600 1 20 20 1 1500 1/2' 12 SMALL ADPL. 11 18 DISHWASHER 12 1/2' 800 1 20 SPACE 19 20 HOOD 12 1/2' 600 1 20 SPACE 21 22 MICROWAVE 12 1/2' 600 1 20 20 1 800 1/2' 12 DOOR'S OPENER 23 24 JACUZZI 12 1/2' 1500 1 20 20 1 600 1/2' 12 GFI RECP. BATH 25 26 GFI RECD. BATH 12 1/2' 600 1 20 60 2 12,000 I' 6 INSTANT W/H 21 28 LT5 4 REC. 14 1/2' 600 1 15 29 30 15 1 600 1/2' 14 LTS 4 REC. 31 32 33 34 35 36 31 38 39 40 SPACE 41 42 SPACE DEMAND LOAD: 45058 WATTS/240 s 191.01 AMPS FEEDER = 3 "3/0 THLIN - 2' COND. FED FROM SERVICE. 1. CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT FOR COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS. 2. COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE 3. PROVIDE', EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM. 4. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTACT. 5. PROVIDETEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER TRADES. 6. NO APPI 'IANCES OUTLES SHALL BE INSTALLED BELOW BASE FLOOD ELEV. 7. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING ARCHITECTURAL FEATURES. 8. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING: CONDITION5. (B. A/C COMPRESSOR SHALL BE INSTALLED ABOVE BASE FLOOD ELEV. 10. OUTDOOR CONDUITS SHALL 13E SCHEDULE 40 PVC. MINIMUM COVER SHALL BE 24'. 11. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR. 12. ELECTRICAL OUTLETS BELOW BASE ELEV. SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEV AND SHALL BE INSTALLED (S3=PARATE) AS INDEPENPANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 13. MAIN CIRCUIT BW PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV. 14. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT METER TO COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 15. ALL OUTLETS AND SWITCHES WILL BE DECORA TYPE 16. ELECTRICAL CONTRACTOR TO CLEAN UP TO MAINTAIN .1013 SITE CLEAN REGARLESS HIS JOB, ELECTRICAL NOTES. 1) ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE ELEVATION SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEVATION AND SHALL BE INSTALLED (SEPARATE) AS INDEPENDANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 2) NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED BELLOW SASE FLOOD ELEVATION. 3) A/C COMPRESSORS SHALL BE INSTALLED ABO` F BASE FLOOD ELEVATION. 4) MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEVATION. 5) IT REQUIRED THAT YOU CONFER WITH FLORIDA POWER 4 LIGHT TO LOCATED THE ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 2 in. MIN. SMOKE DETECTOR NOTE: 1) SMOKE DETECTOR SYSTEM TO BE INSTALLED IN ACCORDANCE W/NFP4 72/99 2) SMOKE DETECTOR SHALL BE NOT BE CLOSER THAN 3' FROM AIR REGISTER 4, BATH DOOR AND 20' FROM COOKING APPLIANCES GROUNDING ELECTRODE CONDUCTOR BOLTED -TYPE 0 CONNECTION DEVICE 0 OR EXOTHERMIC WELD. 0 GROUNDING 0 NONMETALLIC ELECTRODE PROTECTIVE SLEEVE. • CONCRETE FOUNDATION No. 4 AWG OR LARGER BAF - ` • ' '' • • COPPER CONDUCTOR OR S f • REINFORCING BAR OR ROD 4LESS THAN 1/2 -[NCH D IAMETI 20 FT MIN. DIRECT CONT WITH EARTH. SERVICE BY - POWER COMP. ELECTRICAL 0 200 AMP ELECT PANEL ��— 3* 3/0 THWN IN 2' COND GROUND - 1 # 4 CU (GRD PER NEC.) PROVIDE TWO 5/8'X10' COPPER CLAD GROUNDING ROD TO A 3/4" COPPER WATER PIPE STUB -OUT ELECTRICAL RISER DIAGRAM ELECT. LEGEND Switch 15 A 125 V (Q-- Duplex Receptacle 15 A 125 V (n-- Duplex Receptacle 15 A 125 V Switched 0 Incandescent Lighting Fixture I-0 Wall Sra cket Light Q) Junction Sox PH D Phone Outlet -❑ TV T.V. Outlet 0 Electrical Panel q:1 Disconnecting Switch SD Smoke Detector Electrical Meter © Future Fan Fan Outlet CONNECT TO A CONCRETE -ENCASED ELECTRODE CONSISTING OF AT LEAST 20 FT OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 1/2 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. ENCASED GROUNDING ELECTRODE DETAIL. nt8 LOT 3 3* 3/0 THWN IN 2' COND CL Z3 200 A. DISC. BRK. NEMA 3R 0 200 AMP ELECT PANEL ��— 3* 3/0 THWN IN 2' COND GROUND - 1 # 4 CU (GRD PER NEC.) PROVIDE TWO 5/8'X10' COPPER CLAD GROUNDING ROD TO A 3/4" COPPER WATER PIPE STUB -OUT ELECTRICAL RISER DIAGRAM ELECT. LEGEND Switch 15 A 125 V (Q-- Duplex Receptacle 15 A 125 V (n-- Duplex Receptacle 15 A 125 V Switched 0 Incandescent Lighting Fixture I-0 Wall Sra cket Light Q) Junction Sox PH D Phone Outlet -❑ TV T.V. Outlet 0 Electrical Panel q:1 Disconnecting Switch SD Smoke Detector Electrical Meter © Future Fan Fan Outlet CONNECT TO A CONCRETE -ENCASED ELECTRODE CONSISTING OF AT LEAST 20 FT OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 1/2 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. ENCASED GROUNDING ELECTRODE DETAIL. nt8 LOT 3 2- a- 4,- S- 6. - DATE =SEPTEMBER, 2012 SCALD SHOUN DRAWN: M. GA5TELLON DffiC3N BY' JR JOB Na E-2 CL Z3 0 M � , � M (� :z 0 N U- 0 0 U �0 } E O mo=o CL d" O U �- LL -z co () =) EL .E 2- a- 4,- S- 6. - DATE =SEPTEMBER, 2012 SCALD SHOUN DRAWN: M. GA5TELLON DffiC3N BY' JR JOB Na E-2 CL Z3 0 C.� 0 0 0 U E CL d" O U �- LL -z co () =) EL .E W a!f Q (D ccs LLJ W Z3 0 to J O J � Q O U 0 U LLJ � J (D & o O Z �"'� 0 Cj) Co W �— z C0 2- a- 4,- S- 6. - DATE =SEPTEMBER, 2012 SCALD SHOUN DRAWN: M. GA5TELLON DffiC3N BY' JR JOB Na E-2