07-420-039GENERAL STRUCTURAL -NOTES 1. THE GENERAL STRUCTURAL NOTES ARE INTENDED TO AUGMENT THE DRAWINGS AiD SPECIFICATIONS. SHOULD CONFLICTS EXIST BETWEEN THE DRAWINGS AND SPECIFICATIONS AND THE GENERAL STRUCTURAL NOTES, THE STRICTEST PROVISION SHALL GOVERN. 2. GOVERNING CODE: FLORIDA BUILDING CODE 2004 EDITION 3. SEE STRUCTURAL PLANS FOR DESIGN SOIL BEARING PRESSURE AND LIVE LOADS. LIVE - LOADS REDUCED IN ACCORDANCE NITH THE GOVERNING CODE. 4. ROOF SNOW LOAD: GROUND SNON LOAD (Pg) - 0 PSF I - B -IC WLNO SP D 14- MPH PORT NCE FACTOR (Iv4 - = 1. EXPOSURE CATEGORY - =XF05URE C - INTERNAL PRESSURE COEFFICIENT (G Cpi) _0.1 KIT -N DESIGN PRESSURE TABLE E _OMPONNTS A -= - - L BV2xBx1/4 - -_- - 511 - ��>f Roof - 5urfae.e: Area_ Roof Zone I Roof Zane 2 Roof Zane 3 Wall Zone 4 - Wall Zone 5 Ove:rhan_ Overhan (e . ft.) Po5itlve Ne ative. Positive Ne_ ative _- Positive Ne- ative Food ive Ne_ ative Po=sitive, N_e- ative Z<mc 14.2 Zone 3 I . 26.2 -106,0 26.2 1 62.6 53.9 =63.8 58.9 -78.G -92.3 -152.5 14 -G4,4 26.2 - I tibio 26,2 162.E 58.9 -�8.8 58.9 7f . -92.8 -152.8 24 SUPPORTS - -63.3 26.2 -07.1 2+x.2 1 35.8 56.5 =GO.4 56.5 -73.7 -01 ,7 -12#x,1 54 r29 I,1 26.2 =84.8 2&2 -57.1 52.5 -58.x} 52.5 -66.3 -882 -7G.4 (2) 5005162-84 -58. 25.I -?' 69 1244 25.1 X9.8 50,1 -55.5 50,1 -61 .AI = GA CLIP -58.9 22.4 -69,3 22.4 -69.8 48.1 -53,4 48.1 =56.5 -76.4 --13.7 544 217.7 -58.9 24.7 49.8 20.7 -G0.6 44.2 40.1 44.2_ -49.1 -G0.0 �I3.7 1444 24.7 -58.9 24.7 -69.8 24.7 -69.8 44.2 -49.1 44.2 ±-49.1 -C-0.0 -43.7 43 26.2 61.3 24.2 -81.9 26,2_ -99,7 52.8' -58,6 52,8 3 84,1 -79.3 . A COMPONENTS AND CLADDING TABU NOTES.- A. ALL PRESSURES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). B. REFER TO ASCE 1-02 FIGURES 6-11 FOR DEFINITION OF PRESSURE ZONES AND SIGN CONVENTION. -VOR THESE FIGURES, USE 0 - T'-G,I C. LINEAR INTERPOLATION BETWEEN ADJACENT VALUES IS PERMITTED FOR VALUES OF SURFACE AREA OTHER THAN THOSE SHOWN. INTERPOLATION SHALL ONLY BE PERFORMED'BETNEEN PRESSURE VALUES OF THE SAME SIGN. D. WIND PRESSURES INDICATED SHALL ONLY BE USED IN THE LOAD COMBINATIONS SET FORTH IN THE 2004 FLORIDA BUILDING CODE SECTION 1605. FOR LOAD COMBINATIONS IN SECTION 1605.5.Z USE OMEGA = 1.5. . SEISMIC LOAD: SEISMIC USE GROUP - CATEGORY II IMPORTANCE FACTOR - - 1 O MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD (55) - 0.062 MAPPED SPECTRAL RESPONSE ACCELERATION AT ONE -SECOND PERIOD(51)- 0.025 SITE CLASS D SPECTRAL RESPONSE COEFFICIENT AT SHORT PERIOD (SDS) _ 0.06.,E SPECTRAL RESPONSE COEFFICIENT AT ONE -SECOND PERIOD (SDI) 0.051 SEISMIC DESIGN CATEGORY A DESIGN BASE SHEAR 4 KIPS 5E I SM I C RESPONSE COEFFICIENT (Cs) _ 0.017 DESIGN BY EQUIVALENT LATERAL- FORCE PROCEDURE. J. MECHANICAL FRAMING LOADS, OPENINGS, AND STRUCTURE IN ANY WAY RELATED TO MECHANICAL REQUIREMENTS ARE SHOWN FOR BIDDING PURPOSES ONLY, CONTRACTOR SHALL OBTAIN APPROVAL OF MECHANICAL AND OTHER TRADES BEFORE PROCEEDING NITH SUCH PORTION OF THE WORK, EXCESS COST RELATED TO VARIATION IN MECHANICAL REQUIREMENTS TO BE BORNE BY MECHANICAL CONTRACTOR, COORDINATE SIZE AND LOCATION OF ALL OPENINGS NITH THE MECHANICAL DRAWINGS. S. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE _BUILDING IS FULLY COMPLETED, IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND SEQUENCE AND TO INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION. THIS INCLUDES THE ADDITION OF WHATEVER TEMPORARY BRACING, GUYS, OR TIE=DOWNS NHICH MIGHT BE NECESSARY. SUCH MATERIAL SHALL- REMAIN THE CONTRACTOR'S PROPERTY AFTER COMPLETION OF THE PROJECT. q. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOL-LON ALL APPLICABLE SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION. 10,THE CONTRACTOR 15 RESPONSIBLE FOR VERIFYING ALL DIMENSIONS AND CONDITIONS RELATING TO EXISTING CONSTRUCTION AND EXISTING SERVICE ON THE SITE. 11.THE CONTRACTOR SHALL _VERIFY ALL DIMENSIONS AND LOCATIONS OF COLUMNS, N-ALLS, OPENINGS ETC. NITH THE ARCHITECTURAL PRANIN65 PRIOR TO PROCEEDIN& KITH THE WORK. LIGHTGAGE METAL FRAMIN& 1, SPECIFICATIONS AND STANDARDS: A. ALL STRUCTURAL PROPERTIES OF LIGHTGAGE METAL FRAMING SHALL BE COMPUTED IN ACCORDANCE NITH AISI SPECIFICATIONS FOR THE DESIGN OF COLD 1=0RMED STEEL STRUCTURAL MEMBERS" AND SHALL BE PUBLISHED IN THE MANUFACTURERS CATALOG. B. WELDING SHALL BE PERFORMED ONLY BY QUALIFIED OPERATORS USING PROPER EQUIPMENT FOR THE PARTICULAR TYPE OF WORK REQUIRED. C. ANS STANDARD NELDING SYMBOL. D. ANS D1.5 SPECIFICATION FOR WELDING SHEET STEEL IN STRUCTURES. 2. MATERIALS.- A. ATERIALS:A. STRUCTURAL FRAMING MEMBERS 54 MILS AND HEAVIER. ASTM A1005, GRADE 50, TYPE H. B. STRUCTURAL FRAMING MEMBERS 45 MILS AND LIGHTER: ASTM A1005, GRADE SS, TYPE H. _ _ C. ALL TRACK AND BRIDGING MATERIALS, ASTM A1OOS, GRADE SS, TYPE H. P. ALL MEMBERS SHALL BE GALVANIZED PER ASTM A655, GGO. E, WELDING ELECTRODES: ANS A5.1, AS.S OR A5.15 SERIES E&O. B. CONNECTIONS= A. CUT ALL FRAMING COMPONENTS TO FIT SQUARELY AGAINST ABUTTING MEMBERS AND HOLD FIRMLY IN POSITION UNTIL PROPERLY FASTENED. B. ALL PANELS SHALL BE SQUARE AND BRACED AGAINST RACKING. - C. WIRE TYING OF STRUCTURAL FRAMING COMPONENTS.IS NOT PERMITTED. D. -L-IGHTGAGE METAL,FRAMING CONNECTIONS TO BE FASTENED TOGETHER WITH A MINIMUM OF () #a SCREWS OR AS SHOWN ON THE PLANS. 4. ERECTION: A. ATTACH TRACK SECURELY TO THE FLOOR AND OVERHEAD STRUCTURE. -- B. SEAT STUDS SQUARELY TO THE FLOOR AND OVERHEAD TRACK AND ATTACH SECURELY. C. SPLICES IN STRUCTURAL FRAMING MEMBERS ARE NOT PERMITTED WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER. D. DO NOT ALLOW AXIAL LOADS TO STUDS UNTIL ALL BRIDGING, CONNECTIONS, AND ATTACHMENT OF COLLATERAL MATERIALS ARE COMPLETE. E. ATTACH V -BAR BRIDGING TO BOTH FLANGES OF NALL STUBS TO PREVENT STUD ROTATION, BRIDGING RONS SHALL BE SPACED AT 4'-O"r1c- OR IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. F. PROVISIONS SHALL BE MADE FOR STRUCTURE VERTICAL MOVEMENT AT PARTITIONS AND CURTAINNALL INFILL AND NHERE IiVICATED USING VERTICAL SLIDE TRACK AND VERTICAL SLIDE CLIPS. PROVIDE'V-BAR BRIDGING TO BOTH FLANGES OF WALL STUDS WITHIN 6" OF THE SLIDE TRACK LOCATIONS. STRUCTURAL STEEL 1. SPECIFICATIONS AND STANDARDS: UNLESS SPECIFICALLY SHOWN OTHERWISE, DESIGN, FABRICATION AND ERECTION SHALL BE GOVERNED BY THE LATEST REVISIONS OF: A. AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, ASD-qth EDITION. B, AISC CODE OF STANDARD PRACTICE. C. ANS STANDARD WELDING SYMBOLS. D. STRUCTURAL WELDING CODE ANS D1.1-2000 OF THE AMERICAN WELDING SOCIETY. WELDING SHALL BE PERFORMED ONLY BY OPERATORS QUALIFIED, BY THE AWS STANDARD QUALIFICATION PROCEDURE, TO PERFORM THE PARTICULAR TYPE OF WORK REQUIRED. E. SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A525 OR A4gO BOLTS, 2. TESTING; _ _ _ A. WELDS: VISUAL TESTING SHALL BE PERFORMED BY AN INDEPENDENT TESTING LABORATORY ON ALL NEL-DS. INADEQUATE WELDS SHALL BE STRENGTHENED OR CUT OUT AND REPLACED AS DIRECTED. B. STRUCTURAL STEEL/ PROVIDE MILL REPORTS FOR PROPERLY IDENTIFIED - MATERIALS ON REQUEST. C. A525 AND A4,=10 BOLTS: PROVIDE BOLT INSPECTION AS DETAILED IN PARAGRAPH q OF SPECIFICATIONS FOR STRUCTURAL JOINTS USING A525 OR A4gO BOLTS. S. MATERIALS. A. ANGLES, PLATES AND BARS= ASTM AS&. B. WELDING ELECTRODES: AWS A5,1 OR AS.S SERIES E70. C. BOLTS; ASTM A525. D. PAINT AND PROTECTION: I. PRIME COAT, 'POUCH UP AFTER ERECTION. 2. MEMBERS EXPOSED TO WEATHER IN FINISHED STRUCTURE: GALVANIZED AFTER FABRICATION. 4. MISCELLANEOUS REQUIREMENTS: A. STEEL SUPPORTING OR CONNECTING TO MECHANICAL OR OTHER EQUIPMENT IS SHOWN FOR BIDDING PURPOSES ONLY, CONTRACTOR SHALL RECONCILE EXACT SIZE AND LOCATION NITH MECHANICAL AND OTHER REQUIREMENTS BEFORE PROCEEDING WITH THE WORK. CONTRACTOR SHALL COORDINATE EXACT SIZE AND LOCATION FOR ALL STEEL ANGLE FRAMES NITH OPENINGS SHOWN ON THE MECHANICAL AND ARCHITECTURAL DRAWINGS. /-N M 3f F,4RTlAL R00� F:RAM'INC� PLAN �4rr _ 11-011 �zr - �1. PIESIGNL-IVB LOADS: R -F SNON LOAD BASED ON 0 PSF GROUND SNOW LOAD, ROO LO P - _I VE LOAD = BF INDICATES -OF STEEL AND MOIST BEARING ELEVATION. S. EXISTING ROOF CONSTRUCTION: 12-x2O GAGE STEEL ROOF DECK.. 4. ALL CONSTRUCTION IS NEN UNLESS NOTED AS EXISTING (E-). S. PROVIDE LSXS 112 X Blit LLV UNDER CURBS OF ROOF TOP HVAC UNITS AS SHONN ON PLAN. CONNECT TO EXISTING JOIST AT EACH END NITH SEAT L&X5 ill X 5l16 X O' -G" LLV SIMILAR TO DETAIL 215100. (0._INDICATES FRAMED OPENING - PROVIDE FRAME USING L's S 112x5 1/2x114 - 4 SIDES. CONTRACTOR COORDINATES SIZES NITH MECHANICAL AND ARCHITECTURAL REOU I REMENTS 4 .FRAMES ARE REQUIRED AT ROOF DRAINS. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS POR NUMBERS AND LOCATIONS. SEE DETAILS 1/510.0 AND 2/5100. -7. INFORMATION FOR.THE EXISTING BUILDING HAS BEEN TAKEN FROM DRAWINGS AND HAS NOT BEEN VERIFIED IN THE FIELD. CONTRACTOR SHALL VERIFY ALL RELEVANT CONDITIONS AND DIMENSIONS OF EXISTING CONSTRUCTION BEFORE PROCEEDING WITH WORK, S. REFERENCES; GENERAL STRUCTURAL NOTES - 5100. T BOT. CHORD SUSPENDED LOAD 500# MAXIMUM TOP CHORD LOAD GOO# MAXIMUM L1 4x1!/4x b MIN. EXT& MOIST, SEE PLAN NOTES: CONCENTRATED MECH, UNIT LOADS, FOLPING PARTITIONS, SUSPENDED LOADS, ETC, SHOULD BE LOCATED AT MOIST PANEL - POINTS WHERE POSSIBLE. NHEN PANEL POINT IS NOT ACCE5IBLE, SUPPORT LOAD AS SHONN ALL MELDING TO MOIST IS TO BE DONE WITH CARE AS NOT TO IMPAIR THE STRENGTH OF THE MOIST. DETAIL NO SCALE: TYP, SUPPORT OFON ENTRATF-1;) LOAI NOT AT J015T PANED POINT NEW RND. E CNTR� ON z ETG. MTL. DECK EXT&. STL. _15T. I I I I (2) #10- TYP 10 TYP SCREWS TYP TYP NOTE: ALIGN WEDS NITH JOIST PANEL POINTS 5EIST I N S 1/411 - 11-0I1 ROOF OPENINGCONNECT RTU TO L wl COORDINATE OPENING (4) 4C'� STRAP wl (4)) #ICI" SCREWS. REQUIREMENTS w1MECH. CONNECT RTU TO CURB CONTRACTOR w1 #14x4" SCREWS @ 4"1. SEE PLAN NOTES_ 1 SEE MECHANICAL DRAWING FOR LOCATIONS, SIZES, AND QUANTITES OF ROOF OPENINGS. 2. ALL WELDING TO MOIST TO SE DONE NITH CARE SO AS NOT TO IMPAIR THE STRENGTH OF THE JOIST. L?E`TA I L NO SCALE: T 1P. I01= OPENIN SEE ARC* - 5625I62-54 @ 16"r-lrs 5/161/2 -L4x5l2x 4 - L BV2xBx1/4 x0'=Ir LLV -REiNF. EXTG. 511 - JOIST AS N4 = I' -O" - RECD. PER SEE PLAN FOR ETG. i/5I00 FOR. JOiST INFO. LOADS NOT -- AT J015T PANEL PTS. SEE PLAN NOTES_ 1 SEE MECHANICAL DRAWING FOR LOCATIONS, SIZES, AND QUANTITES OF ROOF OPENINGS. 2. ALL WELDING TO MOIST TO SE DONE NITH CARE SO AS NOT TO IMPAIR THE STRENGTH OF THE JOIST. L?E`TA I L NO SCALE: T 1P. I01= OPENIN SEE ARC* - 5625I62-54 @ 16"r-lrs E TG FTS, NOTE; EXISTING CANOPY NOT SHOWN FOR C-LL-ARITY. CANOPY STRUCTURE TO REMAIN AS IS. SECTION, V' ETG CMU I I I N4 = I' -O" - -=100 5100 - 00 WA PO 0 X T_ 0 _S, ELL XT& ROOF } STRUCTURE 111­� ri&". EXT PLYWOOD � 0 SHEATHING -_---- - + _. Fe -D VERIFY FIELD wl #10 SCREWS @- - " ellen AT EDGES z (3) AND INTERIOR _ SUPPORTS - - - i BSIG=4 ii2r�rr - 1t- - - - t (2) 5005162-84 L14 HEADER wl 600TI25-65 T$5 = GA CLIP SECT 4A ONLY - , - .ANGLE wl () / x I5/4" EMIL KWIK CON 11 FASTENERS 562562-54 - TO EXTG MU HALL 6 �k I (2) IO 5CREAS w EA 1 l SECT 4A ONLY STUD, TYP 11 I I II I I r 3 HALL EXTENDSCOOT 125 -GS iNi 0.1-17" BELOW OPENING u PAP @ 5" r @ SECT 4 ONLY -/r- - iOOI,Orr}L .. EXTG 14" NIDE r' CMU FND WALL E TG FTS, NOTE; EXISTING CANOPY NOT SHOWN FOR C-LL-ARITY. CANOPY STRUCTURE TO REMAIN AS IS. 7166 Dublin Road Suite 299 Columbus Ghia 43215!1038, (ONSOLTANT: GLAVAN FEHER ARCHITECTS INC. 2 MIRANOVA PLACE COLUMBUS, OHIO 43215 T€ L 6 1 4 2 2 3. 3 4 0 0 P A X 6 1 4. 2 2 3. 3 3 3 7 W W W. G L A V A N, C 0 M EOP YRI€HT 2007 THIS DRAWIN€ IS AN INSTRUMENT OF SERVICE, AND AS SUCH, REMAINS THE PROPERTY OF CHIPOTLE MEXICAN GRILL INC.. PERmisSION FOR USE OF THIS DOCUMENT IS LIMITED AND CAN BE EXTENDED ONLY SY WRITTEN AGREEMENT WITH OHIPOTLE MEXICAN DRILL INC.. 1 543 WAZEE STREET DENVER, UOLORAOD E30202' PHIONE; (303) 595 4000 FAX: (303) 595-4014 INTERNET: WWW.OHIPEITLE.COM SECTION, PO 4A -- N4 = I' -O" - -=100 5100 - 00 PO 0 X T_ 0 _S, LLJ 111­� '- `gJA � 0 LL 0 W 7166 Dublin Road Suite 299 Columbus Ghia 43215!1038, (ONSOLTANT: GLAVAN FEHER ARCHITECTS INC. 2 MIRANOVA PLACE COLUMBUS, OHIO 43215 T€ L 6 1 4 2 2 3. 3 4 0 0 P A X 6 1 4. 2 2 3. 3 3 3 7 W W W. G L A V A N, C 0 M EOP YRI€HT 2007 THIS DRAWIN€ IS AN INSTRUMENT OF SERVICE, AND AS SUCH, REMAINS THE PROPERTY OF CHIPOTLE MEXICAN GRILL INC.. PERmisSION FOR USE OF THIS DOCUMENT IS LIMITED AND CAN BE EXTENDED ONLY SY WRITTEN AGREEMENT WITH OHIPOTLE MEXICAN DRILL INC.. 1 543 WAZEE STREET DENVER, UOLORAOD E30202' PHIONE; (303) 595 4000 FAX: (303) 595-4014 INTERNET: WWW.OHIPEITLE.COM Issue Record; 03.05.2007 FIRE/GERM SUBMITTAL 4 • Revisions; 03.06.2007. ERRS COMMENTS_ -- 04.26.2007 FE&WB COMMENTS - 07.17.2007 BLDG DEPT. COMMENTS.._ Drawn! MNH Checked: M13H Project No. CMC302 Contents; Roof Framing Plan, General foot' Sections I 100 I I bate of La3t,.:Print; , - •L� 07= 7f Q07-'_- -93%3 t PO 00 PO 0 X T_ 0 0 LLJ 111­� F 0 LL 0 W z (3) _ Issue Record; 03.05.2007 FIRE/GERM SUBMITTAL 4 • Revisions; 03.06.2007. ERRS COMMENTS_ -- 04.26.2007 FE&WB COMMENTS - 07.17.2007 BLDG DEPT. COMMENTS.._ Drawn! MNH Checked: M13H Project No. CMC302 Contents; Roof Framing Plan, General foot' Sections I 100 I I bate of La3t,.:Print; , - •L� 07= 7f Q07-'_- -93%3 t