07-1381-003NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
System No.W-L-1001
September 07, 2004
(Formerly System No. 147)
F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3)
T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3)
L Rating At Ambient - less than 1 CFM/sq ft
L Rating At 400 F - less than 1 CFM/sq ft
- NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
System No. C -A3-1001
August 23, 2004
(Formerly System No. 49)
F Rating - 3 Hr
T Rating - 0 Hr
W Rating - Class I (See Item 4)
SEG 11QN A—A
NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
A
System No.W-3-3081
Septmber 08, 2004
F Rating - 2 Hr
T Rating - 1/2 Hr
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Wall Assembly - The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the
materialsand in the manner described in the Individual U300 or U400 Series Wall or Partition Designs In the UL Fre
Resistance Directory and shall include the following construction features:
A Studs - Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel channel studs.
Wood studs to consist of ram 2 by 4 in. lumber spaced 161n. OC with nom 2 by 41n. lumber end plates and cross
braces. Steil studs to be min 3-5/8 in. wide by 1-3/81n. deep channels spaced max 24 in. or—
B.
CB. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 fL wide with square or tapered edges. The gypsum wallboard
type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the Individual U300 or
U400 Series Design In the UL Fire Resistance Directory. Max diam of opening Is 261n,
2. Through Penetrant - One metallic pipe, conduit or tubing Installed either concentrically or eccentrically within the
firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in.
(point contact) to max 2 In. Pipe, conduit or tubing to be rigidly supported on both sides of wag assembly. The
following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 24 In. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 24 In. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 121n dwm (or
smaller) or Class 50 (or heavier) ductile Iron pressure pipe
C. Conduit - Nom 6 in. diam (or smaller) steel conduit or nom 4 in diam (or smaller) steel electrical metallic tubing
D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavies copper tubing
E. Copper Pipe - Nom 6In. diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product- - Flexible Metal Piping - The following types of steel flexible metal gas piping
may be used:
1. Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be
removed on both skies of floor or wag assembly.
OMEGA FLEX INC
2. Nom 1 len, diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be
removed on both skies of floor or wall assembly.
TITEFLEX CORP, A BUNDY CO
3. Nom 1 M. dlam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be
remove) on both sides of floor or wall assembly.
WARD MFG INC
3. FlII,Void or Cavity Material- - Caulk or Sealant - Min 5/8. 1.1/4,1-7/8 and 2-1/2 in, thickness of caulk or
sealant for 1, Z 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wait
Min 1/4 in. diam bead of caulk or sealant applied to gypsum board/penetrant interface at point contact location on
both sides of wall.
The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly In which It Is
Installed, as shown in the following table.
The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly
fire rating of the wall assembly in which It is installed, as tabulated below:
Max Pipe or F Rating I Rating
o,2 01 1or
oro 1 or4
or
or
or
+When copper pipe Is used, T Rating Is 0 hr.
3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant
-Bearing the UL Classification Marking
CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS
PROJECT SHr 1 of 1 SIGNATURE DATE
WL1001 DWG
SYSTEM/DESIGN NO. DATE NOT 1111
W -L-1001 AS
CDNSTR,CTIDN
DOCUMENT —
3M FIRE PROTECTION PRODUCTS cp: v"TrG.ar.,.r..--
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Floor or Wag Assembly - Min 4-1/2 In. thick lightweight or normal weight (100.150 pcf) concrete.
Wall may also be constructed of any ULClassdied Concrete Bloclks- . Max dlam of circular through
opening is 22-1/2 In.
See Concrete Blocks (CAZT) category In the Fire Resistance Directory for names of manufacturers.
1A. Steel Sleeve (Optional, not shown) - Nom 12 in. diam (or smaller) Schedule 40 (or heavier) steel
pipe sleeve cast Into concrete floor or wail. Sleeve to be flush with or project max 2 In. from top surface
of floor or from both surfaces of wag.
2. Through Penetrant - One metallic pipe, conduit or tubing Installed ether concentrically or
eecentrcalty within the firestop system. The annular space between pipe, conduit or tubing and periphery
of opening shall be min of O in. (pant contact) to max 1-3/8 in. Pipe, conduit or tubing to be rigidly
supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or
tubing may be used:
A. Steel Pipe - Nom 30 In, diam (or smaller) Schedule 10 (or heavier) steel pipe.
Al. Iron Pipe - Nom 30 In. diam (or smaller) cast orductile Iron pipe.
B. Conduit • Nom 6 In. diam (or smaller) NO steel conduit.
C. Conduit - Nom 4 In, diam (or smaller) steel electrical metallic tubing.
3. Packing Material - Polyethylene backer rod or nom 1 In. thickness of tightly -packed ceramic
(alumina silica) fiber blanket, mineral wool batt or glass fiber Insulation material used as a permanent
form. Packing material to be recessed from top surface of floors from both surfaces of sold concrete or
concrete block wall as required to accommodate the required thickness of caulk fill material (Item 4). As
an alternate when max pipe size is 10 in. diam and when max annular space Is 1 In., a min 1 In.
thickness of tightlypacked ceramic fiber blanket or mineral wool batt packing material may be rid
min 1/2 in. from bottom surface of floor or from either side of sold concrete wall.
4. FIII,Void or Cavity Materials• - Caulk or Sealant - Applied to fill the annular space to the min
thickness shown in the following table:
Max Pipe
Diam in.
Max Annular
Space in.
Packing Mel Type (a)
Min Caulk
Thkns In.
10
1
BR, CF,oFMW
)
((bcj
10
1
CFG
1/2
20
2-1/2
BR, CF, GF or MW
1 (b)
(a) BR - Polyethylene backer rod.
CF - Ceramic fiber blanket.
GF - Glass fiber Insulation.
MW - Mineral -wool batt.
(b) Caulk Installed flush with top surface of floor or both surfaces of wag.
(c) Caulk installed flush with bottom surface of floor or one surface of sold (non -concrete block) wag.
3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant. (The W Rating applies only when FB -3000 WT
sealant Is used.)
*Bearing the UL Classtncation Marking
CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS
PROJECT
SHT 1 Of I
SIGNATURE DATE
SIGNATURE DATE
Ca71001 DWG I
WJ3091.DWG
SYSTEM/DESIGN NO/L
DATE
NOT 115E
•, ,.a..y „y,,,,,,-,.y,d,,,.�..
C -Al -1001
AS
AS
DNSTRLICnM
CONSTRUCTION-
DOCU•JEW,
DRAW11,15 NOT
3M FIRE PROTECTION PRODUCTS
DOCLMEM
DRAwJrGto^•-
TO SCALE
TOSCALE
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Wall Assembly - Min 6 In. (152 mm) thick reinforced lightweight or normal weight (100-150 pd
or 1600-2400 kg/m3) concrete wall. Wall may also be constructed of any ULCIassMed Concrete
Blocks- . Max diam of opening .
Pe g ds 8 in. ( 203 mm)
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Cable -One cable Installed eccentrically or concentrically within opening. Annular space between
cable and periphery of opening to be min 0 in. (0 mm) (point contact) to max 1 in. (0 mm to 25 mm).
Cable to be rigidly supported on both sides of the wag. The following types and sizes of cable may be
used:
A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation
and jacketing material.
B. Max I/C No. 350 kcmil (or smaller) copper conductor cable with cross-linked polyethylene (XLPE)
or PVC jacket.
C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC
insulation with XLPE or PVCJacket.
D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with XLPE or PVC
Insulation and jacket.
E. Max 4/C No. 2/0 AWG (or smaller) copper conductor, aluminum dad or steel dad TECK90 cable
with or without PVC Jacketed,
F. Max 110/125 fiber optic (F.O.) cable with PVC Insulation and Jacket.
G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC Insulation and
jacket.
H. Max RG/U coaxial cable with fluorinated ethylene insulation and Jacket.
1. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar Jacket and Insulation.
J. Through Penetrating Product- - Any cables, Armored Cable+ or Metal Clad Cable+
currently Classified under the Through Penetrating Product category.
See Through Penetrating Product (XHLY) category In the Fire Resistance Directory for names of
manufacturers
3. FIII,Votd or Cavity Material- - Caulk or Sealant - Min 5/8 in. (16 mm) thickness mess of caulk or
sealant applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of
caulk or sealant applied to cable/wall Interface at pant contact kxabon on both sides of wall.
3M COMPANY - IC 15WS, CP 25W5+ caulk or FB -3000 WT sealant
-Bearing the UL Classification Marking
CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS
PROJECT
SM I of I
SIGNATURE DATE
WJ3091.DWG
SYSTEM/DESIGN NO. DATE
IT III
•, ,.a..y „y,,,,,,-,.y,d,,,.�..
W-1-3081C
AS
DNSTRLICnM
3M FIRE PROTECTION PRODUCTS
DOCU•JEW,
DRAW11,15 NOT
.N
TO SCALE
• NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
System No.W-L-3110
September 07, 2004
F Ratings - 1 and 2 Hr (See Item 1)
T Rating - 0 Hr
SECTION A -A
• NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
System No. C -A3-3200
SEptember, 2004
F Rating - 2 Hr
T Rating - 1/4 Hr
SECTION A -A
• NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY
System No.W-L-3001
September 07, 2004
(Formerly System No. 149)
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 3/4, 1, 1-1/2 and 2 Hr (See Item 2)
L Rating At Ambient - 15 CFM/sq ft (See Item 3)
L Rating At 400 F - less than 1 CFM/sq ft (See Item 3)
SECTION A -A
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Wall Assembly - The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly shall be constructed
of the materials and In the manner specified In the Individual U300 or U400 Series Wall and Partition
Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to
consist of nom 2 by 4 In. lumber spaced 16 In. OC. Steel studs to be min 3-1/2 In. wide and spaced
max 24 in. OC.
B. Gypsum Board' - Thickness, type, number of layers and fasteners as required in the Individual
Wall and Partition Design. Max diam of opening Is 4-1/2 In.
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall
assembly In which It is Installed.
2. Cables - Max 4 in. diam tight bundle of cables Installed eccentrically or concentrically In opening.
The annular space between the bundled cables and the periphery of the opening to be min. O In (point
contact) to a maximum 1/2 in. Cables may or may not be routed through flexible steel conduit with or
without vinyl coating. Cables to be rigidly supported on both sides of wall assembly. Any combination of
the following types and saes of cables may be used:
A. Max 150 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) Insulation
and jacket
B. Max 1/C 350 kcmll (or smaller) copper conductor cable with cross-linked polyethylene (XLPE
jacket.
C. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor cable with XLPE insulation and
PVC jacket.
D. Max 7/C No. 12 AWG (or smaller) copper conductor cable with PVC Insulation and jacket.
E. Max No. 18 AWG RG 6//U coaxial cable with PVC insulation and jacket.
F. Max 3/C with ground No. 12 AWG (or smaller) NM cable with PVC Insulation and jacket.
G. Through Penetrating Product' - Max 3/C No. 2 AWG (or smaller) aluminum or steel dad
Armored Cable- or aluminum or steel dad Metal Clad Cable- with copper conductors.
ALFLEX CORP
3. FIII,Void or Cavity Materials- - Caulk or Sealant - Min 5/8 in. thickness of fill material applied
within annulus, flush with each surface of wall. Min 5/81n. thickness of fill material applied Into
interstices of cables on both sides of wall.
3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant
-Beanng the UL Classification Marking
CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FORSYSTEMS OR DESIGN DETAILS
PROJECT
SM I Of I
SIGNATURE DATE
WL3110.DWG
SYSTEM/DESIGN NO. DATE
rAT FOR ISE
•, ,.a..y „y,,,,,,-,.y,d,,,.�..
W -L-3110
AS
CONSTRLJCTICN
3M FIRE PROTECTION PRODUCTS
DRAWDaGNOT
.N
TO SCALE
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Floor or Waft Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150
pef or 1600-2400 k0/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick
UL Classified hollow -core Precast Concrete Units' . Wall may also be constructed of any UL Classified
ConcreteBlocks' . Max diam of opening 6 in. (152 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in Fire Resistance Directory for
names of manufacturers.
2. Steel Sleeve (Optional) - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast
or grouted Into floor or wall assembly. Steel sleeve may be installed flush or may project max 2In. (51 mm)
beyond the floor or wag surfaces.
3. Cables -Aggregate cross-sectional area of cables In opening to be max 49 percent of the cross -sec anal
area Inside the sleeve or opening. Annular space between cables and periphery of opening or sleeve shall be
min of o In. (point contact) to max 2 In. (0 mm to max 51 mm) Cables to be rigidly supported on both sidesof
floor or wall assembly. Any combination of the following types and sizes of cable may be used;
A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) Insulation and
Jacketing material.
B. Max 1/C No. 750 kcmii (or smaller) copper conductor cable with aim -linked polyethylene (XLPE) jacket.
C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation
with XLPE or P/C jacket.
D. Max 3/C No. 3/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC Insulation and
jacket.
E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC Jacketed aluminum dad or steel clad TECK90
cable.
F. Max 110/125 fiber optic (F.O.) cable with PVC Insulation and jacket.
G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC Insulation and jacket.
H. RG/U coaxial cable with fluorinated ethylene (FE) or PVC Insulation and jacket.
I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar Jacket and insulation.
J. Max three conductor No. 12 AWG (or smaller) MC (BX) copper cable with polyvinyl chloride insulation and
jacket materials.
K. Through Penetrating Product- - Any cables, Armored Cable+ or Metal Clad Cable+ currently
Classified under the Through Penetrating Product category. See Through Penetrating Product (XHLY)
category In the Fire Resistance Directory for names Of manufacturers
4. Firestop System - The details of the firestop system shall be as follows:
A. Packing Material - Min 3 in. (76 mm) thickness of min 4 pd (64 kg/m3)mineral wool batt Insulation
firmly packed Into opening as a permanent form. Packing material to be recessed from top surface Of floor or
top edge of sleeve or from both surfaces of wall or both ends of sleeve as required to accommodate the
required thickness of NII material. In floors constructed of hollow -core concrete, packing material to be
recessed from top and bottom surfaces of floor or sleeve as required to accommodate the required thickness
of fill material.
B. FIII,Vold or Cavity Materials* -Caulk or Sealant -Min 1/2 In. (13 mm) thickness of caulk or sealant
applied within the annulus, flush with top surface of floor or top edge of sleeve or with both surfaces of wag or
both ends of sleeves. In floors constructed of hollow -core concrete, min 1/2 In. (13 mm) thickness of caulk or
sealant applied within the annulus, flush with top and bottom surfaces of floor or sleeves. Min 1/4 in. (6 mm)
diam bead of caulk applied to the penetrant/concrete or penetrant/sleeve interface at the point contact location
on the top surface of floor or both surfaces of wall or holkwr-core concrete.
3M COMPANY - CP 25WB+, IC 15WB caulk or FB -3000 WT sealant.
• Bearing the UL ClassMaition Marking
+ Bearing the UL Listing Mark
CONSULT CURRENT INDEPENDENT LABORATORIES (UL. OPL) FOR SYSTEMS OR DESIGN DETAILS
PROJECT SM 1 Of 1 SIGNATURE DATE
CA33200.DWG
SYSTEM/DESIGN NO. DATE NOT FOR USE
C -A]-3200 AS.�-.„;�-
CONSTRIJCTICN
3M FIRE PROTECTION PRODUCTS DRAW;I r ^ �
DOCLN NOT ra,•V-w+..
TO SCALE
REVISIONS
ZONE I REV DESCRIPTION DATE APPROVED
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed
of the materials and in the manner described in the Individual U300 or U400 Series Wall or Partttbn
Designs in the UL Fire Resistance Directory and shall Include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to
consist of nom 2 by 4 in. lumber spaced 16 In. OC with nom 2 by 4 in. lumber end plates and cross
braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 In. deep channels spaced max 24 In OC.
B. Gypsum Board* - Nom 1/2 or 5/8 In. thick, 4 ft wide with square or tapered edges. The gypsum
wallboard type, thickness, number of layers and sheet orientation shag be as specified In the Individual
Wall or Partition Design. Diam of circular through opening to be 3/8 In. to 5/8 In. larger than outside
diam of cable or cable bundle.
C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs
with cement coated nalls as specified In the Individual Wall or Partition Design. When steel channel stud
framing is employed, gypsum wallboard attached to studs with Type S self -drilling, self -tapping
bugle -head steel screws as specified In the individual Wail or Partition Design.
The hourly F Rating of the flrestop system is equal to the hourly fire rating of the well
assembly In which It Is Installed.
2. Cables - Individual cable or max 1 In. dlam cable bundle Installed in through opening with an
annular space of min 0 in. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of
wall assembly. The following types and sizes of cables may be used:
A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation
and Jacket materials. When max 25 pair telephone cable is used,
T Rating Is 2 hr.When 50 to 150 pair telephone cable Is used In 1 hr fire rated wall,
T Rating Is 3/4 hr.When 50 to 150 pair telephone cable is used In 2 hr fire rated wall, T
Rating Is 1 hr.
B. Max No. 10 AWG multiple copper conductor Type NM ('Romex' ) nonmetallic sheathed cable with
PVC Insulation and Jacket materials.
When Type NM cable is used, max T Rating Is 1-1/2 hr.
C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of
5/8 In.
When fiber optic cable is used, max T Rating is 2 hr.
D. Max 12 AWG multi conductor (max seven conductors) power/control cable with cross -finked
polyethylene (XLPE) Insulation and XLPE or PVC Jacket materials.
When muni conductor power/control cable Is used, max T Rating Is 2 hr.
E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SERcables with polyvinyl
chloride insulation and Jacket materials.
3. F)llvoid or Cavity Materials' - Caulk, SealarR or Putty - Caulk or putty fill material installed to
completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min
1/4 in. diam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each sole of the
wall.
3M COMPANY - MP+ Stbr putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty
(Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is used.)
-Bearing the UL Classification Mark
CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS
PROJECT SLR 1 Of I SIGNATURE DATE
WL3001.DWG
STSTEM/DESIGN NO. DATE NOT III
W -L-3001 COTAR
NSUCTIONDOCLMEW
3M FIRE PROTECTION PRODUCTS DRAMINOT-^'-
TO SCALE
NLAIM-DARE COUNTY
FIRE DEPARTI M- T
01
. a
REVISIONS
.N
i
• .a
,,w
i
3
J
1 Y
V
t�
.Q
UU
o
w
f�.•
V)
T__X
p
Li
Q
—
^
I..L
w
O
Li
O
F—
LL
w
—
O
�/^)
V
V J
S L
I-
Q
1
U =
O
())
72
LL1U
�
O
0 -
DRAWING TYPE
FIRE ALARM PLAN
SEAL
H
HOLLYWOOD VIOIMMINO
�r
4{
ROOM IIF)1sm% P.E /I
428 1 wain omr
H="11= R 33=
1154- 19f7. �
FL Lr- I amm
1
NN
•
Z
MM
W
0
t.®
U®
0
00
0
0
0
N
0
W
W
®
U)
ea
TIM,
�
LL
w
-S
0firm
®
C,
LawW
a
.4
�1
W
U
LLJ
k
N
I_
0
X
(M .3
® ®
LQ
f
O <
—0 X
V)
I--
U
Q
f
Z
O
U
DWG #: 0920-209F-2072
REVISION:
0
DATE: 09/20/2007
SCALE:
1/811=10-0e ,
DRAWN BY
F.O.
CHECKED BY
R.W.
SHEET
F A -
-30F
3