07-1381-003NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY System No.W-L-1001 September 07, 2004 (Formerly System No. 147) F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3) L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft - NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY System No. C -A3-1001 August 23, 2004 (Formerly System No. 49) F Rating - 3 Hr T Rating - 0 Hr W Rating - Class I (See Item 4) SEG 11QN A—A NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY A System No.W-3-3081 Septmber 08, 2004 F Rating - 2 Hr T Rating - 1/2 Hr REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Wall Assembly - The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materialsand in the manner described in the Individual U300 or U400 Series Wall or Partition Designs In the UL Fre Resistance Directory and shall include the following construction features: A Studs - Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel channel studs. Wood studs to consist of ram 2 by 4 in. lumber spaced 161n. OC with nom 2 by 41n. lumber end plates and cross braces. Steil studs to be min 3-5/8 in. wide by 1-3/81n. deep channels spaced max 24 in. or— B. CB. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 fL wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the Individual U300 or U400 Series Design In the UL Fire Resistance Directory. Max diam of opening Is 261n, 2. Through Penetrant - One metallic pipe, conduit or tubing Installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (point contact) to max 2 In. Pipe, conduit or tubing to be rigidly supported on both sides of wag assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 24 In. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 24 In. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 121n dwm (or smaller) or Class 50 (or heavier) ductile Iron pressure pipe C. Conduit - Nom 6 in. diam (or smaller) steel conduit or nom 4 in diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavies copper tubing E. Copper Pipe - Nom 6In. diam (or smaller) Regular (or heavier) copper pipe. F. Through Penetrating Product- - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used: 1. Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both skies of floor or wag assembly. OMEGA FLEX INC 2. Nom 1 len, diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both skies of floor or wall assembly. TITEFLEX CORP, A BUNDY CO 3. Nom 1 M. dlam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be remove) on both sides of floor or wall assembly. WARD MFG INC 3. FlII,Void or Cavity Material- - Caulk or Sealant - Min 5/8. 1.1/4,1-7/8 and 2-1/2 in, thickness of caulk or sealant for 1, Z 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wait Min 1/4 in. diam bead of caulk or sealant applied to gypsum board/penetrant interface at point contact location on both sides of wall. The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly In which It Is Installed, as shown in the following table. The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which It is installed, as tabulated below: Max Pipe or F Rating I Rating o,2 01 1or oro 1 or4 or or or +When copper pipe Is used, T Rating Is 0 hr. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant -Bearing the UL Classification Marking CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS PROJECT SHr 1 of 1 SIGNATURE DATE WL1001 DWG SYSTEM/DESIGN NO. DATE NOT 1111 W -L-1001 AS CDNSTR,CTIDN DOCUMENT — 3M FIRE PROTECTION PRODUCTS cp: v"TrG.ar.,.r..-- REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Floor or Wag Assembly - Min 4-1/2 In. thick lightweight or normal weight (100.150 pcf) concrete. Wall may also be constructed of any ULClassdied Concrete Bloclks- . Max dlam of circular through opening is 22-1/2 In. See Concrete Blocks (CAZT) category In the Fire Resistance Directory for names of manufacturers. 1A. Steel Sleeve (Optional, not shown) - Nom 12 in. diam (or smaller) Schedule 40 (or heavier) steel pipe sleeve cast Into concrete floor or wail. Sleeve to be flush with or project max 2 In. from top surface of floor or from both surfaces of wag. 2. Through Penetrant - One metallic pipe, conduit or tubing Installed ether concentrically or eecentrcalty within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of O in. (pant contact) to max 1-3/8 in. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 In, diam (or smaller) Schedule 10 (or heavier) steel pipe. Al. Iron Pipe - Nom 30 In. diam (or smaller) cast orductile Iron pipe. B. Conduit • Nom 6 In. diam (or smaller) NO steel conduit. C. Conduit - Nom 4 In, diam (or smaller) steel electrical metallic tubing. 3. Packing Material - Polyethylene backer rod or nom 1 In. thickness of tightly -packed ceramic (alumina silica) fiber blanket, mineral wool batt or glass fiber Insulation material used as a permanent form. Packing material to be recessed from top surface of floors from both surfaces of sold concrete or concrete block wall as required to accommodate the required thickness of caulk fill material (Item 4). As an alternate when max pipe size is 10 in. diam and when max annular space Is 1 In., a min 1 In. thickness of tightlypacked ceramic fiber blanket or mineral wool batt packing material may be rid min 1/2 in. from bottom surface of floor or from either side of sold concrete wall. 4. FIII,Void or Cavity Materials• - Caulk or Sealant - Applied to fill the annular space to the min thickness shown in the following table: Max Pipe Diam in. Max Annular Space in. Packing Mel Type (a) Min Caulk Thkns In. 10 1 BR, CF,oFMW ) ((bcj 10 1 CFG 1/2 20 2-1/2 BR, CF, GF or MW 1 (b) (a) BR - Polyethylene backer rod. CF - Ceramic fiber blanket. GF - Glass fiber Insulation. MW - Mineral -wool batt. (b) Caulk Installed flush with top surface of floor or both surfaces of wag. (c) Caulk installed flush with bottom surface of floor or one surface of sold (non -concrete block) wag. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant. (The W Rating applies only when FB -3000 WT sealant Is used.) *Bearing the UL Classtncation Marking CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS PROJECT SHT 1 Of I SIGNATURE DATE SIGNATURE DATE Ca71001 DWG I WJ3091.DWG SYSTEM/DESIGN NO/L DATE NOT 115E •, ,.a..y „y,,,,,,-,.y,d,,,.�.. C -Al -1001 AS AS DNSTRLICnM CONSTRUCTION- DOCU•JEW, DRAW11,15 NOT 3M FIRE PROTECTION PRODUCTS DOCLMEM DRAwJrGto^•- TO SCALE TOSCALE REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Wall Assembly - Min 6 In. (152 mm) thick reinforced lightweight or normal weight (100-150 pd or 1600-2400 kg/m3) concrete wall. Wall may also be constructed of any ULCIassMed Concrete Blocks- . Max diam of opening . Pe g ds 8 in. ( 203 mm) See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Cable -One cable Installed eccentrically or concentrically within opening. Annular space between cable and periphery of opening to be min 0 in. (0 mm) (point contact) to max 1 in. (0 mm to 25 mm). Cable to be rigidly supported on both sides of the wag. The following types and sizes of cable may be used: A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material. B. Max I/C No. 350 kcmil (or smaller) copper conductor cable with cross-linked polyethylene (XLPE) or PVC jacket. C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE or PVCJacket. D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with XLPE or PVC Insulation and jacket. E. Max 4/C No. 2/0 AWG (or smaller) copper conductor, aluminum dad or steel dad TECK90 cable with or without PVC Jacketed, F. Max 110/125 fiber optic (F.O.) cable with PVC Insulation and Jacket. G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC Insulation and jacket. H. Max RG/U coaxial cable with fluorinated ethylene insulation and Jacket. 1. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar Jacket and Insulation. J. Through Penetrating Product- - Any cables, Armored Cable+ or Metal Clad Cable+ currently Classified under the Through Penetrating Product category. See Through Penetrating Product (XHLY) category In the Fire Resistance Directory for names of manufacturers 3. FIII,Votd or Cavity Material- - Caulk or Sealant - Min 5/8 in. (16 mm) thickness mess of caulk or sealant applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk or sealant applied to cable/wall Interface at pant contact kxabon on both sides of wall. 3M COMPANY - IC 15WS, CP 25W5+ caulk or FB -3000 WT sealant -Bearing the UL Classification Marking CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS PROJECT SM I of I SIGNATURE DATE WJ3091.DWG SYSTEM/DESIGN NO. DATE IT III •, ,.a..y „y,,,,,,-,.y,d,,,.�.. W-1-3081C AS DNSTRLICnM 3M FIRE PROTECTION PRODUCTS DOCU•JEW, DRAW11,15 NOT .N TO SCALE • NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY System No.W-L-3110 September 07, 2004 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr SECTION A -A • NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY System No. C -A3-3200 SEptember, 2004 F Rating - 2 Hr T Rating - 1/4 Hr SECTION A -A • NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY System No.W-L-3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1-1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM/sq ft (See Item 3) L Rating At 400 F - less than 1 CFM/sq ft (See Item 3) SECTION A -A REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Wall Assembly - The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly shall be constructed of the materials and In the manner specified In the Individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 16 In. OC. Steel studs to be min 3-1/2 In. wide and spaced max 24 in. OC. B. Gypsum Board' - Thickness, type, number of layers and fasteners as required in the Individual Wall and Partition Design. Max diam of opening Is 4-1/2 In. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly In which It is Installed. 2. Cables - Max 4 in. diam tight bundle of cables Installed eccentrically or concentrically In opening. The annular space between the bundled cables and the periphery of the opening to be min. O In (point contact) to a maximum 1/2 in. Cables may or may not be routed through flexible steel conduit with or without vinyl coating. Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and saes of cables may be used: A. Max 150 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) Insulation and jacket B. Max 1/C 350 kcmll (or smaller) copper conductor cable with cross-linked polyethylene (XLPE jacket. C. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor cable with XLPE insulation and PVC jacket. D. Max 7/C No. 12 AWG (or smaller) copper conductor cable with PVC Insulation and jacket. E. Max No. 18 AWG RG 6//U coaxial cable with PVC insulation and jacket. F. Max 3/C with ground No. 12 AWG (or smaller) NM cable with PVC Insulation and jacket. G. Through Penetrating Product' - Max 3/C No. 2 AWG (or smaller) aluminum or steel dad Armored Cable- or aluminum or steel dad Metal Clad Cable- with copper conductors. ALFLEX CORP 3. FIII,Void or Cavity Materials- - Caulk or Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush with each surface of wall. Min 5/81n. thickness of fill material applied Into interstices of cables on both sides of wall. 3M COMPANY - CP 25WB+ caulk or FB -3000 WT sealant -Beanng the UL Classification Marking CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FORSYSTEMS OR DESIGN DETAILS PROJECT SM I Of I SIGNATURE DATE WL3110.DWG SYSTEM/DESIGN NO. DATE rAT FOR ISE •, ,.a..y „y,,,,,,-,.y,d,,,.�.. W -L-3110 AS CONSTRLJCTICN 3M FIRE PROTECTION PRODUCTS DRAWDaGNOT .N TO SCALE REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Floor or Waft Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pef or 1600-2400 k0/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow -core Precast Concrete Units' . Wall may also be constructed of any UL Classified ConcreteBlocks' . Max diam of opening 6 in. (152 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve (Optional) - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted Into floor or wall assembly. Steel sleeve may be installed flush or may project max 2In. (51 mm) beyond the floor or wag surfaces. 3. Cables -Aggregate cross-sectional area of cables In opening to be max 49 percent of the cross -sec anal area Inside the sleeve or opening. Annular space between cables and periphery of opening or sleeve shall be min of o In. (point contact) to max 2 In. (0 mm to max 51 mm) Cables to be rigidly supported on both sidesof floor or wall assembly. Any combination of the following types and sizes of cable may be used; A. Max 200 pair No. 22 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) Insulation and Jacketing material. B. Max 1/C No. 750 kcmii (or smaller) copper conductor cable with aim -linked polyethylene (XLPE) jacket. C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE or P/C jacket. D. Max 3/C No. 3/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC Insulation and jacket. E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC Jacketed aluminum dad or steel clad TECK90 cable. F. Max 110/125 fiber optic (F.O.) cable with PVC Insulation and jacket. G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable with PVC Insulation and jacket. H. RG/U coaxial cable with fluorinated ethylene (FE) or PVC Insulation and jacket. I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar Jacket and insulation. J. Max three conductor No. 12 AWG (or smaller) MC (BX) copper cable with polyvinyl chloride insulation and jacket materials. K. Through Penetrating Product- - Any cables, Armored Cable+ or Metal Clad Cable+ currently Classified under the Through Penetrating Product category. See Through Penetrating Product (XHLY) category In the Fire Resistance Directory for names Of manufacturers 4. Firestop System - The details of the firestop system shall be as follows: A. Packing Material - Min 3 in. (76 mm) thickness of min 4 pd (64 kg/m3)mineral wool batt Insulation firmly packed Into opening as a permanent form. Packing material to be recessed from top surface Of floor or top edge of sleeve or from both surfaces of wall or both ends of sleeve as required to accommodate the required thickness of NII material. In floors constructed of hollow -core concrete, packing material to be recessed from top and bottom surfaces of floor or sleeve as required to accommodate the required thickness of fill material. B. FIII,Vold or Cavity Materials* -Caulk or Sealant -Min 1/2 In. (13 mm) thickness of caulk or sealant applied within the annulus, flush with top surface of floor or top edge of sleeve or with both surfaces of wag or both ends of sleeves. In floors constructed of hollow -core concrete, min 1/2 In. (13 mm) thickness of caulk or sealant applied within the annulus, flush with top and bottom surfaces of floor or sleeves. Min 1/4 in. (6 mm) diam bead of caulk applied to the penetrant/concrete or penetrant/sleeve interface at the point contact location on the top surface of floor or both surfaces of wall or holkwr-core concrete. 3M COMPANY - CP 25WB+, IC 15WB caulk or FB -3000 WT sealant. • Bearing the UL ClassMaition Marking + Bearing the UL Listing Mark CONSULT CURRENT INDEPENDENT LABORATORIES (UL. OPL) FOR SYSTEMS OR DESIGN DETAILS PROJECT SM 1 Of 1 SIGNATURE DATE CA33200.DWG SYSTEM/DESIGN NO. DATE NOT FOR USE C -A]-3200 AS.�-.„;�- CONSTRIJCTICN 3M FIRE PROTECTION PRODUCTS DRAW;I r ^ � DOCLN NOT ra,•V-w+.. TO SCALE REVISIONS ZONE I REV DESCRIPTION DATE APPROVED 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the Individual U300 or U400 Series Wall or Partttbn Designs in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 In. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 In. deep channels spaced max 24 In OC. B. Gypsum Board* - Nom 1/2 or 5/8 In. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers and sheet orientation shag be as specified In the Individual Wall or Partition Design. Diam of circular through opening to be 3/8 In. to 5/8 In. larger than outside diam of cable or cable bundle. C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs with cement coated nalls as specified In the Individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self -drilling, self -tapping bugle -head steel screws as specified In the individual Wail or Partition Design. The hourly F Rating of the flrestop system is equal to the hourly fire rating of the well assembly In which It Is Installed. 2. Cables - Individual cable or max 1 In. dlam cable bundle Installed in through opening with an annular space of min 0 in. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and Jacket materials. When max 25 pair telephone cable is used, T Rating Is 2 hr.When 50 to 150 pair telephone cable Is used In 1 hr fire rated wall, T Rating Is 3/4 hr.When 50 to 150 pair telephone cable is used In 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ('Romex' ) nonmetallic sheathed cable with PVC Insulation and Jacket materials. When Type NM cable is used, max T Rating Is 1-1/2 hr. C. Multiple fiber optical communication cable jacketed with PVC and having a max outside diam of 5/8 In. When fiber optic cable is used, max T Rating is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power/control cable with cross -finked polyethylene (XLPE) Insulation and XLPE or PVC Jacket materials. When muni conductor power/control cable Is used, max T Rating Is 2 hr. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SERcables with polyvinyl chloride insulation and Jacket materials. 3. F)llvoid or Cavity Materials' - Caulk, SealarR or Putty - Caulk or putty fill material installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. diam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each sole of the wall. 3M COMPANY - MP+ Stbr putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant is used.) -Bearing the UL Classification Mark CONSULT CURRENT INDEPENDENT LABORATORIES (UL, OPL) FOR SYSTEMS OR DESIGN DETAILS PROJECT SLR 1 Of I SIGNATURE DATE WL3001.DWG STSTEM/DESIGN NO. DATE NOT III W -L-3001 COTAR NSUCTIONDOCLMEW 3M FIRE PROTECTION PRODUCTS DRAMINOT-^'- TO SCALE NLAIM-DARE COUNTY FIRE DEPARTI M- T 01 . a REVISIONS .N i • .a ,,w i 3 J 1 Y V t� .Q UU o w f�.• V) T__X p Li Q — ^ I..L w O Li O F— LL w — O �/^) V V J S L I- Q 1 U = O ()) 72 LL1U � O 0 - DRAWING TYPE FIRE ALARM PLAN SEAL H HOLLYWOOD VIOIMMINO �r 4{ ROOM IIF)1sm% P.E /I 428 1 wain omr H="11= R 33= 1154- 19f7. � FL Lr- I amm 1 NN • Z MM W 0 t.® U® 0 00 0 0 0 N 0 W W ® U) ea TIM, � LL w -S 0firm ® C, LawW a .4 �1 W U LLJ k N I_ 0 X (M .3 ® ® LQ f O < —0 X V) I-- U Q f Z O U DWG #: 0920-209F-2072 REVISION: 0 DATE: 09/20/2007 SCALE: 1/811=10-0e , DRAWN BY F.O. CHECKED BY R.W. SHEET F A - -30F 3