07-1381-002FIRE -LITE MS-5UD-3 BATTERY CALCULATIONS
WIRE LEGEND
SYM.
CD QTY
STANDYBY
PER.DEV.
TOTAL
STANDBY
ALARM
PER.DEV.
TOTAL
ALARM
FIRE ALARM PANEL
1
0.08000
0.08000
0.112000
0.112000
2W -B SMOKE DETECTOR
7
0.000050
0.00035
0.000050
0.00035
ANN -80 ANNUNCIATOR
1
0.037000
0.037000
0.040000
0.040000
STROBE WALL MOUNT (75CD)
SYSTEM SENSOR
SR
DD
DUCT SMOKE DETECTOR
INSTALLED BY OTHERS
WP
WEATHERPROOF HORN/STROBE WALL MOUNT (75cd)
SYSTEM SENSOR
P2RK
OHEAT
DETECTOR
SYSTEM SENSOR
5600
I
14
II
0.00307
FORMULA FOR CALCULATION OF VOLTAGE
L=
80
DROP IN DC 2 WIRE CIRCUITS
1=
0.905
VD=
OA4
VD=R x 2 L x 1
VOLTAGE AT LAST DEVICE
19.96
Q
%OF VOLTAGE DROP
2.18%
W HERE VD = VOLTAGE DROP AT THE LAST DEVICE ON THE CIRCUIT
ACCEPTABLE V - DROP
OK
TOTAL INPUT:
0.152
CIRCUIT #1 2.5 Amps Max.
FOOT ( VALUES OF RESISTANCE FOR COPPER WIRE
_0
NAC #3 W IRE SIZE
PER TABLE ABOVE) "I"= TOTAL CIRCUIT CURRENT IN AMPERES
P2R WALL MOUNT HORN/STROBE
75 2
N/A
N/A
0.176
0.352
SR WALL MOUNT STROBE
75 2
N/A
N/A
0.158
0.316
P2R WALL MOUNT HORN STROBE
95 1
N/A
N/A
0.201
0.201
P2RK WEATHERPROOF WALL MOUNT HORN/STROBE
75 1
N/A
N/A
0.176
0.176
W
NAC#4 WIRESIZE
I-
TOTAL CIRCUIT #1:
1.045
CIRCUIT #2 2.5 Amps Max.
#NIA
(INFORMA77ON PROVIDED BY CUSTOMER)
L7 -
=I=
�1
P2R WALL MOUNT HORN/STROBE
75 2
N/A
N/A
0.176
0.352
P2R WALL MOUNT HORN/STROBE
95 1
N/A
N/A
0.201
0.201
P2RK WEATHERPROOF WALL MOUNT HORN/STROBE
75 2
N/A
N/A
0.176
0.352
U
TOTAL CIRCUIT #2:
0.905
CIRCUIT #3 2.5 Amps Max. (SPARE)
CD
P2R WALL MOUNT HORN/STROBE
75 0
N/A
N/A
0.176
0.000
SR WALL MOUNT STROBE
75 0
N/A
N/A
0.158
0.000
TOTAL CIRCUIT #3:
0.000
CIRCUIT #4 2.5 Amps Max. (SPARE)
FIRE ALARM PLAN
SEAL
P2R WALL MOUNT HORN/STROBE
75 0
N/A
N/A
0.176
0.000
SR WALL MOUNT STROBE
75 0
N/A
N/A
0.158
0.000
TOTAL CIRCUIT #4:
0.000
�'I• Cv!
(A) TOTAL STANDBY
0.117
ALARM
2.102
(B) STANDBY HOURS
(24 OR 60):
24
(A) X (B) = (C) (C) TOTAL STANDBY AMP HOURS:
2.808
V.
(D) ALARM SOUNDING PERIOD
IN MINUTES (5 OR 15): 5
MINUTES =
0.083 HOURS
TOTAL ALARM X 0.083 = (E) TOTAL ALARM
(F) TOTAL ALARM +
AMP HOURS:
STANDBY AH:
0.174
2.982
MOLT. BY DERATING FACTOR - 1.2
3.578
QTY:2 REQUIRED MINIMUM 12 AH
BATTERY PROVIDED CHARGE CAPACITY IS 18 AH
ZONE 3
INITIATING CIRCUITS TO BE CLASS B
ANSUL
SYSTEM HOOD
ZONE 5
-LD--t-mf
Z502 Z501
ZONE 4 P P P
Z403 Z402 Z401
2307 2306 2305 2304 2303 2302
ZONE 2-
ZONE 1
FIRE ALARM 'LEGEND
WIRE LEGEND
SYM.
WIRE TYPE AND
DESCRIPTION
A
14-2 FPL WIRE FOR
HORNS AND STROBES
B
18-2 FPL WIRE FOR
INITIATION
C
12 AWG THHN WIRE FOR
FACP & POWER SUPP. POWER
D
12 AWG THHN WIRE FOR
FACP & POWER SUPP. GROUND
F
18-2 FPL 24 VOLT
POWER
E
4C-#18 FPLR
DETECTORS
ZONE 3
INITIATING CIRCUITS TO BE CLASS B
ANSUL
SYSTEM HOOD
ZONE 5
-LD--t-mf
Z502 Z501
ZONE 4 P P P
Z403 Z402 Z401
2307 2306 2305 2304 2303 2302
ZONE 2-
ZONE 1
FIRE ALARM 'LEGEND
SYMBOL
DESCRIPTION
MANUFACTURER
MODEL
FACP
FIRE ALARM CONTROL PANEL
FIRE -LITE
MS-5UD-3
FAAP
FIRE ALARM ANNUNCIATOR PANEL
FIRE -LITE
ANN -80
R=
HORN/STROBE WALL MOUNT (75cd)
SYSTEM SENSOR
P2R
OP
PULL STATION
FIRE -LITE
BG -12L
OSMOKE
DETECTORS
SYSTEM SENSOR
2W -B
L❑
STROBE WALL MOUNT (75CD)
SYSTEM SENSOR
SR
DD
DUCT SMOKE DETECTOR
INSTALLED BY OTHERS
WP
WEATHERPROOF HORN/STROBE WALL MOUNT (75cd)
SYSTEM SENSOR
P2RK
OHEAT
DETECTOR
SYSTEM SENSOR
5600
I
14
II
0.00307
FORMULA FOR CALCULATION OF VOLTAGE
L=
80
DROP IN DC 2 WIRE CIRCUITS
NA.C. VOLTAGE DROP CALCULATIONS
176
176
DC RESISTANCE FOR SOLID COPPER WIRES
176 176
H2O2 H2O3
7
AT 75 DEGREES -C
9
NAC #1 W IRE SIZE
14
B
ig
91
R=
0.00307
SIZE OHMS PER FOOT
fi-ftWP
L=
105
18 0.00777
1=
1.045
16 0.00489
VD=
0.67
14 0.00307
VOLTAGE AT LAST DEVICE
19.73
12 0.00193
%OF VOLTAGE DROP
3.30%
10 0.00121
H104
ACCEPTABLE V -DROP
YES
VALUES TAKEN FROM 1999 NEC CHAPTER 9 TABLE 8
NAC #2 W IRE SIZE
14
1=
0.00307
FORMULA FOR CALCULATION OF VOLTAGE
L=
80
DROP IN DC 2 WIRE CIRCUITS
1=
0.905
VD=
OA4
VD=R x 2 L x 1
VOLTAGE AT LAST DEVICE
19.96
Q
%OF VOLTAGE DROP
2.18%
W HERE VD = VOLTAGE DROP AT THE LAST DEVICE ON THE CIRCUIT
ACCEPTABLE V - DROP
OK
"R" = RESISTANCE OF WIRE IN OHMS PER
FOOT ( VALUES OF RESISTANCE FOR COPPER WIRE
_0
NAC #3 W IRE SIZE
PER TABLE ABOVE) "I"= TOTAL CIRCUIT CURRENT IN AMPERES
R=
#NIA
" L" =LENGTH ONE WAYOF THE CIRCUIT IN FEET
Q
L=
L d
<
1=
VD=
#NIA
STARTING VOLTAGE USED IN CALCULATIONS IS 20A
�
VOLTAGE AT LAST DEVICE
# WA
PER U.L & NFPA REQUIREMENTS
p
%OF VOLTAGE DROP
#NIA
W
ACCEPTABLE V - DROP
#WA
W
NAC#4 WIRESIZE
I-
�
w
#NIA
(INFORMA77ON PROVIDED BY CUSTOMER)
L7 -
=I=
�1
0=
I=
VD=
#WA
007
VOLTAGE AT LAST DEVICE
#NIA
%OF VOLTAGE DROP
#NIA
Q
ACCEPTABLE V - DROP
#NIA
2301
2201
DDE DD
2102 2101
13
PHONE LINE #1 -
PHONE LINEA2 -
(TO U.L. CENTRALS TION)
NOTIFICATION CIRCUITS TO BE STYLE Y
C
9
FACP
NEW
FI ELITE F1
MS -50-3
PANEL
DACT
120VAC
22AWGTHHN CONDUCTOR
PANEL E BREAKERCKT18 OVERCURRENT 2�
120 VOLT MAXIMUM.
FIRE ALARM GENERAL NOTES:
1. NEW FIRE -LITE MS-5UD-3 FIRE ALARM PANEL =_
TO BE POWER LIMITED AND HAVE BATTERY BACKUP.
2. BUILDING IS EXISTING. _ -- _
3. BUILDING IS NOT SPRINKLERED. _
4. OCCUPANCY: RESTAURANT -
5. SYSTEM AND INSTALLATION TO COMPLY WITH LIFE SAFETY 2003,
NFPA-72 2002 EDITION, NEC -760 2005, AND NFPA101 2003 EDITION.
6. WIRING MINIMUMS;
INITIATING CIRCUITS 18/2 FPL
INDICATING CIRCUITS 14/2 FPL (NAC)
7. CONDUIT IF REQUIRED WILL BE 1/2-, MINIMUM 40% FILL MAX.
8. ALL DEVICES TO BE MOUNTED PER NFPA GUIDELINES OR ADA WHERE REQUIRED.
9. SYSTEM COMPONENTS SHALL BE U.L LISTED AND COMPATIBLE.
10. CIRCUITS TO BE CLASS B.
11. WHERE AUDIBLE APPLIANCES ARE INSTALLED, THEY SHALL HAVE A SOUND LEVEL OF AT LEAST
15dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dB ABOVE THE MAXIMUM SOUND LEVEL,
HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FEET ABOVE THROUGHOUT ALL OCCUPIED AREAS.
AFA WILL CERTIFY THE DBA LEVEL WITH AN APPROVED DBA METER PRIOR TO THE ISSUANCE OF THE
CERTIFICATE OF OCCUPANCY.
12. AUDIBLE RATINGS, AS MEASURED BY THE MANUFACTURER AND THE QUALIFIED TESTING LABS, ARE SPECIFIED
AS A DECIBEL RATING AT A PREDETERMINED DISTANCE, USUALLY 10 FT. THE RULE OF THUMB IS THAT THE OUTPUT
OF AN AUDIBLE NOTIFICATION APPLIANCE IS REDUCED BY 6dI3 IF THE DISTANCE BETWEEN THE APPLIANCE AND
LISTENER IS DOUBLED.
13. CEILING HEIGHT IS 12'0" A.F.F. THROUGHOUT RESTAURANT AREA.
14. EACH STROBE SHALL BE ADEQUATE TO PROVIDE REQUIRED COVERAGE.
15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11-4.28.3.
SCOPE OF WORK:
1. INSTALL NEW CONVENTIONAL FIRE -LITE MS-5UD-3 FIRE ALARM PANEL AT REFERENCED PROPERTY.
2. SCOPE OF WORK IS LIMITED ONLY TO WHAT IS PROVIDED ON FLOOR PLAN AND RISER.
3. FIRE ALARM CONTROL PANEL TO BE PROTECTED BY SMOKE DETECTOR.
4. INSTALL PULL STATIONS AT EXITS.
5. INSTALL HORN/STROBES AND STROBES THROUGHOUT.
6. AUDIBLE TROUBLE SIGNAL TO BE LOCATED AT FACP AND ANNUNCIATOR.
7. SYSTEM SHALL BE A CERTIFICATED U.L. CENTRAL STATION WITH 24 HOURS OF STANDBY.
8. DEVICE Z501 & Z502 ARE FOR REPRESENTATION ONLY. THESE DEVICES ALLOW INSTALLERS TO BE AWARE OF CONNECTIONS TO THE HOOD & ANSUL SYSTEMS.
SEQUENCE OF OPERATION:
THE ACTUATION OF THE FIRE ALARM INITIATING DEVICE SHALL AUTOMATICALLY INITIATE THE FUNCTION DETAILED BELOW.
A. MANUAL FIRE ALARM PULL STATION
- ACTIVATION OF THE MANUAL FIRE ALARM PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL.
2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF A HORN/STROBE
DEVICE. GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES
OR COMBINATION HORN/STROBE NOTIFICATION DEVICES.
3. INDICATE THE LOCATION OF THE PULL STATION, BY DISPLAYING IN ENGLISH THE ALARMED DEVICE AND ITS LOCATION ON THE
FACP AND REMOTE ANNUNCIATOR DISPLAY.
4. WHEN ALARMED, TRANSMITS A FIRE ALARM SIGNAL TO THE U.L CENTRAL STATION.
B. SMOKE DETECTOR/HEAT DETECTOR
- ACTIVATION OF THE SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL.
2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF A HORN/STROBE
DEVICE. GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES
OR COMBINATION HORN/STROBE NOTIFICATION DEVICES.
3. INDICATE THE LOCATION OF THE SMOKE DETECTOR, BY DISPLAYING IN ENGLISH THE ALARMED DEVICE AND ITS LOCATION ON THE
FACP AND REMOTE ANNUNCIATOR DISPLAY.
4. WHEN ALARMED, TRANSMITS A FIRE ALARM SIGNAL TO THE U.L CENTRAL STATION.
C. TROUBLE SIGNAL
1. TROUBLE AND SUPERVISORY DEVICES SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, INSTEAD THEY SHOULD SHOW A
SUPERVISORY OR TROUBLE INDICATION AT FACP AND REMOTE ANNUNCIATOR IF INSTALLED. A TROUBLE SIGNAL COULD INDICATE
A BREAK IN THE CIRCUIT WIRING OR A DETECTOR THAT IS NOT OPERATING PROPERLY.
2. WHEN ALARMED, TRANSMITS A TROUBLE SIGNAL TO THE U.L. CENTRAL STATION.
D. DUCT DETECTORS
- ACTIVATION OF THE SMOKE DUCT DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SUPERVISORY SIGNAL AT FIRE ALARM CONTROL PANEL ONLY.
2. INDICATE THE LOCATION OF THE SMOKE DUCT DETECTOR BY DISPLAYING IN ENGLISH
THE ALARMED DEVICE AND ITS LOCATION ON THE FACP ANNUNCIATOR DISPLAY .
3. SHUT OFF THE AIR HANDLING UNIT AND A/C EQUIPMENT ASSOCIATED WITH THE DUCT DETECTOR.
4. WHEN ALARMED, TRANSMITS A SUPERVISORY SIGNAL TO THE U.L CENTRAL STATION.
1 1
176
176
201
176 176
H2O2 H2O3
7
7
9
75CD 75CD
E
B
ig
91
ig
igwp igwp
9
FACP
NEW
FI ELITE F1
MS -50-3
PANEL
DACT
120VAC
22AWGTHHN CONDUCTOR
PANEL E BREAKERCKT18 OVERCURRENT 2�
120 VOLT MAXIMUM.
FIRE ALARM GENERAL NOTES:
1. NEW FIRE -LITE MS-5UD-3 FIRE ALARM PANEL =_
TO BE POWER LIMITED AND HAVE BATTERY BACKUP.
2. BUILDING IS EXISTING. _ -- _
3. BUILDING IS NOT SPRINKLERED. _
4. OCCUPANCY: RESTAURANT -
5. SYSTEM AND INSTALLATION TO COMPLY WITH LIFE SAFETY 2003,
NFPA-72 2002 EDITION, NEC -760 2005, AND NFPA101 2003 EDITION.
6. WIRING MINIMUMS;
INITIATING CIRCUITS 18/2 FPL
INDICATING CIRCUITS 14/2 FPL (NAC)
7. CONDUIT IF REQUIRED WILL BE 1/2-, MINIMUM 40% FILL MAX.
8. ALL DEVICES TO BE MOUNTED PER NFPA GUIDELINES OR ADA WHERE REQUIRED.
9. SYSTEM COMPONENTS SHALL BE U.L LISTED AND COMPATIBLE.
10. CIRCUITS TO BE CLASS B.
11. WHERE AUDIBLE APPLIANCES ARE INSTALLED, THEY SHALL HAVE A SOUND LEVEL OF AT LEAST
15dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dB ABOVE THE MAXIMUM SOUND LEVEL,
HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FEET ABOVE THROUGHOUT ALL OCCUPIED AREAS.
AFA WILL CERTIFY THE DBA LEVEL WITH AN APPROVED DBA METER PRIOR TO THE ISSUANCE OF THE
CERTIFICATE OF OCCUPANCY.
12. AUDIBLE RATINGS, AS MEASURED BY THE MANUFACTURER AND THE QUALIFIED TESTING LABS, ARE SPECIFIED
AS A DECIBEL RATING AT A PREDETERMINED DISTANCE, USUALLY 10 FT. THE RULE OF THUMB IS THAT THE OUTPUT
OF AN AUDIBLE NOTIFICATION APPLIANCE IS REDUCED BY 6dI3 IF THE DISTANCE BETWEEN THE APPLIANCE AND
LISTENER IS DOUBLED.
13. CEILING HEIGHT IS 12'0" A.F.F. THROUGHOUT RESTAURANT AREA.
14. EACH STROBE SHALL BE ADEQUATE TO PROVIDE REQUIRED COVERAGE.
15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11-4.28.3.
SCOPE OF WORK:
1. INSTALL NEW CONVENTIONAL FIRE -LITE MS-5UD-3 FIRE ALARM PANEL AT REFERENCED PROPERTY.
2. SCOPE OF WORK IS LIMITED ONLY TO WHAT IS PROVIDED ON FLOOR PLAN AND RISER.
3. FIRE ALARM CONTROL PANEL TO BE PROTECTED BY SMOKE DETECTOR.
4. INSTALL PULL STATIONS AT EXITS.
5. INSTALL HORN/STROBES AND STROBES THROUGHOUT.
6. AUDIBLE TROUBLE SIGNAL TO BE LOCATED AT FACP AND ANNUNCIATOR.
7. SYSTEM SHALL BE A CERTIFICATED U.L. CENTRAL STATION WITH 24 HOURS OF STANDBY.
8. DEVICE Z501 & Z502 ARE FOR REPRESENTATION ONLY. THESE DEVICES ALLOW INSTALLERS TO BE AWARE OF CONNECTIONS TO THE HOOD & ANSUL SYSTEMS.
SEQUENCE OF OPERATION:
THE ACTUATION OF THE FIRE ALARM INITIATING DEVICE SHALL AUTOMATICALLY INITIATE THE FUNCTION DETAILED BELOW.
A. MANUAL FIRE ALARM PULL STATION
- ACTIVATION OF THE MANUAL FIRE ALARM PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL.
2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF A HORN/STROBE
DEVICE. GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES
OR COMBINATION HORN/STROBE NOTIFICATION DEVICES.
3. INDICATE THE LOCATION OF THE PULL STATION, BY DISPLAYING IN ENGLISH THE ALARMED DEVICE AND ITS LOCATION ON THE
FACP AND REMOTE ANNUNCIATOR DISPLAY.
4. WHEN ALARMED, TRANSMITS A FIRE ALARM SIGNAL TO THE U.L CENTRAL STATION.
B. SMOKE DETECTOR/HEAT DETECTOR
- ACTIVATION OF THE SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL.
2. GENERATE AN AUDIBLE ALARM SIGNAL SIMULTANEOUSLY ON DESIGNATED AREAS OF THE BUILDING BY MEANS OF A HORN/STROBE
DEVICE. GENERATE A VISUAL ALARM SIGNAL SIMULTANEOUSLY ON ALL AREAS OF THE BUILDING BY THE USE OF STROBE DEVICES
OR COMBINATION HORN/STROBE NOTIFICATION DEVICES.
3. INDICATE THE LOCATION OF THE SMOKE DETECTOR, BY DISPLAYING IN ENGLISH THE ALARMED DEVICE AND ITS LOCATION ON THE
FACP AND REMOTE ANNUNCIATOR DISPLAY.
4. WHEN ALARMED, TRANSMITS A FIRE ALARM SIGNAL TO THE U.L CENTRAL STATION.
C. TROUBLE SIGNAL
1. TROUBLE AND SUPERVISORY DEVICES SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, INSTEAD THEY SHOULD SHOW A
SUPERVISORY OR TROUBLE INDICATION AT FACP AND REMOTE ANNUNCIATOR IF INSTALLED. A TROUBLE SIGNAL COULD INDICATE
A BREAK IN THE CIRCUIT WIRING OR A DETECTOR THAT IS NOT OPERATING PROPERLY.
2. WHEN ALARMED, TRANSMITS A TROUBLE SIGNAL TO THE U.L. CENTRAL STATION.
D. DUCT DETECTORS
- ACTIVATION OF THE SMOKE DUCT DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS:
1. GENERATE AN AUDIBLE SUPERVISORY SIGNAL AT FIRE ALARM CONTROL PANEL ONLY.
2. INDICATE THE LOCATION OF THE SMOKE DUCT DETECTOR BY DISPLAYING IN ENGLISH
THE ALARMED DEVICE AND ITS LOCATION ON THE FACP ANNUNCIATOR DISPLAY .
3. SHUT OFF THE AIR HANDLING UNIT AND A/C EQUIPMENT ASSOCIATED WITH THE DUCT DETECTOR.
4. WHEN ALARMED, TRANSMITS A SUPERVISORY SIGNAL TO THE U.L CENTRAL STATION.
1 1
1 1 1 1
, l
' `^ E. O. L.
A H2O1
H2O2 H2O3
H2O4
H2O5
176
.176 .158
176
158 .201
75CD
75CD 75CD
75CD
75CD 95CD
fi-ftWP
L
L
E. 0. L.
A H101
H102 H103
H104
H105 H106
CIRCUIT #2
0.905 AMPS USED
2.5 AMPS MAX.
STYLE Y
CIRCUIT #1
1.045 AMPS USED
2.5 AMPS MAX.
STYLE Y
LOCATED IN
OFFICE
FIRE ALARM NOTES, DETAILS, RISER
SCALE:NTS
'woum
'1 A THHN CONDUCTOR
80" A.F.F. OR
6" BELOW CEILING
(WHICHEVER IS LOWEF
t� ASI M S"YSItM To BE
111STALL -D IN ACCORDANCE WPIH
NFPA 72; M 101 -
APPROVED
NIIA,NH-DARE COUNTY FIRE DEPARTMENT
BLDG. PERMIT FIRE ALAAU
FIRE SUPPRRESSIIOON WATER MAIN EXT.
DATE: A� P/ --7 ur
STROBE OR
HORN/STROBE
ION
ADA HEIGHT REQUIREMENTS
REVISIONS
z
�
Q
=
�-
_0
Q
0
L d
<
�
�
W
p
W
0
W
ry
I-
�
�1
0=
007
(f)�
Q
�-
0
U
CD
n
DRAWING TYPE
FIRE ALARM PLAN
SEAL
f
HOLLYWOOD EHOVIMMTRING '
N
Rowr Kamm pm�-r 423 s ow mcFmr
NGt1Y� = It 33m
,
.
�'I• Cv!
. ZJ to
V.
z
Do
0
®
O
0
0
0
N
®
w <
W
"fa
®
LL
}
I
U) LJ
ra
z
tamI
<
�
it
W®0)x0w
U
��
-
<
w
��=
<
®oQ
o ���
U
Q
Z
0
DWG #: 0920-209F-2072
REVISION:
0
DATE: 09/20/2007
SCALE:
DRAWN BY
F.O.
CHECKED BY
R.W.
SHEET
FA -2
of
3