06-633-010MECHANICAL NOTES 1.0 -GENERAL 1.1 - PROVIDE ( FURNISH AND INSTALL) ALL NECI=SARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATION SYSTEM AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED .IN5TALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, A5HRAE , NFPA, AND LOCAL ORDINANCES. 12 - SCOPE of WORK : PROVIDE THE FOLLOWING COMPLETE SYSTEMS A. SUPPLY AND RETURN DUCT SYSTEM. B. EXHAUST SYSTEM FOR BATHROOMS.(WHEN REQUIRED) C. AIR CONDITIONING UNITS WITH REFRIGERANT PIPING AND CONTROLS. 13 - PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED. 1.4 - VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS AND EQUIPMENT SIZES PRIOR TO DUCT FABRICATION OR INSTALLATION, COORDINATE REQUIREMENTS TO AVOID INTERFERENCE WITH OTHER TRADES. 1.5 - SUBMIT SHOP DRAWING FOR ARCHITECT/ ENGINEER APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS. Ib - GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. 2-0 - MATERIALS 2.1 - DUCTWORK ALL DUCT 51ZE ARE CLEAR INSIDE DIMENSIONS. A. GENERAL AREAS: FIVE POUNDS DENSITY 1.5' THICK GLASSFIBER (R-6) DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH 5MACNA'5 LOW PRESURE DUCT MANUAL ALL DUCT JOINTS SHALL BE SEALED AND TAPED. B: TOILETS ROOM, KITCHEN, CLOTH DRYER EXHAUST AND FRESH AIR INTAKE IF APPLICABLE: GALVANIZED SHEETMETAL, CONSTRUCTED AND INSTALLED ACCORDING t0 LATEST EDITION OF 5MACNA'5, LOW VELOCITY CONSTRUCTION 5TD. 2.1.1 - PROVIDE DOUBLE THICKNESS TURNING VANES At ALL SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS INSTEAD. 2.12 - PROVIDE VOLUME EXTRACTOR BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH. 22 - REFRIGERANT PIPING. SEAMLESS COPPER TYPE 'L' AND HARD OR SOFT DRAWN ON AGR COPPER TUBING WITH WROUGHT COPPER SOLDER JOINT FITTING, SOLDER SHALL BE 95/5 APPLIED WITH SUITABLE FLUX. 23 - INSULATE ALL REFRIGERANT SUCTION PIPING WITH 3/4' CLOSED CELL POLYETHYLENE PREMOLDED PIPE INSULATION, WITH AN APPROVED PIPE AND SMOKE JACKET. PAINT ALL EXPOSED INSULATION WITH TWO COATS OF WHITE LATEX PAINT. 2.4 - PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE NEAT -COOL TWERM05TACT5 WITH ON-OFF AUTO SUB -BASE SWITCH, FURNISHED BY THE EQUIPMET MANUFACTURER 2.5 - ALL AIR CONDITIONING COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF FIVE YEARS AFTER DATE OF ACCEPTANCE OF THE PROJECT. 2b - AIR DISTRIBUTION PRODUCTS: 2.6.1 - PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED ON THE DRAWINGS. 2.62 - PROVIDE EXTRUDED ALL ALUMINIUM AIR DISTRIBUTION PRODUCTS. 2.63 - PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS. 2.6.4 - PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS. 2fo.5 - PROVIDE (FURNISH AND INSTALL) POWER SUPPLY WIRING SOURCE TO POWER CONNECTION, INCLUDE STARTERS, DISCONNECTS AND REQUIRED ELECTRICAL DEVICES, INTERLOCK WIRING, RACEWAY, CONDUITS, PULL WIRES AND EXPOSED CONDUITS FOR TEMPERATURE CONTROL SYSTEM. ALL WIRING SHALL RUN IN CONDUITS, NO EXCEPTION. 3-0 - INSTALLATION 3.1 - INSTALL ALL EQUIPMENT IN ACCORDANCE TO THE MANUFACTURER'S MANUAL AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION t0 REQUIRED CLEARANCES FOR INSTALLATION, OPERATION AND SERVICE. 3.2 - BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND CAPACITIES, INDICATED ON DRAWINGS. SUBMIT FINAL TEST AND BALANCE REPORT t0 ARCHITECT/ ENGINEER FOR ACCEPTANCE. SUPPLY AIR DUCT METAL VOLUME DAMPER— QUADRANT OPERATOR TO BE OUTSIDE INSULATION PROVIDE INSULATION GUARD WNERE NECESSARY. INSULATE TOP OF ALL AIR TERMINALS DIi�USER —� INSULATED FLEX DUCT SEAL JOINT W/EPDXY AND DUCT TAPE - NO BOOT ONLY COLLAR SEAL JOIN" W1 EPDXY 4 mar 4 TAFE. ASG" SCHEDULE (RUUD SYSTEM RESIDENTIAL OR SIMILAR) UNIT TONS SEER GOND. UNIT MODEL NUM. AIR HANDLER MOVal- NUM. CFM COOLING CAPACITY (BTU/4) NET 5EN515LE (STU/H) NET LATENT (BTU/H) CONDENSER AIR HANDLER GOMPREB'R RLA/LRA FAX MTR FLA DIMENBfGN H -W -D WT. L55. ELECT. 6ERVICE FUSE REF. LINER LIQ.-SUCT. DIMENSIONS H -W -D FAN MTR HP WT. L66. 1 1.5 14.05 UAMC-018J U5HK-11 600 19,200 14,100 5,100 9/41 0.9 1gx233i4x351i2 140 208/230V-1-60 20 1/4 - 3/4 35x17'/2x22 1/3 92 2 4.0 130 UAMC-048J U51HK-24 1000 48000 33,500 14,500 19.2/131 1.5 23x31'/2x443%o 235 206123OV-1-60 40 3/a - 1-Va 35441i242 1/2 125 3 40 13-0 UAMC-048.1 UB1HK-24 160:'0 48,000 33,500 14,500 19.2/137 1.5 23x311i2x443ia 235 208/23OV-1-60 40 3/6 -1-1/6 35441i242 1/2 125 p ..77 A w/IMPERMEABLE, RESILIENT MATERIAL U PROVIDE SECONDARY Q DRAIN F -AN W/ ,J SUCTION LINE OVERFLC UJ SWITCH w/i/2'ARMAFLEX INSULATION NOTE: NO PLASTIC OR PVC IN R/A PLENUM. HVAC DESIGN REaUIRI=S: Y=5 NO DUCT SMOKE DETECTOR RESTROOM x FIRE DAMPER(S) OPENING REQUIRED x SMOKE DAMPER(5) CENTRIFUGAL CEILING FAN x FIRE RATED ENCLOSURE MAX_ SONE VALUE x FIRE RATED ROOF/FLOOR 100 x CEILING ASSEMBLY MOTOR HORSEPOWER R.P.M. x FIRE 5TOPING 120-1-60 x SMOKE CONTROL MODEL x FAN SCHEDULE NUMBER EF -I AREA SERVED RESTROOM LOCATION 15t FLOOR OPENING REQUIRED --- FAN TYPE CENTRIFUGAL CEILING FAN DRIVE TYPE DIRECT MAX_ SONE VALUE 1.5 AIR QUANTITY CFM. 100 FAN SPEED IN W.G. 1200 MOTOR HORSEPOWER R.P.M. 65 WATTS ELECTRICAL SERVICE 120-1-60 MANUFACTURER COOK MODEL GEMINI GC -240 REMARKS 1D 2O O lO PROVIDE WALL CAP MODEL WCA-Z ® PROVIDE FAN SPEED CONTROL t�3 PROVIDE ALUMINUM GRILLE OF WOOD ,JOISTS J c T"rFICAL A.H.U. CONDENSATE [DRAIN CONNECTION DETAIL N.t.S, MTL. PITCH PAN SECURE TO STRUCTURE PEEL BACK EXIST. ROOF FELTS INSTALL PITCH PAN HOT MOP FELTS DN. 4 LAP OVER TOP OF PAN WALL ROOF CAP w/ BUILT-IN CORROSION RE61TANT SCREEN (MESH SIZE NOT LARGER THAN 1/29 TILES 6'O MTL. DUCT EXHAU5T [DUCT pEiAIL N.T.S. PL.EXIE3LE DUCT CONNECTION DiL. N.T.S. A f fR HAND L E fR DETAIL N.t.S, CONDENSINCT UNIT MOUNiINC3 DETAIL N.T.S. (TO WITHSTAND 15(d MI=N WIND) FLEXIBLE CONNECTION WRAP AROUND EQUIPMENT M Q CD W/ 1/4'0 CABLE TO � 0 U REFRIGEIRANT LINES N N I- N WITHSTAND 150 MPH WIND FO (SUCTION INSULATED, AHU O LIQUID UiNINSULATED) CONDENSING UNIT METAL PAN FOR C 3 U X p EMERGENCY DRAIN C OUr PG GLEANLU O C m LLL TRAP CONCRETE BASE POWER 4 CONT. U PROVIDE ISOMODE w/6"x6'-10/10 WWF CONNECTIONS ISOLATION PADS GALVANIZED STEEL MOUNTING FRAME FASTEN C.U_ TO ANCHORED 4' 2x4 METAL SUPPORT ..M 2' CONDENSATE DRAIN FASTENED TO CONIC. SLAB LIQUID LINE Q_ TO DISCPARGE 6' A.F.G. OUTSIDE w/(2)1/2'7x3'ANCHOR BOLTS EA. w/O INSULATION cD Z BOLT TO FLOOR oo 12" FROM'BLDG. ° — 6' O SCH 40 2' EMERGENCY DRAIN SEAL ENTRANCE OF REF. PVC PIPE LINES INTO PVC PIPE p ..77 A w/IMPERMEABLE, RESILIENT MATERIAL U PROVIDE SECONDARY Q DRAIN F -AN W/ ,J SUCTION LINE OVERFLC UJ SWITCH w/i/2'ARMAFLEX INSULATION NOTE: NO PLASTIC OR PVC IN R/A PLENUM. 4 VAPOR BARRIER NO PVC, FOR A/C DRAIN LINE (NON COMBUSTIBLE) PL.EXIE3LE DUCT CONNECTION DiL. N.T.S. A f fR HAND L E fR DETAIL N.t.S, CONDENSINCT UNIT MOUNiINC3 DETAIL N.T.S. (TO WITHSTAND 15(d MI=N WIND) SHEET: M-3 OF: 3 M Q CD 0) � 0 U Li.l a D N N I- N ' ^ `T/ V r O Lo 3 U X p � M n SHEET: M-3 OF: 3 M M M p Z n O m LLL U O > IL W W 0 Q_ cD Z 000 �O U SHEET: M-3 OF: 3