06-633-010MECHANICAL NOTES
1.0 -GENERAL
1.1 - PROVIDE ( FURNISH AND INSTALL) ALL NECI=SARY MATERIALS AND LABOR FOR A COMPLETELY
OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATION SYSTEM AS SHOWN ON THE DRAWINGS AND
HEREIN SPECIFIED .IN5TALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
A5HRAE , NFPA, AND LOCAL ORDINANCES.
12 - SCOPE of WORK :
PROVIDE THE FOLLOWING COMPLETE SYSTEMS
A. SUPPLY AND RETURN DUCT SYSTEM.
B. EXHAUST SYSTEM FOR BATHROOMS.(WHEN REQUIRED)
C. AIR CONDITIONING UNITS WITH REFRIGERANT PIPING AND CONTROLS.
13 - PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED.
1.4 - VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS AND EQUIPMENT SIZES PRIOR TO DUCT
FABRICATION OR INSTALLATION, COORDINATE REQUIREMENTS TO AVOID INTERFERENCE WITH OTHER TRADES.
1.5 - SUBMIT SHOP DRAWING FOR ARCHITECT/ ENGINEER APPROVAL BEFORE PROCEEDING WITH THE PURCHASE
OR INSTALLATION OF EQUIPMENT AND MATERIALS.
Ib - GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD
OF ONE YEAR FROM DATE OF ACCEPTANCE.
2-0 - MATERIALS
2.1 - DUCTWORK ALL DUCT 51ZE ARE CLEAR INSIDE DIMENSIONS.
A. GENERAL AREAS: FIVE POUNDS DENSITY 1.5' THICK GLASSFIBER (R-6) DESIGNED, CONSTRUCTED AND
INSTALLED IN ACCORDANCE WITH 5MACNA'5 LOW PRESURE DUCT MANUAL
ALL DUCT JOINTS SHALL BE SEALED AND TAPED.
B: TOILETS ROOM, KITCHEN, CLOTH DRYER EXHAUST AND FRESH AIR INTAKE IF APPLICABLE:
GALVANIZED SHEETMETAL, CONSTRUCTED AND INSTALLED ACCORDING t0 LATEST EDITION OF
5MACNA'5, LOW VELOCITY CONSTRUCTION 5TD.
2.1.1 - PROVIDE DOUBLE THICKNESS TURNING VANES At ALL SQUARE ELBOWS.
WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS INSTEAD.
2.12 - PROVIDE VOLUME EXTRACTOR BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH.
22 - REFRIGERANT PIPING. SEAMLESS COPPER TYPE 'L' AND HARD OR SOFT DRAWN ON AGR COPPER TUBING
WITH WROUGHT COPPER SOLDER JOINT FITTING, SOLDER SHALL BE 95/5 APPLIED WITH SUITABLE FLUX.
23 - INSULATE ALL REFRIGERANT SUCTION PIPING WITH 3/4' CLOSED CELL POLYETHYLENE PREMOLDED PIPE
INSULATION, WITH AN APPROVED PIPE AND SMOKE JACKET. PAINT ALL EXPOSED INSULATION
WITH TWO COATS OF WHITE LATEX PAINT.
2.4 - PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE NEAT -COOL TWERM05TACT5
WITH ON-OFF AUTO SUB -BASE SWITCH, FURNISHED BY THE EQUIPMET MANUFACTURER
2.5 - ALL AIR CONDITIONING COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF FIVE
YEARS AFTER DATE OF ACCEPTANCE OF THE PROJECT.
2b - AIR DISTRIBUTION PRODUCTS:
2.6.1 - PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED ON THE DRAWINGS.
2.62 - PROVIDE EXTRUDED ALL ALUMINIUM AIR DISTRIBUTION PRODUCTS.
2.63 - PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES
AS SHOWN ON ARCHITECTURAL DRAWINGS.
2.6.4 - PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS.
2fo.5 - PROVIDE (FURNISH AND INSTALL) POWER SUPPLY WIRING SOURCE TO POWER CONNECTION, INCLUDE
STARTERS, DISCONNECTS AND REQUIRED ELECTRICAL DEVICES, INTERLOCK WIRING, RACEWAY, CONDUITS,
PULL WIRES AND EXPOSED CONDUITS FOR TEMPERATURE CONTROL SYSTEM.
ALL WIRING SHALL RUN IN CONDUITS, NO EXCEPTION.
3-0 - INSTALLATION
3.1 - INSTALL ALL EQUIPMENT IN ACCORDANCE TO THE MANUFACTURER'S MANUAL AND RECOMMENDATIONS,
PAYING SPECIAL ATTENTION t0 REQUIRED CLEARANCES FOR INSTALLATION, OPERATION AND SERVICE.
3.2 - BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND CAPACITIES, INDICATED ON DRAWINGS.
SUBMIT FINAL TEST AND BALANCE REPORT t0 ARCHITECT/ ENGINEER FOR ACCEPTANCE.
SUPPLY AIR DUCT
METAL VOLUME DAMPER—
QUADRANT OPERATOR
TO BE OUTSIDE INSULATION
PROVIDE INSULATION
GUARD WNERE NECESSARY.
INSULATE TOP OF
ALL AIR TERMINALS
DIi�USER —�
INSULATED FLEX DUCT
SEAL JOINT W/EPDXY
AND DUCT TAPE
- NO BOOT ONLY COLLAR
SEAL JOIN" W1
EPDXY 4 mar
4 TAFE.
ASG" SCHEDULE (RUUD SYSTEM RESIDENTIAL OR SIMILAR)
UNIT
TONS
SEER
GOND. UNIT
MODEL NUM.
AIR HANDLER
MOVal- NUM.
CFM
COOLING
CAPACITY
(BTU/4)
NET
5EN515LE
(STU/H)
NET
LATENT
(BTU/H)
CONDENSER
AIR HANDLER
GOMPREB'R
RLA/LRA
FAX MTR
FLA
DIMENBfGN
H -W -D
WT.
L55.
ELECT. 6ERVICE
FUSE
REF. LINER
LIQ.-SUCT.
DIMENSIONS
H -W -D
FAN MTR
HP
WT.
L66.
1
1.5
14.05
UAMC-018J
U5HK-11
600
19,200
14,100
5,100
9/41
0.9
1gx233i4x351i2
140
208/230V-1-60
20
1/4 - 3/4
35x17'/2x22
1/3
92
2
4.0
130
UAMC-048J
U51HK-24
1000
48000
33,500
14,500
19.2/131
1.5
23x31'/2x443%o
235
206123OV-1-60
40
3/a - 1-Va
35441i242
1/2
125
3
40
13-0
UAMC-048.1
UB1HK-24
160:'0
48,000
33,500
14,500
19.2/137
1.5
23x311i2x443ia
235
208/23OV-1-60
40
3/6 -1-1/6
35441i242
1/2
125
p
..77 A
w/IMPERMEABLE, RESILIENT MATERIAL
U
PROVIDE SECONDARY
Q
DRAIN F -AN W/ ,J
SUCTION LINE
OVERFLC UJ SWITCH
w/i/2'ARMAFLEX INSULATION
NOTE: NO PLASTIC OR PVC IN R/A PLENUM.
HVAC DESIGN REaUIRI=S:
Y=5
NO
DUCT SMOKE DETECTOR
RESTROOM
x
FIRE DAMPER(S)
OPENING REQUIRED
x
SMOKE DAMPER(5)
CENTRIFUGAL
CEILING FAN
x
FIRE RATED ENCLOSURE
MAX_ SONE VALUE
x
FIRE RATED ROOF/FLOOR
100
x
CEILING ASSEMBLY
MOTOR HORSEPOWER R.P.M.
x
FIRE 5TOPING
120-1-60
x
SMOKE CONTROL
MODEL
x
FAN SCHEDULE
NUMBER
EF -I
AREA SERVED
RESTROOM
LOCATION
15t FLOOR
OPENING REQUIRED
---
FAN TYPE
CENTRIFUGAL
CEILING FAN
DRIVE TYPE
DIRECT
MAX_ SONE VALUE
1.5
AIR QUANTITY CFM.
100
FAN SPEED IN W.G.
1200
MOTOR HORSEPOWER R.P.M.
65 WATTS
ELECTRICAL SERVICE
120-1-60
MANUFACTURER
COOK
MODEL
GEMINI
GC -240
REMARKS
1D 2O O
lO PROVIDE WALL CAP MODEL WCA-Z
® PROVIDE FAN SPEED CONTROL
t�3 PROVIDE ALUMINUM GRILLE
OF WOOD ,JOISTS
J
c
T"rFICAL A.H.U. CONDENSATE
[DRAIN CONNECTION DETAIL
N.t.S,
MTL. PITCH PAN SECURE
TO STRUCTURE
PEEL BACK EXIST.
ROOF FELTS INSTALL PITCH
PAN HOT MOP FELTS DN. 4
LAP OVER TOP OF PAN WALL
ROOF CAP w/ BUILT-IN
CORROSION RE61TANT
SCREEN (MESH SIZE NOT
LARGER THAN 1/29
TILES
6'O MTL. DUCT
EXHAU5T [DUCT pEiAIL
N.T.S.
PL.EXIE3LE DUCT CONNECTION DiL.
N.T.S.
A f fR HAND L E fR DETAIL
N.t.S,
CONDENSINCT UNIT MOUNiINC3 DETAIL
N.T.S. (TO WITHSTAND 15(d MI=N WIND)
FLEXIBLE CONNECTION
WRAP AROUND EQUIPMENT
M
Q
CD
W/ 1/4'0 CABLE TO
�
0
U
REFRIGEIRANT LINES
N
N
I-
N
WITHSTAND 150 MPH WIND FO
(SUCTION INSULATED,
AHU
O
LIQUID UiNINSULATED)
CONDENSING UNIT
METAL PAN FOR C
3
U
X
p
EMERGENCY DRAIN C
OUr PG
GLEANLU
O
C
m LLL
TRAP
CONCRETE BASE
POWER 4 CONT.
U
PROVIDE ISOMODE
w/6"x6'-10/10 WWF
CONNECTIONS
ISOLATION PADS GALVANIZED STEEL
MOUNTING FRAME
FASTEN C.U_ TO ANCHORED
4'
2x4 METAL SUPPORT
..M
2' CONDENSATE DRAIN
FASTENED TO CONIC. SLAB
LIQUID LINE
Q_
TO DISCPARGE 6' A.F.G. OUTSIDE
w/(2)1/2'7x3'ANCHOR BOLTS EA.
w/O INSULATION
cD Z
BOLT TO FLOOR oo 12" FROM'BLDG.
°
—
6' O SCH 40
2' EMERGENCY DRAIN
SEAL ENTRANCE OF REF.
PVC PIPE
LINES INTO PVC PIPE
p
..77 A
w/IMPERMEABLE, RESILIENT MATERIAL
U
PROVIDE SECONDARY
Q
DRAIN F -AN W/ ,J
SUCTION LINE
OVERFLC UJ SWITCH
w/i/2'ARMAFLEX INSULATION
NOTE: NO PLASTIC OR PVC IN R/A PLENUM.
4 VAPOR BARRIER
NO PVC, FOR A/C DRAIN LINE (NON COMBUSTIBLE)
PL.EXIE3LE DUCT CONNECTION DiL.
N.T.S.
A f fR HAND L E fR DETAIL
N.t.S,
CONDENSINCT UNIT MOUNiINC3 DETAIL
N.T.S. (TO WITHSTAND 15(d MI=N WIND)
SHEET: M-3
OF: 3
M
Q
CD
0)
�
0
U
Li.l
a
D
N
N
I-
N
' ^
`T/
V
r
O
Lo
3
U
X
p
�
M
n
SHEET: M-3
OF: 3
M
M
M
p
Z
n
O
m LLL
U
O
>
IL
W
W 0
Q_
cD Z
000
�O
U
SHEET: M-3
OF: 3