05-499-010AOl 'Wd I I V r% %a I V %.J I L- 0 1.0 1.1 PROVIDE FURNISH AND INSTALL ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS. 1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE SMACNA, NFPA AND LOCAL ORDINANCES. 1.3 SCOPE OF WORK : PROVIDE THE FOLLOWING COMPLETE SYSTEMS A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM. B. EXHAUST SYSTEM FOR TOILET ROOMS. C. EXHAUST SYSTEMS FOR WAREHOUSE. D. AIR CONDITIONING UNITS AND CONTROLS. E. INDEPENDENT TEST AND BALANCE. 1.4 NOT USED 1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED 1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND FABRICATION OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS FOR SERVICE AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER TRADES. 1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE SPECIFICATIONS. 1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS SHOWING DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL INFORMATION FROM 1.6 ABOVE. 1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE THE PURCHASE OR INSTALLATION OP EQUIPMENT AND MATERIALS. ALL SHOP DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE NO LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT. 1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE. 2.0 .NdM s 2.1 DUCTWORK 2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. 2.1.2 DUCTWORK MATERIALS: A: GENERAL OFFICE AREAS: FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER (R--6) DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA'S FIBROUS GLASS DUCT CONSTRUCTION STANDARDS. DUCT JOINTS SHALL BE SEALED AND TAPED. B: TOILET ROOM EXHAUST AND FRESH AIR INTAKES: GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION STD. (0.5" W.G.) C: EXPOSED AIR CONDITIONING DUCTWORK SPIRAL GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION STD, (0,5" W.G.) 2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS VANES. .1 ALTERNATE A: PROVIDE 3 -PIECE ELBOWS IN LIEU OF TURNING VANES FOR GLASS FIBER DUCTS ONLY. .2 ALTERNATE A: PROVIDE FULL RADIOS ELBOWS IN LIEU OF TURNING VANES. 2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH. 2.2 NOT USED. 2.3 NOT USED. GREENWICH TITLE INSURANCE OFFICE CONDO BUILDOUT SUITE 510, FIFTH FLOOR, PLAZA 57 7300 S.W. 57TH COURT CITY OF SOUTH MIAMI SOUTH MIAMI, FLORIDA 33143 L9:£ti:Z500VI,I,/£ `6MP'Z0W-H0IAAN33�J0\31111 HOIAAN33�JO-99L-tO\-�:I3laN`dHO\tOOZ\S1O3f'O�Icd\:d 2.4 AIR DISTRIBUTION PRODUCTS : 2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS. 2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED ON THE DRAWINGS AND SCHEDULES. 2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS. 2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS. 2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR CONDITIONING COMPRESSORS STARTING FROM THE DATE OF PROJECT ACCEPTANCE. 2.6 CONTROLS: 2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK WIRING INDICATED FOR EACH PIECE OF EQUIPMENT. 2.6.2 OFFICE AREA DX EQUIPMENT: PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT/COOL THERMOSTATS WITH ON-OFF AUTO SUB -BASE SWITCH AS FURNISHED BY THE EQUIPMENT MANUFACTURER. 2.7 STARTERS: PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST HAVE HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED/GREEN PILOT LIGHTS. PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS FOR THE INTENDED OPERATION AND INTERLOCKS. 2.8 NOT USED. 2.9 IDENTIFICATION: 2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12"x4" HIGH WITH WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE DOCUMENTS. 2.10 RETURN AIR CEILING PLENUMS: 2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS" ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A. "NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM." 2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING SPACE. SEE ARCHITECTURAL PLAN FOR COORDINATION 3.0 ,EXEQOQd 3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION do SERVICE. FOR INSTALLATION, OPERATION AND SERVICE. 3.2 NOT USED 3.3 THERMOSTAT LOCATION. THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION. INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS. RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING. 3.4 RETURN AIR FOR INDIVIDUAL ROOMS IS BEING PROVIDED AS SHOWN ON PLANS AND IS SIZED COUNTING ON A 1" UNDERCUT FOR ALL DOORS IN ADDITION TO THE REQUIRED RETURN OR TRANSFER SYSTEM. 3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION REPAIR AND/OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A/E. 3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES TO MATCH SPECIFIED FLOWS & CAPACITIES. CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS. SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE. ANTONIO FRANYIE PE #11640 MECH CHAMLER AM ASSMAT S NO. DATE VIVIANA FRANYIE PE #49185 ME AR I3„ P.A. M 0403070 e 7 LAM It. cHArrorM. Au ASL NO. iwoss SOUTH MIAMI. FLORIDA 3:1143 . ' NW 27 Street, Miami FL 33172 TEL On 6110-7.92 TEL: (305'rn 592-1360 FAX: (305) 594-9279 FAX i30�7a www, rah ieen ineers.co DESIGN I DRAWN ` JDATE G01`1F''L.ETEp AAF ` Ifi' (o -22 - 04 WWW.CHAMLERARCETrECrUPtECOM JOB NUMBER 04-1ro(o I 1 1! \ VI I �I 1 ! \ I I.n1 V I I W I• 4/ W 1 \� \-/ V� rr1 DESIGNATION AHU-4 NO QUANTITY EXI5TING SUPPLY AREA SERVED SUITE 525 ALUMINIUM MANUFACTURER TRANE CAPACITY C.F.M. FAN COIL MODEL No. - CONDENSING UNIT MODEL No. 2tt 061) - C O M B I N E D R A T I N G S TOTAL SENSIBLE CAPACITY BTU HR (00,500 - GRAND TOTAL CAPACITY BTU HR 43WO DIRECTIONAL CEILING TOTAL HEATING CAPACITY BTU/HR 25,500 - ENERGY EFFICIENCY RATIO SEER EER 12BO - COEFFICIENT OF PERFORMANCE COP - ALL ALUMINIUM FAN COIL UNIT TYPE VERTICAL T - BAR'S TOTAL AIR SUPPLY CFM IA00 30 MAX OUTSIDE AIR SUPPLY CFM 200 MANUFACTURER ENTERING AIR CONDITIONS FDB FWB 80/61 EVAPORATOR COIL MIN. ROWS MAX. F.P.I. - RH EXTERNAL STATIC PRESSURE "H20 0.5 OPPOSED BLADE REGIST. FAN SPEED RPM HIGH SPEED FIRE DAMPER FAN MOTOR HP 112 CONNECTION SIZE ELECTRICAL SERVICE AVAILABLE 1 208/1/60 RUNNING LOAD AMPS 3.1 NOTES. ELECTRIC RESISTANCE HEATER SIZE KW 1.5 2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE UNIT WEIGHT 225 SUPPLY OUTLETS MODEL - OBDC. *� C O N D E N S I N G U N I T TYPE AIR COOLED G. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS. LOCATION ROOF REFRIGERANT TYPE R-22 AMBIENT AIR TEMPERATURE FDB 135'1= NUMBER OF COMPRESSORS I NUMBER OF REFRIGERANT CIRCUITS 1 CAPACITY REDUCTION STEPS % 0-100 ELECTRICAL SERVICE AVAILABLE 208/1/60 RUNNING LOAD AMPS 24.0 MINIMUM CIRCUIT AMPS 38.0 MAXIMUM FUSE SIZE AMPS 60.0 UNIT WEIGHT 212 A C C E S S O R I E S REFRIGERANT PIPING LENGHT FT. ;�_l 60 LIQUID LINE TYPE O.D. - SUCTION LINE SIZE O.D. THERMOSTAT HEAT/COOL FILTER SECTION AND FILTER TYPE 11/2THROWAWAY SMOKE DETECTOR IN SUPPLY V I E RATI O N ISO L AT O R S FOR FAN COIL UNIT FOR CONDENSING UNIT - A U T O M A T I C C O N TR O LS TYPE - DESCRIPTION - ANTONIO FRANYIE PE #11640 MECH CHAMLER AM ASSMAT S NO. DATE VIVIANA FRANYIE PE #49185 ME AR I3„ P.A. M 0403070 e 7 LAM It. cHArrorM. Au ASL NO. iwoss SOUTH MIAMI. FLORIDA 3:1143 . ' NW 27 Street, Miami FL 33172 TEL On 6110-7.92 TEL: (305'rn 592-1360 FAX: (305) 594-9279 FAX i30�7a www, rah ieen ineers.co DESIGN I DRAWN ` JDATE G01`1F''L.ETEp AAF ` Ifi' (o -22 - 04 WWW.CHAMLERARCETrECrUPtECOM JOB NUMBER 04-1ro(o I 1 1! \ VI I �I 1 ! \ I I.n1 V I I W I• 4/ W 1 \� \-/ V� rr1 DESIGNATION YES NO Remarks USE SUPPLY RETURN CONSTRUCTION ALUMINIUM ALUMINIUM - CAPACITY C.F.M. SHOWN ON PLAN - SIZE SHOWN ON PLAN - - TYPE 24' x 24' MODULAR - COMMENTS DIRECTIONAL CEILING DIFFUSER - - SMOKE CONTROL - - FINISH ALL ALUMINIUM ALL ALUMINIUM �RCa_+ECT N0 MOUNTING TYPE t - BAR T - BAR'S r NOISE CRITERIA 30 MAX 30 MAX MANUFACTURER METALAIRE METALAIRE MODEL 5500 RH A C C E S S O R I E S OPPOSED BLADE REGIST. 015D - FIRE DAMPER - - CONNECTION SIZE SHOWN ON PLANS NOTES. 1. FINISHES AND MES OF MOUNTS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS. 2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE THICKNESS TURNING VANES AT ALL SO- SQUARE ELBOWS, OR 3 PIECE ELBOWS., 3. PROVIDE VOLUME EXTRACTORS DEHIND EACH SUPPLY OUTLET AND AT EACH DUCT` BRANCH SUPPLY OUTLETS MODEL - OBDC. *� DUCT BRANCH TAKE -OFF MODEL - AIRTROL MOD. 102 4. PROVIDE O.B. DAMPER AT ALL SUPPLY OUTLETS. 5. DUCT WORK TYPE SEE A/C NOTES.�� G. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS. 7. DIFFUSOR NECK SIZE SHOWN ON PLANS. (6x6, Rxg, 1202, OR 1505) HVAC DESIGN REQUIRES: r� 7 YES NO Remarks DUGT SMOKE DETECTOR I/ - - FIRE DAMPER($) - - - SMOKE DAMPER(S) - - - FIRE RATED ENCLOSURE - - - FIRE RATED ROOF/FLOOR CEILING ASSEMBLY - - FIRE STOPPING,; - - - SMOKE CONTROL - - - AHU-4 OFFICES Vu0;,, . ,_4 el OUTSIDE OUTSIDE AIR CALCULATIONS 5F ------ 10 PEOPLE------ 20 20 CFM/PI=R50N - -0 CFM / O/A' - --------tea ... O/A PROAL SD 200 CFM / O/A ! ' k4l s DRAWING TITLE:P It 7 I'�VIu�ION r� 7 'x6 �. �v !♦ SCHMULES s DRAWING TITLE:P It 7 I'�VIu�ION HVAC 'x6 �. !♦ SCHMULES SUITE 510 SCALE- Dt.'.E: 7-20-04 100% C.D'". ' J �RCa_+ECT N0 2004.6 r `I)RA' VING NO: oJ W n Wi•... ., W U V W i+i•y •rwo y W cW� yvWy