05-499-010AOl 'Wd
I I V r% %a I V %.J I L- 0
1.0
1.1 PROVIDE FURNISH AND INSTALL ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING
(HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS.
1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE
SMACNA, NFPA AND LOCAL ORDINANCES.
1.3 SCOPE OF WORK :
PROVIDE THE FOLLOWING COMPLETE SYSTEMS
A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM.
B. EXHAUST SYSTEM FOR TOILET ROOMS.
C. EXHAUST SYSTEMS FOR WAREHOUSE.
D. AIR CONDITIONING UNITS AND CONTROLS.
E. INDEPENDENT TEST AND BALANCE.
1.4 NOT USED
1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION
CHARGES REQUIRED
1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF
MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND FABRICATION
OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS FOR SERVICE
AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER TRADES.
1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND
TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A
COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE SPECIFICATIONS.
1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS SHOWING
DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL BEFORE
PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL INFORMATION FROM 1.6 ABOVE.
1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE
THE PURCHASE OR INSTALLATION OP EQUIPMENT AND MATERIALS.
ALL SHOP DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE
NO LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT.
1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A
A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE.
2.0 .NdM s
2.1 DUCTWORK
2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSIONS.
2.1.2 DUCTWORK MATERIALS:
A: GENERAL OFFICE AREAS:
FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER (R--6)
DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE
WITH SMACNA'S FIBROUS GLASS DUCT CONSTRUCTION STANDARDS.
DUCT JOINTS SHALL BE SEALED AND TAPED.
B: TOILET ROOM EXHAUST AND FRESH AIR INTAKES:
GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD. (0.5" W.G.)
C: EXPOSED AIR CONDITIONING DUCTWORK
SPIRAL GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD, (0,5" W.G.)
2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS.
WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS VANES.
.1 ALTERNATE A: PROVIDE 3 -PIECE ELBOWS IN LIEU
OF TURNING VANES FOR GLASS FIBER DUCTS ONLY.
.2 ALTERNATE A: PROVIDE FULL RADIOS ELBOWS IN LIEU
OF TURNING VANES.
2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY
OUTLET AND AT EACH DUCT BRANCH.
2.2 NOT USED.
2.3 NOT USED.
GREENWICH TITLE INSURANCE
OFFICE CONDO BUILDOUT
SUITE 510, FIFTH FLOOR, PLAZA 57
7300 S.W. 57TH COURT
CITY OF SOUTH MIAMI
SOUTH MIAMI, FLORIDA 33143
L9:£ti:Z500VI,I,/£ `6MP'Z0W-H0IAAN33�J0\31111 HOIAAN33�JO-99L-tO\-�:I3laN`dHO\tOOZ\S1O3f'O�Icd\:d
2.4 AIR DISTRIBUTION PRODUCTS :
2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS.
2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED
ON THE DRAWINGS AND SCHEDULES.
2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE
CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS.
2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS
BEHIND ALL AIR SUPPLY OUTLETS.
2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR CONDITIONING
COMPRESSORS STARTING FROM THE DATE OF PROJECT ACCEPTANCE.
2.6 CONTROLS:
2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION
OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK
WIRING INDICATED FOR EACH PIECE OF EQUIPMENT.
2.6.2 OFFICE AREA DX EQUIPMENT:
PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT/COOL
THERMOSTATS WITH ON-OFF AUTO SUB -BASE SWITCH AS FURNISHED
BY THE EQUIPMENT MANUFACTURER.
2.7 STARTERS:
PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION
AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST HAVE
HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED/GREEN PILOT LIGHTS.
PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS
FOR THE INTENDED OPERATION AND INTERLOCKS.
2.8 NOT USED.
2.9 IDENTIFICATION:
2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12"x4" HIGH WITH
WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE DOCUMENTS.
2.10 RETURN AIR CEILING PLENUMS:
2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS"
ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE
A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM
SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING SPACE.
SEE ARCHITECTURAL PLAN FOR COORDINATION
3.0 ,EXEQOQd
3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION
TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION do SERVICE.
FOR INSTALLATION, OPERATION AND SERVICE.
3.2 NOT USED
3.3 THERMOSTAT LOCATION.
THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION.
INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS.
RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING.
3.4 RETURN AIR FOR INDIVIDUAL ROOMS IS BEING PROVIDED AS SHOWN ON PLANS
AND IS SIZED COUNTING ON A 1" UNDERCUT FOR ALL DOORS IN ADDITION TO
THE REQUIRED RETURN OR TRANSFER SYSTEM.
3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION
REPAIR AND/OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND
TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A/E.
3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES
TO MATCH SPECIFIED FLOWS & CAPACITIES.
CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE.
ANTONIO FRANYIE
PE #11640 MECH CHAMLER AM ASSMAT S NO. DATE
VIVIANA FRANYIE
PE #49185 ME AR I3„ P.A.
M 0403070
e
7 LAM It. cHArrorM. Au ASL NO. iwoss
SOUTH MIAMI. FLORIDA 3:1143
. ' NW 27 Street, Miami FL 33172 TEL On 6110-7.92
TEL: (305'rn 592-1360 FAX: (305) 594-9279 FAX i30�7a
www, rah ieen ineers.co
DESIGN I DRAWN ` JDATE G01`1F''L.ETEp
AAF ` Ifi' (o -22 - 04 WWW.CHAMLERARCETrECrUPtECOM
JOB NUMBER 04-1ro(o
I 1 1! \ VI I �I 1 ! \ I I.n1 V I I W I• 4/ W 1 \� \-/ V� rr1
DESIGNATION
AHU-4
NO
QUANTITY
EXI5TING
SUPPLY
AREA SERVED
SUITE 525
ALUMINIUM
MANUFACTURER
TRANE
CAPACITY C.F.M.
FAN COIL MODEL No.
-
CONDENSING UNIT MODEL No.
2tt 061)
-
C O M B I N E D R A T I N G S
TOTAL SENSIBLE CAPACITY BTU HR
(00,500
-
GRAND TOTAL CAPACITY BTU HR
43WO
DIRECTIONAL CEILING
TOTAL HEATING CAPACITY BTU/HR
25,500
-
ENERGY EFFICIENCY RATIO SEER EER
12BO
-
COEFFICIENT OF PERFORMANCE COP
-
ALL ALUMINIUM
FAN COIL UNIT
TYPE
VERTICAL
T - BAR'S
TOTAL AIR SUPPLY CFM
IA00
30 MAX
OUTSIDE AIR SUPPLY CFM
200
MANUFACTURER
ENTERING AIR CONDITIONS FDB FWB
80/61
EVAPORATOR COIL MIN. ROWS MAX. F.P.I.
-
RH
EXTERNAL STATIC PRESSURE "H20
0.5
OPPOSED BLADE REGIST.
FAN SPEED RPM
HIGH SPEED
FIRE DAMPER
FAN MOTOR HP
112
CONNECTION SIZE
ELECTRICAL SERVICE AVAILABLE 1
208/1/60
RUNNING LOAD AMPS
3.1
NOTES.
ELECTRIC RESISTANCE HEATER SIZE KW
1.5
2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE
UNIT WEIGHT
225
SUPPLY OUTLETS MODEL - OBDC. *�
C O N D E N S I N G U N I T
TYPE
AIR COOLED
G. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS.
LOCATION
ROOF
REFRIGERANT TYPE
R-22
AMBIENT AIR TEMPERATURE FDB
135'1=
NUMBER OF COMPRESSORS
I
NUMBER OF REFRIGERANT CIRCUITS
1
CAPACITY REDUCTION STEPS %
0-100
ELECTRICAL SERVICE AVAILABLE
208/1/60
RUNNING LOAD AMPS
24.0
MINIMUM CIRCUIT AMPS
38.0
MAXIMUM FUSE SIZE AMPS
60.0
UNIT WEIGHT
212
A C C E S S O R I E S
REFRIGERANT PIPING LENGHT FT.
;�_l 60
LIQUID LINE TYPE O.D.
-
SUCTION LINE SIZE O.D.
THERMOSTAT
HEAT/COOL
FILTER SECTION AND FILTER TYPE
11/2THROWAWAY
SMOKE DETECTOR
IN SUPPLY
V I E RATI O N ISO L AT O R S
FOR FAN COIL UNIT
FOR CONDENSING UNIT
-
A U T O M A T I C C O N TR O LS
TYPE
-
DESCRIPTION
-
ANTONIO FRANYIE
PE #11640 MECH CHAMLER AM ASSMAT S NO. DATE
VIVIANA FRANYIE
PE #49185 ME AR I3„ P.A.
M 0403070
e
7 LAM It. cHArrorM. Au ASL NO. iwoss
SOUTH MIAMI. FLORIDA 3:1143
. ' NW 27 Street, Miami FL 33172 TEL On 6110-7.92
TEL: (305'rn 592-1360 FAX: (305) 594-9279 FAX i30�7a
www, rah ieen ineers.co
DESIGN I DRAWN ` JDATE G01`1F''L.ETEp
AAF ` Ifi' (o -22 - 04 WWW.CHAMLERARCETrECrUPtECOM
JOB NUMBER 04-1ro(o
I 1 1! \ VI I �I 1 ! \ I I.n1 V I I W I• 4/ W 1 \� \-/ V� rr1
DESIGNATION
YES
NO
Remarks
USE
SUPPLY
RETURN
CONSTRUCTION
ALUMINIUM
ALUMINIUM
-
CAPACITY C.F.M.
SHOWN ON PLAN
-
SIZE
SHOWN ON PLAN
-
-
TYPE
24' x 24' MODULAR
-
COMMENTS
DIRECTIONAL CEILING
DIFFUSER
-
-
SMOKE CONTROL
-
-
FINISH
ALL ALUMINIUM
ALL ALUMINIUM
�RCa_+ECT N0
MOUNTING TYPE
t - BAR
T - BAR'S
r
NOISE CRITERIA
30 MAX
30 MAX
MANUFACTURER
METALAIRE
METALAIRE
MODEL
5500
RH
A C C E S S O R I E S
OPPOSED BLADE REGIST.
015D -
FIRE DAMPER
- -
CONNECTION SIZE
SHOWN ON PLANS
NOTES.
1. FINISHES AND MES OF MOUNTS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS.
2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE
THICKNESS TURNING VANES AT ALL SO- SQUARE ELBOWS, OR 3 PIECE ELBOWS.,
3. PROVIDE VOLUME EXTRACTORS DEHIND EACH SUPPLY OUTLET AND AT EACH DUCT` BRANCH
SUPPLY OUTLETS MODEL - OBDC. *�
DUCT BRANCH TAKE -OFF MODEL - AIRTROL MOD. 102
4. PROVIDE O.B. DAMPER AT ALL SUPPLY OUTLETS.
5. DUCT WORK TYPE SEE A/C NOTES.��
G. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS.
7. DIFFUSOR NECK SIZE SHOWN ON PLANS. (6x6, Rxg, 1202, OR 1505)
HVAC DESIGN REQUIRES:
r� 7
YES
NO
Remarks
DUGT SMOKE DETECTOR
I/
-
-
FIRE DAMPER($)
-
-
-
SMOKE DAMPER(S)
-
-
-
FIRE RATED ENCLOSURE
-
-
-
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
-
-
FIRE STOPPING,;
-
-
-
SMOKE CONTROL
-
-
-
AHU-4
OFFICES
Vu0;,,
.
,_4
el
OUTSIDE
OUTSIDE AIR CALCULATIONS
5F ------ 10 PEOPLE------ 20
20 CFM/PI=R50N - -0 CFM / O/A'
- --------tea ...
O/A PROAL SD 200 CFM / O/A ! '
k4l
s
DRAWING TITLE:P It
7
I'�VIu�ION
r� 7
'x6 �.
�v
!♦
SCHMULES
s
DRAWING TITLE:P It
7
I'�VIu�ION
HVAC
'x6 �.
!♦
SCHMULES
SUITE
510
SCALE-
Dt.'.E:
7-20-04 100%
C.D'".
' J
�RCa_+ECT N0
2004.6
r
`I)RA' VING NO:
oJ W
n
Wi•... ., W U V W
i+i•y •rwo y W cW�
yvWy