12-224-023ELECTRICAL LOAD CALCULATION
A.- GENERAL LIGHTING LOAD
3,348 S.F. 6 3W/6F = 10,044 WATTS
B.- (2) SMALL APLIANCE CIRCUITS X 1,500 = 3,000 WATTS
C.- FIXED APPLIANCES: RANGE ---------------- 12,000
REFRIGERATOR------------ 1,000
DISHWASHER --------------- 800
WASHER ------------------- 1,500
DRYER -------------------- 5,000
INSTANT W/H----------- 12,000
DOOR OPENER'S ----------- 800
HOOD --------------------- 600
MICROWAVE ----------------600
JACUZZI ------------------- 1,500
CONNECTED LOAD LESS A/C = 48,844 WATTS
10,000 WO 100 %a = 10,000 WATTS
REST W 6.40 % = 15,538 WATTS
(A/C (OR HEATING) 6 100 51- = 20000 WATTS
DEMAND LOAD = 45,538 / 240 WATTS = 189.14 AMPS 240/120 V.
SERVICE SIZE = 200 AMPS.
C.- NEUTRAL LOAD
LIGHTING, SMALL APPLIANCE 4 WASHER 14,544 WATTS
FIRST 3,000 W 0 100 qo 3,000 WATTS
REST W635% = 4,040 WATTS
RANGE X -10 %o = 5,600 WATTS
DRYER X -10 %o = 3,500 WATTS
REFRIGERATOR = 1,000 WATTS
DISHWASHER = 1,000 WATTS
TOTAL NEUTRAL WATTS = 18,140 WATTS = -15.56 AMPS.
ELECTRICAL NOTES
1. CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND
EQUIPMENT FOR COMPLETE ELECTRICAL INSTALLATION IN
ACCORDANCE WITH THESE DRAWINGS.
2, COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE
3. PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM.
4, OBTAIN ALL PERMITS FOR WORK UNDER TH15 CONTACT.
5. PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY
OTHER TRADES.
6. NO APPLIANCES OUTLES SHALL BE INSTALLED BELOW BASE FLOOD ELEV-
-1. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING
ARCHITECTURAL FI=ATURES.
8. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF
WITH ALL EXISTING CONDITIONS.
9, A/C COMPRESSOR SHALL BE INSTALLED ABOVE BASE FLOOD ELEV..
10. OUTDOOR CONDUITS SHALL BE SCHEDULE 40 PVC.
MINIMUM COVER SHALL BE 24'.
11. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR.
12. ELECTRICAL OUTLETS BELOW BASE ELEV. SHALL BE INSTALLED AT THE
HIGHEST PERMITTED ELEV AND SHALL BE INSTALLED (SEPARATE) A5
INDEPEND,ANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS.
13. MAIN CIRCUIT BRK PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV.
14. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT METER TO
COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS.
15. ALL OUTLETS AND SWITCHES WILL BE DECORA TYPE
16. ELECTRICAL CONTRACTOR TO CLEAN UP TO MAINTAIN JOB SITE CLEAN
REGARLESS HIS JOB,
ELECTRICAL NOTES.
1) ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING)
BELOW BASE ELEVATION SHALL BE INSTAL! QED AT THE HIGHEST
PERMITTED ELEVATION AND 514ALL BE INSTALLED (SEPARATE) AS
INDEPENDANT CIRCUITS FROM TH05E IN THE HABITABLE AREAS.
2) NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED
BELLOW BASE FLOOD ELEVATION.
3) A/C COMPRESSORS SHALL BE INSTALLED ABOVE BASE FLOOD
ELEVATION.
4) MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE
FLOOD ELEVATION.
5) IT REQUIRED THAT YOU CONFER WITH FLORIDA POWER 4 LIGHT TO
LOCATED THE ELECTRICAL METER TO COMPLY WITH FEDERAL
EMERGENCY MANAGEMENT AGENCY REQUIREMENTS.
2 1n.
MIN.
SMOKE DETECTOR NOTE:
1) SMOKE DETECTOR SYSTEM TO BE INSTALLED IN ACCORDANCE W/NFPA
'12/99
2) SMOKE DETECTOR SHALL BE NOT BE CLOSER THAN 3' FROM AIR
REGISTER 4 BATH DOOR AND 20' FROM COOKING APPLIANCES
GROUNDING
ELECTRODE
CONDUCTOR
GROUNDING
ELECTRODE
BOLTED -TYPE
CONNECTION DEVICE
OR EXOTHERMIC WELD.
NONMETALLIC
PROTECTIVE
SLEEVE.
SERVICE BY -
POWER COMP.
ELECTRICAL METE
TYPE
SERVICE
VOLTAGE
MOUNTING
: SQUARE 'D' or APPROVED EQUAL
RESIDENCE�I
: 240/120 V 1+ - 3W.
SURFACE
PANEL
NEMA 3R
MAIN BUS
NEUTRAL
MAINS
AIC
200 AMPS
200 AMPS
200 AMPS
10,000 AMPS
AMPS
TOTAL COND
POLI= WIRE
REMARKS
CKT.
CKT.
REMARKS
WIRE
CON
TOTAL
AMPS
0
VA.
SIZE+
NO.
NO.
ce
W
51ZE+
VA.OLES
J
60
2 10000
1' 6
A/C AHU-1
1
2
U - 2
10
3/4'
5,000 2
30
V
Z
3
4
0■
W
30
2 5000
3/4' 10
DRYER
5
v
1 GU -1
10
3/4'
5,000 2
30
7
a
50
2 12000
1' 6
RANGE
9
10
REFRIGERATOR
12
1/2'
1000 1
20
ti
11
12
A/C AHU. - 2
6
1'
10000 2
60
20
1 1500
1/2' 12
WASHER
13
14
20
1 1500
1/2' 12
SMALL APDL.
15
16A
GFI RECP. OUTSIDE
12
1/2'
600 1
20
165
GFI RECD. OUTSIDE
12
1/2'
600 1
20
20
1 1500
1/2" 1 12
SMALL APPL.
1-T
IS
D1514111ASHER
12
1/2'
800 1
20
SPACE
IS
20
HOOD
12
1/2'
600 1
20
SPACE
21
22
MICROWAVE
12
1/2'
600 1
20
20
1 800
1/2' 12
DOORS OPENER
23
24
JACUZZI
12
1/2'
1500 1
20
20
1 600
1/2' 12
C:-1 RECD. BATH
25
26
GPI RECD. BATH
12
1/2'
600 1
20
60
2 12ADOO
I" 6
INSTANT W/H
21
28
LTS 4 REC.
14
1/2'
600 1
15
2e
30
15
1 600
1/2' 14
LTS 4 REC.
31
32
33
34
35
36
31
38
39
40
SPACE
41
42
SPACE
DEMAND LOAD. 45,858 WATTS/240 = 191.01 AMPS
FEEDER 3 M 3/0 THWN
- 2' COND.
FED FROM : SERVICE.
SERVICE BY -
POWER COMP.
ELECTRICAL METE
O
200 AMP
ELECT PANEL
�— 30 3/0 THWN
IN 2' COND
GROUND - 1 0 4 CU (GRD PER NEC.)
PROVIDE TWO 5/8'X10' COPPER CLAD
GROUNDING ROD TO A 3/4' COPPER
WATER PIPE STUB -OUT
ELECTRICAL RISER DIAGRAM
ELECT. LEGEND
Wall Switch 15 A, 125 V
Duplex receptacle 15 A 125 V
Duplex Receptacle 15 A 125 V Switched
o Incandescent Lightine Fixture
a Wa I I Sra cket Light
U Junction Sox
PH D Phone Outlet
-7 TV T.V. Outlet
® Electrical Panel
'-❑ Disconnectince Switch
SD Smoke Detector
E[ Electrical Meter
(f) Future Pan Fan Outlet
CONNECT TOA CONCRETE -ENCASED
ELECTRODE CON515TING OF AT LEAST
20 FT OF ONE OR MORE BARE OR ZINC
GALVANIZED STEEL REINFORCING BARS
OF NOT LESS THAN 1/2 INCH OR CONSISTING
OF AT LEAST 20 FT. OF BARE COPPER
CONDUCTOR NOT SMALLER THAN No. 4 AND
LOCATED WITHIN AND NEAR THE BOTTOM
OF A CONCRETE FOUNDATION OR FOOTING
THAT IS IN DIRECT CONTACT WITH EARTH.
ENC:45ED GROUNDING ELECTfRODE DETAIL nts
LOT 17
3* 3/0 THWN
IN 2' COND
a
200A.
D I SC. BRK.
NEMA 3R
O
200 AMP
ELECT PANEL
�— 30 3/0 THWN
IN 2' COND
GROUND - 1 0 4 CU (GRD PER NEC.)
PROVIDE TWO 5/8'X10' COPPER CLAD
GROUNDING ROD TO A 3/4' COPPER
WATER PIPE STUB -OUT
ELECTRICAL RISER DIAGRAM
ELECT. LEGEND
Wall Switch 15 A, 125 V
Duplex receptacle 15 A 125 V
Duplex Receptacle 15 A 125 V Switched
o Incandescent Lightine Fixture
a Wa I I Sra cket Light
U Junction Sox
PH D Phone Outlet
-7 TV T.V. Outlet
® Electrical Panel
'-❑ Disconnectince Switch
SD Smoke Detector
E[ Electrical Meter
(f) Future Pan Fan Outlet
CONNECT TOA CONCRETE -ENCASED
ELECTRODE CON515TING OF AT LEAST
20 FT OF ONE OR MORE BARE OR ZINC
GALVANIZED STEEL REINFORCING BARS
OF NOT LESS THAN 1/2 INCH OR CONSISTING
OF AT LEAST 20 FT. OF BARE COPPER
CONDUCTOR NOT SMALLER THAN No. 4 AND
LOCATED WITHIN AND NEAR THE BOTTOM
OF A CONCRETE FOUNDATION OR FOOTING
THAT IS IN DIRECT CONTACT WITH EARTH.
ENC:45ED GROUNDING ELECTfRODE DETAIL nts
LOT 17
REVIRON$
L-
2.-
I-
4,-
i-
6. -
DME FEBRUARY, 2012
9CAL$ 5HOWN
DRAW. M. CASTELLON
DEWN BY' JR
JOB NO
E-2
L
NE
ME
LL
<
2
LL
z
Ql
Uj
0
Oi12
0
MIME
UjH
Ift
ce
W
Z
4
J
0
�
U
a
z
LU
Q
J
V
Z
0
0■
W
Z
o�
�
v
to
REVIRON$
L-
2.-
I-
4,-
i-
6. -
DME FEBRUARY, 2012
9CAL$ 5HOWN
DRAW. M. CASTELLON
DEWN BY' JR
JOB NO
E-2
NE
ME
LL
J
LU
LL
z
Uj
0
MIME
UjH
Ift
ce
W
J
0
�
U
a
z
LU
Q
J
V
Z
0
0■
W
Z
o�
to
REVIRON$
L-
2.-
I-
4,-
i-
6. -
DME FEBRUARY, 2012
9CAL$ 5HOWN
DRAW. M. CASTELLON
DEWN BY' JR
JOB NO
E-2