12-224-023ELECTRICAL LOAD CALCULATION A.- GENERAL LIGHTING LOAD 3,348 S.F. 6 3W/6F = 10,044 WATTS B.- (2) SMALL APLIANCE CIRCUITS X 1,500 = 3,000 WATTS C.- FIXED APPLIANCES: RANGE ---------------- 12,000 REFRIGERATOR------------ 1,000 DISHWASHER --------------- 800 WASHER ------------------- 1,500 DRYER -------------------- 5,000 INSTANT W/H----------- 12,000 DOOR OPENER'S ----------- 800 HOOD --------------------- 600 MICROWAVE ----------------600 JACUZZI ------------------- 1,500 CONNECTED LOAD LESS A/C = 48,844 WATTS 10,000 WO 100 %a = 10,000 WATTS REST W 6.40 % = 15,538 WATTS (A/C (OR HEATING) 6 100 51- = 20000 WATTS DEMAND LOAD = 45,538 / 240 WATTS = 189.14 AMPS 240/120 V. SERVICE SIZE = 200 AMPS. C.- NEUTRAL LOAD LIGHTING, SMALL APPLIANCE 4 WASHER 14,544 WATTS FIRST 3,000 W 0 100 qo 3,000 WATTS REST W635% = 4,040 WATTS RANGE X -10 %o = 5,600 WATTS DRYER X -10 %o = 3,500 WATTS REFRIGERATOR = 1,000 WATTS DISHWASHER = 1,000 WATTS TOTAL NEUTRAL WATTS = 18,140 WATTS = -15.56 AMPS. ELECTRICAL NOTES 1. CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT FOR COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS. 2, COMPLY WITH THE NEC. AND THE FLORIDA BUILDING CODE 3. PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM. 4, OBTAIN ALL PERMITS FOR WORK UNDER TH15 CONTACT. 5. PROVIDE TEMPORARY POWER AND LIGHT OUTLETS FOR USE BY OTHER TRADES. 6. NO APPLIANCES OUTLES SHALL BE INSTALLED BELOW BASE FLOOD ELEV- -1. COORDINATE ALL OUTLET LOCATIONS WITH BUILDING ARCHITECTURAL FI=ATURES. 8. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS. 9, A/C COMPRESSOR SHALL BE INSTALLED ABOVE BASE FLOOD ELEV.. 10. OUTDOOR CONDUITS SHALL BE SCHEDULE 40 PVC. MINIMUM COVER SHALL BE 24'. 11. ALL MOUNTING HARDWARE SHALL BE BY CONTRACTOR. 12. ELECTRICAL OUTLETS BELOW BASE ELEV. SHALL BE INSTALLED AT THE HIGHEST PERMITTED ELEV AND SHALL BE INSTALLED (SEPARATE) A5 INDEPEND,ANT CIRCUITS FROM THOSE IN THE HABITABLE AREAS. 13. MAIN CIRCUIT BRK PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEV. 14. IT IS REQUIRED THAT CONFER WITH F.P.L. TO LOCATED THE ELECT METER TO COMPLY W/ FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 15. ALL OUTLETS AND SWITCHES WILL BE DECORA TYPE 16. ELECTRICAL CONTRACTOR TO CLEAN UP TO MAINTAIN JOB SITE CLEAN REGARLESS HIS JOB, ELECTRICAL NOTES. 1) ELECTRICAL OUTLETS (RECEPTACLES AND LIGHTING) BELOW BASE ELEVATION SHALL BE INSTAL! QED AT THE HIGHEST PERMITTED ELEVATION AND 514ALL BE INSTALLED (SEPARATE) AS INDEPENDANT CIRCUITS FROM TH05E IN THE HABITABLE AREAS. 2) NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED BELLOW BASE FLOOD ELEVATION. 3) A/C COMPRESSORS SHALL BE INSTALLED ABOVE BASE FLOOD ELEVATION. 4) MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE FLOOD ELEVATION. 5) IT REQUIRED THAT YOU CONFER WITH FLORIDA POWER 4 LIGHT TO LOCATED THE ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY MANAGEMENT AGENCY REQUIREMENTS. 2 1n. MIN. SMOKE DETECTOR NOTE: 1) SMOKE DETECTOR SYSTEM TO BE INSTALLED IN ACCORDANCE W/NFPA '12/99 2) SMOKE DETECTOR SHALL BE NOT BE CLOSER THAN 3' FROM AIR REGISTER 4 BATH DOOR AND 20' FROM COOKING APPLIANCES GROUNDING ELECTRODE CONDUCTOR GROUNDING ELECTRODE BOLTED -TYPE CONNECTION DEVICE OR EXOTHERMIC WELD. NONMETALLIC PROTECTIVE SLEEVE. SERVICE BY - POWER COMP. ELECTRICAL METE TYPE SERVICE VOLTAGE MOUNTING : SQUARE 'D' or APPROVED EQUAL RESIDENCE�I : 240/120 V 1+ - 3W. SURFACE PANEL NEMA 3R MAIN BUS NEUTRAL MAINS AIC 200 AMPS 200 AMPS 200 AMPS 10,000 AMPS AMPS TOTAL COND POLI= WIRE REMARKS CKT. CKT. REMARKS WIRE CON TOTAL AMPS 0 VA. SIZE+ NO. NO. ce W 51ZE+ VA.OLES J 60 2 10000 1' 6 A/C AHU-1 1 2 U - 2 10 3/4' 5,000 2 30 V Z 3 4 0■ W 30 2 5000 3/4' 10 DRYER 5 v 1 GU -1 10 3/4' 5,000 2 30 7 a 50 2 12000 1' 6 RANGE 9 10 REFRIGERATOR 12 1/2' 1000 1 20 ti 11 12 A/C AHU. - 2 6 1' 10000 2 60 20 1 1500 1/2' 12 WASHER 13 14 20 1 1500 1/2' 12 SMALL APDL. 15 16A GFI RECP. OUTSIDE 12 1/2' 600 1 20 165 GFI RECD. OUTSIDE 12 1/2' 600 1 20 20 1 1500 1/2" 1 12 SMALL APPL. 1-T IS D1514111ASHER 12 1/2' 800 1 20 SPACE IS 20 HOOD 12 1/2' 600 1 20 SPACE 21 22 MICROWAVE 12 1/2' 600 1 20 20 1 800 1/2' 12 DOORS OPENER 23 24 JACUZZI 12 1/2' 1500 1 20 20 1 600 1/2' 12 C:-1 RECD. BATH 25 26 GPI RECD. BATH 12 1/2' 600 1 20 60 2 12ADOO I" 6 INSTANT W/H 21 28 LTS 4 REC. 14 1/2' 600 1 15 2e 30 15 1 600 1/2' 14 LTS 4 REC. 31 32 33 34 35 36 31 38 39 40 SPACE 41 42 SPACE DEMAND LOAD. 45,858 WATTS/240 = 191.01 AMPS FEEDER 3 M 3/0 THWN - 2' COND. FED FROM : SERVICE. SERVICE BY - POWER COMP. ELECTRICAL METE O 200 AMP ELECT PANEL �— 30 3/0 THWN IN 2' COND GROUND - 1 0 4 CU (GRD PER NEC.) PROVIDE TWO 5/8'X10' COPPER CLAD GROUNDING ROD TO A 3/4' COPPER WATER PIPE STUB -OUT ELECTRICAL RISER DIAGRAM ELECT. LEGEND Wall Switch 15 A, 125 V Duplex receptacle 15 A 125 V Duplex Receptacle 15 A 125 V Switched o Incandescent Lightine Fixture a Wa I I Sra cket Light U Junction Sox PH D Phone Outlet -7 TV T.V. Outlet ® Electrical Panel '-❑ Disconnectince Switch SD Smoke Detector E[ Electrical Meter (f) Future Pan Fan Outlet CONNECT TOA CONCRETE -ENCASED ELECTRODE CON515TING OF AT LEAST 20 FT OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 1/2 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. ENC:45ED GROUNDING ELECTfRODE DETAIL nts LOT 17 3* 3/0 THWN IN 2' COND a 200A. D I SC. BRK. NEMA 3R O 200 AMP ELECT PANEL �— 30 3/0 THWN IN 2' COND GROUND - 1 0 4 CU (GRD PER NEC.) PROVIDE TWO 5/8'X10' COPPER CLAD GROUNDING ROD TO A 3/4' COPPER WATER PIPE STUB -OUT ELECTRICAL RISER DIAGRAM ELECT. LEGEND Wall Switch 15 A, 125 V Duplex receptacle 15 A 125 V Duplex Receptacle 15 A 125 V Switched o Incandescent Lightine Fixture a Wa I I Sra cket Light U Junction Sox PH D Phone Outlet -7 TV T.V. Outlet ® Electrical Panel '-❑ Disconnectince Switch SD Smoke Detector E[ Electrical Meter (f) Future Pan Fan Outlet CONNECT TOA CONCRETE -ENCASED ELECTRODE CON515TING OF AT LEAST 20 FT OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 1/2 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. ENC:45ED GROUNDING ELECTfRODE DETAIL nts LOT 17 REVIRON$ L- 2.- I- 4,- i- 6. - DME FEBRUARY, 2012 9CAL$ 5HOWN DRAW. M. CASTELLON DEWN BY' JR JOB NO E-2 L NE ME LL < 2 LL z Ql Uj 0 Oi12 0 MIME UjH Ift ce W Z 4 J 0 � U a z LU Q J V Z 0 0■ W Z o� � v to REVIRON$ L- 2.- I- 4,- i- 6. - DME FEBRUARY, 2012 9CAL$ 5HOWN DRAW. M. CASTELLON DEWN BY' JR JOB NO E-2 NE ME LL J LU LL z Uj 0 MIME UjH Ift ce W J 0 � U a z LU Q J V Z 0 0■ W Z o� to REVIRON$ L- 2.- I- 4,- i- 6. - DME FEBRUARY, 2012 9CAL$ 5HOWN DRAW. M. CASTELLON DEWN BY' JR JOB NO E-2