05-1438-013FIRE SPRINKLER NOTES: GENERAL: A) THE FIRE SPRINKLER SYSTEM FOR THIS PROJECT 15 TO BE PROCURED ON A DESIGN BUILD BASIS WITH THE SPRINKLER CONTRACTOR FULLY RESPONSIBLE FOR THE DETAILED DESIGN OF AND SHALL CONFORM TO LOCAL CODE, DEVELOPER, INSURANCE UNDERWRITER, AND ALL PERTINENT STANDARDS OF NFPA. B) ORDER NEW WATER FLOW TEST FROM THE FIRE DEPARTMENT TO USE AS BASIS FOR DESIGN. C) COORDINATE WITH ALL OTHER TRADES BEFORE PREPARATION OF DESIGN DOCUMENTS. FOR SUBMITTAL AND PERMIT PURPOSES. U THE PROPOSED BUILDING SHALL BE FULLY SPRINKLERED IN COMPLIANCE WITH THE FOLLOWING: a, LOCAL AUTHORITY HAYING JURISDICTION. b. NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS c. NFPA 14 - NOT USED d. NFPA 20 - NOT USED e. NFPA 24 - PRIVATE FIRE SERVICE MAINS F. NFPA 101- LIFE SAFETY CODE g. THE FLORIDA BUILDING CODE - 2000 h, THE FLORIDA FIRE PREVENTION CODE 1. ALL OTHER APPLICABLE CODES AND STANDARDS. 2) PROVIDE A WET PIPE SPRINKLER SYSTEM, ALTERNATIVELY FED FROM THE FIRE 5TANDPIPE6 AND PUMP SYSTEM. 3) PREPARE FULLY DIMENSIONED AND COORDINATED SPRINKLER AND FIRE STANDPIPE SHOP DRAWINGS IN ACCORDANCE WITH THE REQUIREMENT OF THIS BUILDING AND ALL APPLICABLE CODES AND STANDARDS. SHOP DRAWINGS SHALL BE PREPARED BY A LICENSED SPRINKLER CONTRACTOR AND SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, TOGETHER WITH THE HYDRAULIC CALCULATIONS. 4) SPRINKLER SYSTEM LAYOUT, AND HYDRAULIC CALCULATIONS SHALL BE PREPARED IN ACCORDANCE WITH THE FOLLOWING NFPA 13 HAZARD CLASSIFICATIONS: a. CORRIDORS t TOILET AREAS - ORDINARY HAZARD GROUP 2,(1-4.1.2) b. OFFICE SPACES - LIGHT HAZARD (1-4.1.2) c. LOBBY AREAS - ORDINARY HAZARD (1-1.3.1) d) ALL EXPOSED PIPING SHALL BE $CH. 40 -GALVANIZED STEELSTEEL. e) PROVIDE CORROSION RESISTANCE TREATMENT TO SPRINKLER HEADS EXPOSED TO WEATHER ALL NON AIR CONDITIONED AREAS ARE TO BE CONSIDERED EXPOSED TO WEATHER 50 PIPING SHALL BE IN ACCORDANCE WITH SECTION 2-3, NFPA 13, 1999 EDITION. AND A5 FOLLOWS. a) GENERAL DISTRIBUTION -5CH. 40 -BLACK STEEL. W/THREADED JOINTS. b) UNDERGROUND SERVICE PIPE FROM MAIN TO RISER-4' D.I.P. c) RISER - SCR 10 - 4' BLACK STEEL W/ VICTAULIC FITTINGS. GENERAL DISTRIBUTION - d) FIRE SPRINKLER CONTROL VALVES TO BE OF THE PRE55URE RESTRICTIVE TYPE WHERE PRESSURE EXCEEDS 115 P.S.I.G. (o) INSTALL HANGERS IN ACCORDANCE WITH CHAPTER (o, NFPA 13, 1999 EDITION. HANGER TO BE MANUFATURED BY ERICO CO. 1) PROTECT ELEVATORS IN ACCORDANCE WITH STATE FIRE MARSHALL'S UNIFORM SAFETY RULES, CHAPTER 4A-41. ELECTRICAL AND ELEVATOR CONTRACTORS MUST COMPLY WITH THESE REQUIREMENTS. 6) PROVIDE SPARE SPRINKLER CABINET IN ACCORD WITH NFPA 13 PROVIDE A MINIMUM OF 6 SPARE HEADS OF EACH TYPE, SIZE AND RATING USED. (NOT LESS THAN 24 TOTAL) LOCATE CABINETLIN APPROVED LOCATION. THE CABINET. 9) INSTALL FIRE SPRINKLER HEADS IN THE CENTER OF THE CEILING TILES. 10) THE INSTALLATION OF H.V.A.C. AND PLUMBING HAS PRECEDENCE OVER FIRE PROTECTION. THE FIRE SPRINKLER CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO ALLOW ALL DUCTWORK TO BE INSTALLED AS HIGH A5 P0551BLE. II) COORDINATE WITH ELECTRICAL CONTRACTOR FOR ANY CONFLICTS OF SPRINKLER HEADS AND LIGHT FIXTURES, SEE ELECTRICAL PLANS PHILLIPS CONCRETE FASTENER OR EQUAL .... _.__... r r r r r , r r r r r r r r r r r r m MINIMUM D.IST f CE _ V CONCRETE J = CONSTRUCTION Q ALL THREAD ROD - 0 SWIVEL RING SWIVEL RING TAKE-OUT U ' PIPE HANGER DETAIL - DROP -IN ANCHOR N.T.S. PIPE ROD TYPE OF MIN "C" MAX "D" SIZE SIZE FASTENER DIM. DIM. 3/4 , 1/2' 1 5/a , 1 5/ ' 1 3/4' 3 / � a 1-3/a' x 1 11/32' DROP -IN ANCHOR I " 1/ 4 13/16' 1 a 11/2" 15/1&' 2' 2" 1 3/16' 2 3/a" 21/2" 1/ , 1-1i2' x 1 15/32' 1 1/16' 2 3,41 3" 1 3/ " 4 3 i/ 4 2 DROP -IN ANCHOR 31/2' 2' 3 5/8" 4' 5/a 1-5/a' x 2 15/32' DROP -IN ANCHOR 2 1/4 1 3" 5° 2 3/4' 4 3/4' 0 3/4' 1-3/41X3 1/4' DROP -IN ANCH. 3 5/16' 5 1/2' 0 N/A N/A N/A N/A 24" MAX. ARM OVER- LENTH PER NFPA 13 1996 4-14.2.3.4 NEW 1" TEE (M 24" MAX. ARM OVER LENTH PER NFPA 13 1996 4-14.2.3.4 (TYPICAL) I PLAN KEYED NOTES 1J CONNECT NEW SEMIRECESSED SPRINKLER DEAD TO EXISTING FIRE PROTECTION WATER PIPE SYSTEM. FIRE SPRINKLER LEGEND: 2' aSBUIELRTB AIN A5 PER EREFERET. NECED r-----� NEW FIRE SPRINKLER BRANCH ON DENOTES NEW PENDANT SPRINKLER HEAD LOCATE IN CENTER OF TILE (C'� At DENOTES RELOC ED PENDANT HEAD LOCATE R At CENTER OF TILE. ROVIDE IN DROP MIN. 0 DENOTES EXIST. PENDANT TO REMAIN TOTAL NO. OF HEADS NEW RELOCATED REMAIN REMOVED PENDANTS ,• „ „ ,• TOTAL NO. OF HEADS AVERAGE COVERAGE PROVIDED 11�� FT. PER HEAD mIGINAaDr:slwCRIT��I� 1. HYDRAULIC DESIGN CRITERIA: C. OFFICES 4 GENERAL CORRIDOR 4 TOILET AREAS NFPA HAZARD CLASSIFICATION---- OH - 2 DESIGN AREA OF APPLICATION---- 1,500 SF. DESIGN DENSITY ---------------- 0.10 GPM/5F DESIGN COVERAGE PER HEAD---- 130 SF. MAXIMUM. MAXIMUM HEAD SPACING --------- 15 FT, SIR SPRINKLER LEGEND OFFICES AREAS COMMON AREAS, OFFICES, ETC. UPRIGHT OR PENDANT SPRINKLER HEAD. CENTRAL MODEL TY-B (QUICK RESPONSE) 165'F - K=5.6 1/2' ORIFICE. PROVIDE CLEVIS TYPE HANGER APPROVED BY UPRIGHT OR PENDANT SPRINKLER HEAD. FIRE SPRINKLER CONSTRUCTION NOTES CONTRACTOR SHALL NOTIFY MDAD I WORKING DAYS BEFORE A SHUT DOWN WILL OCCUR FOR INSTALLATION OF NEW HEADS OR LINES. NEW 1 1/4" TEE. (MIN) 1" DROP I 1" DROP I 1" DROP EXISTIN EXISTING SPRINKLER SPRINKLER SUPPLY SUPPLY BRANCH BRANCH I CEILING CEILING NEW SEMI -RECESSED PENDANT SPRINKLER HEAD CENTERED IN CEILING TILE ANEW SEMI -RECESSED PENDANT SPRINKLER HEAD CENTERED IN CEILING TILE NEW HEAD INSTALLATION DETAIL NO SCALE OFFICES FOR HANZMA + CRID N, P,A, OFFICE CONDO BUILDOUT SUITE 515, FIFTH FLOOR, PLAZA 57 7301 S.W. 57TH COURT CITY OF SOUTH MIAMI SOUTH MIAMI, FLORIDA 33143 .ej Ee I- 1 ­ L __, �_}1 I_d _.� f� PARTNER'S lk ID t 4 13 t I —gypMN-- i -- -� PARiNF�R'S-T ?._ _, - 1.-T--- E r T_ PliNTR - --- N sT e 5 I. f j ! 1 l_ _1L___I • L--_- _-- EEXISTINGFIRE N-, . 8PRINKLER LAYOUT. _�� M .� SEE SHELL PERMIT SET I_ _ .... --- _77 11 — PdRA 1 — --�— F-1 L L La - - _ J � N r{ � STAIR N0.1 I- L RO�IOt" 1J it y ' 1 4 I o FIRE PROTECTION OFFICE SCALE- Q I I IT LEVEL BUILDING PLAN SCALE: 1' 330'-0' ANT'ONiO F'RANY'E WWQ TITLE' PE 1t > o , ; GN CHANDLER AND ASSOCIATES NO. DATE REIII,SiON No. DATE REVISION DFiA ,; Fa, CHAND i ,, }}, ME ARCPA FIRE PROTECTION AA OOOM PARnAL OFFICE, PLAN JASON P.CHAAIDLPdt. A.TA A& Na 16065 ,. r A '1 " Certificate of € ��\� , A / ° su 1 1.. V 15 Authorization # 00002906 SOUTH MIAMI FLORMA 33143 J "� •; q0 ® .. tJ _ � EC T NO, 20051 _ TEL: (306}5`261 ' MM NW 27 SFAX: t(345) 594 9279Miami FL 3172 FAX 669-7993 = r sM'r'r c WINQ Nae`s'r �Y wwvu.tiren iee n ineers.com DESI D N DATE W.CHAMLERARCliTBCTURE.COM WWFP•� JOB NUMBER : s AN -SURE 515 APPROVED FOR BUILDING PERMITTING PURPOSES BY MIAMI-DADE COUIUTY FIRE DEPAnTMENT FIRE PROTECTION CONTivcrows VUURKINO PLAN AS PER NFPA 13 CHAI.I. PE SUFtkAITTF.D FOR APPROVAL TO NIIA', 0A1:E FI! E DEPART VE NT BEFORE ;ANY Fil r:_CT;tJ'J IS 1.STALL ED OR REN110C LF.E DATF4/ r'p : I I I I I J ; I I I I I - 545 oFRCE SUITE 555 OfICE SMITE SO OFICE SUITE 510 d.. i I, i .I