05-1438-010HVAC NOTES
1.0
1.1 PROVIDE (FURNISH AND INSTALL) ALL NECESSARY MATERIALS AND LABOR
FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING
(HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS.
1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE
SMACNA, NFPA AND LOCAL ORDINANCES.
1.3 SCOPE OF WORK :
PROVIDE THE FOLLOWING COMPLETE SYSTEMS
A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM.
B. EXHAUST SYSTEM FOR TOILET ROOMS.
C. EXHAUST SYSTEMS FOR WAREHOUSE.
D. AIR CONDITIONING UNITS AND CONTROLS.
E. INDEPENDENT TEST AND BALANCE.
1.4 NOT USED
1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION
CHARGES REQUIRED
1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF
MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND FABRICATION
OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS FOR SERVICE
AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER TRADES.
1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND
TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A
COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE SPECIFICATIONS.
1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS SHOWING
DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL BEFORE
PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL INFORMATION FROM 1.6 ABOVE.
1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE
THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS.
ALL SHOP DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE
NO LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT.
1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A
A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE.
2.0 AAAT'FRIAI t
2.1 DUCTWORK
2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSIONS.
2.1.2 DUCTWORK MATERIALS:
A: GENERAL OFFICE AREAS:
FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER (R-6)
DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE
WITH SMACNA'S FIBROUS GLASS DUCT CONSTRUCTION STANDARDS.
DUCT JOINTS SHALL BE SEALED AND TAPED.
B: TOILET ROOM EXHAUST AND FRESH AIR INTAKES:
GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD. (0.5" W.G.)
C: EXPOSED AIR CONDITIONING DUCTWORK
SPIRAL GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED
ACCORDING TO LATEST EDITION OF SMACNA'S. LOW
PRESSURE CONSTRUCTION STD. (0.5" W.G.)
2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS.
WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS VANES.
.1 ALTERNATE A: PROVIDE 3-PIECE ELBOWS IN LIEU
OF TURNING VANES FOR GLASS FIBER DUCTS ONLY.
.2 ALTERNATE A: PROVIDE FULL RADIOS ELBOWS IN LIEU
OF TURNING VANES.
2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY
OUTLET AND AT EACH DUCT BRANCH.
2.2 NOT USED.
2.3 NOT USED.
0)
N
N
M
N
LO
O
O
N
3
-0
N
O
Q
N
Q
LO
LO
r-
Z
Q
N
Z
Q
2
co
ti
O
CN
SUITE 515, FIFTH FLOOR, PLAZA 57
w 7301 S.W. 57TH COURT
o CITY OF SOUTH MIAMI
a SOUTH MIAMI, FLORIDA 33143
2.4 AIR DISTRIBUTION PRODUCTS :
2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS.
2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED
ON THE DRAWINGS AND SCHEDULES.
2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE
CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS.
2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS
BEHIND ALL AIR SUPPLY OUTLETS.
2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR CONDITIONING
COMPRESSORS STARTING FROM THE DATE OF PROJECT ACCEPTANCE.
2.6 CONTROLS:
2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION
OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK
WIRING INDICATED FOR EACH PIECE OF EQUIPMENT.
2.6.2 OFFICE AREA DX EQUIPMENT:
PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT/COOL
THERMOSTATS WITH ON -OFF AUTO SUB -BASE SWITCH AS FURNISHED
BY THE EQUIPMENT MANUFACTURER.
2.7 STARTERS:
PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION
AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST HAVE
HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED/GREEN PILOT LIGHTS,
PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS
FOR THE INTENDED OPERATION AND INTERLOCKS.
2.8 NOT USED.
2.9 IDENTIFICATION:
2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12"0" HIGH WITH
WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE DOCUMENTS.
2.10 RETURN AIR CEILJNG PLENUMS:
2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS"
ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE
A MAXIMUM FLAME SPREAD INDEX OF 26 AND A MAXIMUM
SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A.
"NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM."
2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING SPACE,
SEE ARCHITECTURAL PLAN FOR COORDINATION
3.0 EXECUTION
3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION
TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION & SERVICE.
FOR INSTALLATION, OPERATION AND SERVICE.
3.2 NOT USED
3.3 THERMOSTAT LOCATION.
THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION.
INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS.
RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING.
3.4 RETURN AIR FOR INDIVIDUAL ROOMS IS BEING PROVIDED AS SHOWN ON PLANS
AND IS SIZED COUNTING ON A 1" UNDERCUT FOR ALL DOORS IN ADDITION TO
THE REQUIRED RETURN OR TRANSFER SYSTEM.
3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION
REPAIR AND OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND
TO BE OBJ CTIONABLE, TO THE SATISFACTION OF THE A/E.
3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES
TO MATCH SPECIFIED FLOWS & CAPACITIES.
CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE.
OUTSIDE AIR CALCULATIONS
I (2) AHU 5 I
I I_ ^^2,430 SF a 1�1 PEOPLi=- -.- 4- a 20 CFM/PERSON _ ._ __ _ � il 360 CFM O/A�
OFFICES I O/A PROVIDED ! 400 CFM / O/AI
I_ __ _ - _ _ _ _. _- _- - ____ _ ___ - __ __ _ _ q .m __ ._ _._ _.. __ _ _ .- __ _._ _ _ _ _ _ _ __ __ - -._ .-. --- _ _ _s .- __ _- J
EXISTING SYSTEM PER SHELL DRAWM6
A/C SPLIT SYSTEM SCHEDULE
-- DESIGNATION ------------------- L------�'---L----------
QUANTITY ____________________ _EXISTING(2)_
A_R_E_A_S_ERV_E_D_ ______________I ___51JIT� 515__ I ________
--_MA_N_U_FA_C_TU_R_ER-_-- -
--------------- ___TRANE __-----------
__ FA_N_C_OILMOD_E_L_N_o. _ _________�TILJEP 3 I_________.
CONDENSING _UNIT _ MODEL No. LL________-
_M__B_i _N_E__D__R_A_T_I__
TOTAL SENSIBLE CAPACITY B_TU/HR ___I __ 61000___L________-
GRAND TOTAL CAPACITY__ BTUI/HR _____ I _ 45100 __ I _________
__ ERGTOTAL_HEATINGC_AP_ACITYBTULHR ____ __25,500 __- - - - - - - - -
ENYEF_FICIE_NC_YRATIO SEER (EERI__ -- 12. 0___--____-_-
__ COEFFICIENT OF PE_R_FOR_MANCE COP_____L_________L_________
F_A_ N__C 0 1 L U_N_ I_T______ ___ _ ________
--TYPE-----------------------L---_VERTICAL-L---------
TOTAL _AIR _SUP P_L_YCFM_ _I I 2�00 __ ________
OUTSIDE AIR _SUPPLY __C_F_M___ ______L__ 200 __L_________
EN_TERIN_G_ AI_R_C_O_NDIT_IO_N_S__F_D_B/FWB I -80/6� _ I
__ EV_APO_R_AT_0_R_C_OII _MIN__RO_W_S_/_MA_X. F.P.I j ____ - I _________
EXTERNAL _STA_TI_C_PRESSURE "H20 r ___0.5___ I
-_-_ FAN SPEED RPM ----------------j-_NICiN_5P_E_ED__- j -__-_--__--_-_-_-
-- FA_N_M_0_T_ORHP_--_--_-_-_- _- -----3/4 ___4----------
__ ELECTRICAL __SERVICE AVAILABLE _0_ I __ 208/I/60_
RU_N_NIN_G_L_0_ADA_MP_S_______�___ 3_9 ___4-________
ELECTRIC RESISTANCE HEATER SIZEK_W___I
-- UNIT WEIGHT-------------------�r-----225---L------- �''
C O N D ENS I N G_ U N_I_T _ __ __ _ ________
TY_PE------------------------�-- AIR COOLED-L---------
LOCATION ___ __________________I ___ ROO_P___ I ________
--RE_F_RI_GER_ANT_ TYPE ---------------L--- R-2�---L--------
AMBIENT AIR TEMPERATURE
FDB �___
NUMBER _0_FCOM_PRSO_RS_ _____ ____ I ____ ________
NUMBER OFCU _REFRIGERANT CIRITS____ I ____--- _______
__CA_P_AC_IT_Y_ REDUCTION -STEPS %______I __ 0-10_0 __I ---------
__ EL_ECT_RIC_ALSERVICE _AVAILABLE _________�__ 206/I/6ID4-________
RU_N_N_IN
_G_L_0_AD__A_MP_S_______________1 ___ --24---
4. 0___ 1 ________
MI_HIM_UM_CIR_C_UIT_A_M_PS__________________ 38.0___4-________
_MA_XIM_U_M_F_U_SE SIZE AM_PSI ___60._0___1
--UNIT WEIGHT-------------r-----212---L--------
AC_C__E_S__S_0__R_I_E__S_ _ _ _______ __
_ REFRIGERANT PIPING LENGHT FT________ __ti
---------------
__ LIQ_UIDLINE TYPE O.D. -____ I
SUCTION _LINE SIZE O.D._ - t
TH__E_RM_0_S_TA_T_ HEAT/COOL I
FILT_ER_ SECTION _AND _FILTER TYPE_______ llj!_THROWAIU_AY_L________
SMOKE DETECTOR ___I __IN 6UI90LY I ________
V_I_B_RAT_I_0_NISOLATORS
_FA_N_C_OILUN_IT- _r-_--_-_-_-r-_--_-_-_-_-_-
FO_R_CON_DEN_SIN_G_UNIT___
___ L - - I
AU_TOMATIC CONTROLS
-- TYPE
DESCRIPTION-------------------F---- _----j--------
ANTON10 FRANYIE
VIV NA Fi?ANYtE
Certificate of
Authorization #
00002906
�06 NW 27 Street, Miami FL 33172
TEL (306 52-1 FAX: (305) 594-9279
wwvu. ran LOj tigineers.com
DESI(rl D DATE
JOB NUMBER 05-
CHANDLER AND ASSOCIATES
ARCHITECYTURE, P.A.
AA 00W=
LA" R CHANDLEK AIA Al NQ 1606b
SOUTH MTAK FWRHM M43
TEL (306) 669-7992
FAX (" 669-7993
W W W.CI- AMLERARCHITEC'TURE.COM
00rj3 w mot
NO. DATE
AIR DISTRIBUTION SCHE%�ULE
DESIG
r0000ee000000_000lorso a asa.�osfo®�=Seoaor000s0000r
NATION 1 C R L
_ USE -------------+--SUPPLY---; REr!1I --}-----------
CONST_RUCTION I ALUMIN131 I ALUMINIUM I
I----------
_ SIZE-ISNOWN ON FLAN31--___-'� I
_ TYPE - - - - - - - - - - - - --------___- J 24' x_2_4' mooUL�R ____r ______--
COMMENTS I DIRECTIONAL CEILING DIFFUSER I
-----------------1---------J---------L--------
FINIS_H _ I _ALL _ALUMINIUM _ I ALL A_M LUMINIU__1
_ MOUNTING TYPE --___-I t -BAR_-�-- T-BAR
_ NO SE CRITERIA 30 MAX 1 30 MAX I _
MANUFACTURERI METALAIR_E_ I MEtALAIn I ______
_ MODEL-----------i-- 5-0- --J--------RH L--------
A C_C E_S S 0 R I E S __ ___ ____ ____ 17 ________
O_PPO_S_E_D_B_LAD_E RE_GIST__L__ 0ap___J-_-------L-_-_---_
FIRE DAMPER __ I __ I - I
CONNECTION SIZE - j SHOWN ON PLANO j -----------------T--------- 1-------------------
-o 000as00000000000ir00000eoo�0000ee000ir000eoose
NOTES
1. FINISHES AND TYPES OF MOUNTS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS.
2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE
THICKNESS TURNING VANES AT ALL 90* SQUARE ELBOWS, OR 3 PIECE ELBOWS.
3. PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH
SUPPLY OUTLETS MODEL - OBDC.
DUCT BRANCH TAKE -OFF MODEL - AIRTROL MOD. 102
4. PROVIDE O.B. DAMPER AT ALL SUPPLY OUTLETS.
5. DUCT WORK TYPE -.--_ SEE A/C NOTES.
6. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS.
7. DIFFUSOR NECK SIZE SHOWN ON PLANS. (6x6, 9x9, 12x12, OR 15x15)
HVAC DESIGN REQUIRES:
YES
NO
Remarks
DUCT SMOKE DETECTOR
-
FIRE DAMPER($)
-
$MOKE DAMPER(S)
-
_
-
FIRE RATED ENCLOSURE
-
-
-
FIRE RATED ROOF/FLOOR
CEILING A$$EMBLY
FIRE STOPPING
-
-
-
$MOKE CONTROL
-
-
-
TERMINAL UNIT SCHEDULE
ee DESIGNATION eeeeeeeeeeeeeeeew�eee 8 eee
-- -4 --
__ QUANTITY IVE_RIFY_-_P_R_OV_ID_EPER PLA_N_SL7_ SEE PLAN__
LOCATION _,_PERIMETER _
_-AREA SERVED ---------------- --SIDETI- OAF_
__ OPERATING WEIGHT 1_____
MANUFACTURER ETI
MODEL No. I_ VVR_1006__
G E N ERAL DATA _
--jyp_�-----------------------l-Fp.l____
DESIGN_ AIR_FLOW_,_ CFM______
MINIMUM_ DESIGN_ AIR FLOW _CFM
---MAXIM.�BFS�� QBQP�._ »�-0 - - - -- 0.06 ----
__ INLET_ STATIC PRESSURE, __TI 0
__ - STATIC_PRE_SS_UR_EL_"H O______
DESIGN SOUND LEVEL,_ NC_____ 20
INLET CONNECTION SIZE _ IN._______1___10'0____
H__E A _T_I N _G ______________ ____ ___
-- HEAT,[FAN_, CFM ______________1---400---
ELECTRIC RESISTANCE _KW +___WA ___
INDUCTION FAN HP _ ________ I __ 1/6 HP
ELECTRICAL SEg�CE AV AIIABLE______1__2_1M60Q
A C_C E S S 0 R I E S __________________
__ R,�A PLENVM_FILTER ___________ -r __ ___
----L___--____
--------------------------
AUT_0_MATIC CONTROLS
TYPE
DESCRIPTION T--
NOTES:
ALL VAV BOXES ARE ELECTRONIC - PREWRE INDI=PENDENT.
F.P.I. z FAN POWERED INDUCTION 50XE8 MODEL 400 W. SIXES A$ SCHEDULED
0 PROVIDE WITH 211/120 TRANWORMER FOR ELECTRICAL SERVICE,
NOTE: I: FAN PERFORMANCE SELECTED 0 MAXM CM a 025 ESP.
PROVIDE FILTER SECTION W/ FILTER ON FPI.
FEY1801 I NO. DATE PEVISION
DRAWING TITLE:
'l/
H.V.A.C. NOTES