13-749-112METAL PIPE OR CONDUIT 3M FIRE CARRIER CP 25 C n SIN IT NOTES: 1- FLOOR OR WALL ASSEMBLY - MIN, 2-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR A NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS, MAX DIAM OF OPENING IS 30-7/8 IN. IA- STEEL FLOOR UNIT/FLOOR ASSEMBLY - AS AN ALTERNATE TO ITEM 1, THE FLOOR ASSEMBLY MAY CONSIST OF A FLUTED STEEL FLOOR UNIT / CONCRETE FLOOR ASSEMBLY. THE FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL FLOOR -CEILING DESIGN THE THE FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES A, CONCRETE - MIN 2-1/2 IN. THICK REINFORCED LIGHTWEIGHT ON NORMAL WEIGHT (100-150 PCF) CONCRETE, AS MEASURED FROM THE TOP PLANE THE FLOOR UNITS. B. STEEL FLOOR AND FORM UNITS - COMPOSITE OR NON -COMPOSITE 1-1/2" TO 3 IN. DEEP FLUTED GALV STEEL UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR - CEILING DESIGN. MAX DIAM OF OPENING IS 30-7/8 IN, 2- THROUGH -PENETRANT- ONE METALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR RE CARRIER SPACE BETWEEN PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN, 5 CAULK TO MAX 7/8 IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY, THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED: A. STEEL PIPE - NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. D. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) SECTION A -A COPPER TUBING. E. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT. F, CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT). UL APPROVED PIPING SATING ASSEMBLIES EQUAL TO UL SYSTEM xCAJ-1175 FOR INSULATED PIPE AND 3- FILL, VOID, OR CAVITY MATERIAL -SEALANT -MIN I/2 IN. THICKNESS OF FILL SYSTEM xC-AJ-1291 FOR NON INSULATED PIPE MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN PIPE AND CONCRETE, A MIN 1/4 IN, DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE / PIPE INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF WALL. PIPE PENETRATION FIRESTOP DETAIL METAL PIPE OR CONDUIT 3M FIRE CARRIER CP 25 CAU FIRE RATED CONC, FLOOR SLAB N.T.S. 9 TRAP RESEAL DETAIL N,T,S. FLUSH VALVE SILVER SOLDER CHROMED COUPLING TO TAILPIECE 1/4" CHROME- PLATED ESCUTCHEON PLATED AT WALL NOTE: - THIS DETAIL APPLICABLE FOR RESEALING OF ALL TOILET ROOM FLOOR DRAINS. ALL OTHER FLOOR DRAINS ARE TO BE RESEALED BY MEANS OF A JOSAM 88250 SERIES PRIME VALVE INSTALLED IN THE C.W. SUPPLY LINE OF THE NEAREST SINK C SLOPED TO THE FLOOR DRAIN. POSITION OF FLUSH VALVE HANDLE AT HANDICAPPED FACILITIES TO BE ON SIDE FARTHEST FROM ADJACENT WALL. METAL PIPE OR CONDUIT I, 2, 3, OR 4 HOUR FIRE RATED CONCRETE FLOOR SLAB ............................................ NOTES USE 3M CP -25 WB (*) SELF -LEVELING CAULK ON HORIZONTAL SURFACES WHEN FILLING GAPS FROM ABOVE THE PENETRATION. USE 3M CP -25 WB (■) NO SAG CAULK ON VERTICAL SURFACES AND ON HORIZONTAL SURFACES WHEN FILLING GAPS FROM BELOW. INSULATION (IF REQUIRED BY SPECIFICATION) FILL GAP COMPLETELY AROUND PIPE WITH 3M CP -25 WB (*) CAULK (SEE NOTES 3-5) DAMPING MATERIAL (FIBERGLASS INSULATION, BACKER ROD OR MINERAL WOOL) ENOUGH TO SUPPORT WEIGHT OF 3M CP -25 WB (*) CAULK. SECTION VIEW (SLAB) I, 2, 3, OR 4 HOUR RATED CONCRETE BLOCK WALL - FOR SOLID CONCRETE WALL (SEE NOTE 1) NOTES: DAMPING PIPE 1. FOR SOLID CONCRETE WALLS. CENTER 3M CP -25 WB (*) CAULK MATERIAL OR CONDUIT WITHIN WALL WITH DAMPING MATERIAL ON ONE SIDE. 2. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E-814 (UL -1479) FIRE TEST AND UL CLASSIFICATION FIRE STOP SYSTEM CAJ-1175. INSULATION (IF REQUIRED 3, WET INSTALLED DEPTH OF 3M CP -25 WB (*) CAULKS DEPENDS ON BY SPECIFICATION) 3M CP -25 WB (*) N/S CAULK TYPE AND SIZE OF PIPE: AND DESIRED RATING. BOTH SIDES OF WALL WET DEPTH PIPE SIZE FIRE RATING (SEE NOTE) 1/2" (13MM) MAX. 8' (203MM) 1-2 NRS. I" (25MM) MAX. 8• (203MM) 3-4 HRS, 4. UP TO 401 SHRINKAGE OF 3M CP -25 (*) N/S OR S/L CAULK IS ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION. SECTION VIEW (WALL) 5. MAXIMUM ANNULAR SPACE TO BE FILLED IS 1 3/8" (35MM). UL APPROVED PIPING SAFING ASSEMBLIES EQUAL TO UL SYSTEM xCAJ-1175 FOR INSULATED PIPE AND SYSTEM XWJ-1009 FOR INSULATED PIPE PIPE PENETRATION FIRESTOP DETAIL SILVER SOLDER CHROMED COUPLING TO TAILPIECE 1/4" CHROME- PLATED ESCUTCHEON PLATED AT WALL TYP. FLUSH VALVE LOCATION FOR HANDICAPPED FACILITIES N.T.S. N.T.S. (*) (OR APPROVED EQUIVALENT) PLUMBING FIXTURE COLD WATER TO FIXTURE DIMER VALVE JOSAM x88250-10 OR APPROVED EQUAL W/ VACUUM BREAKER, NOTE: ALL EXPOSED PLUMBING ITEMS, SHALL BE CHROME PLATED FLOOR DRAIN -�— DN, j`- -�— DN. 1/2" MIN. ALTERNATE CONN'S. (CONTRACTOR'S OPTION) SLOPE DN, TO OUTLET • 1/8" FT. W/ NO TRAP OR INTERMEDIATE LOW POINTS. NOTE: USED WHERE NO SUITABLE WATER CLOSET, ELECTRIC WATER COCLER, OR DRINKING FOUNTAIN IS WITHIN 30 FEET. TRAP PRIMER VALVE DETAIL (T.P.V.) N.T.S PARTITION OR CHASE C.W. SUPPLY TO PLUMBING FIXTURE HOSE BRACKET 24" X 24" X 10" ONE PIECE TERRAZZO STONE CORNER BASIN -0 • • A a • MOP SINK DETAIL NTS CONNECT TO TOP OR WITHIN 45 OF TOP ONLY i® ®I SPOUT BRACE SPOUT WITH HOSE END E PAILHOOK - CHROME PLATED SERVICE FAUCET WIT VACUUM BREAKER - 30" NOSE DRAIN O A n a 3" DIA, P -TRAP DO NOT VALVE TRAP PRIMER VALVE CONN. COLD WATER BRANCH OR MAIN, PROD. No. 23026 CAy924 iV• iV• r LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS - 9150 SOUTH DADELAND BLVD. "'i'S�ITE 900„ MIAMI, FLORIDA 33156 TELEPHONE: (305) 670-0141 ••+• •lily FAX: (305) 670--0144 ; • • • • i i www.ljocpa.com • MOP HANGER WALL STRUCTURE "PDT" PRESSURE DROP ACTIVATED W/ BACKFLOW PREVENTER NO VALVE DIRECTLY TO DRAIN OUTLET OR DISTRIBUTION UNIT CLEAR TOP • SUPPORT BRACKET 12" A.F.F. MIN. VERTICLE TRAP SUPPLIES bJ ld ld MIN, 3/8" (NO VALVES) 80 E VERTICLE TO HORIZONTAL HORIZONTAL TRAP SUPPLIES MIN 1/2" SLOPE I/8" MIN. WITH NO TRAPS OR NOTE! I_wV r'U11N I b USED WHERE NO SUITABLE WATER CLOSET, ELECTRIC WATER COOLER, OR DRINKING FOUNTAIN IS WITHIN 30 FEET. PRESSURE DROP TRAP PRIMER (P.D.T.) + DISTRIBUTION UNIT (T.P.D.) DETAIL N.T.S. VACUUM BREAKER VENT - V ? OPENING (2) FIXTURE VALVE UJIER ESCUTCHEON VALVE E DISTRIBUTOR — PLATES (SEAL MUST BE ACCESSIBLE PARTITION (NOT NECESSARY TO OPENINGS) BE DIRECTLY IN-LINE TO OR SAME LOCATION) 0— "TDP" DISTRIBUTION i UNIT (MAX, 2 W/ 4 51, OUTLETS EA. MANI- U FOLDED ON ONE TRAP . PRIMER VLV) MAY BE REMOTE FROM PRIMER VLV FINISH N� FLOOR CHECKED: R.M. — 3/8", 45 MAX. PENETRATION 20CC SLEEVE C SEAL AS REQUIRED BY LOCATION j (REFER TO NOTE: COMPONENTS A DETAIL) SHALL BE PRECISION PLUMBING PRODUCTS INC. "OREGON" NO] VALVE C DISTRIBUTOR OR APPROVED EQUAL i® ®I SPOUT BRACE SPOUT WITH HOSE END E PAILHOOK - CHROME PLATED SERVICE FAUCET WIT VACUUM BREAKER - 30" NOSE DRAIN O A n a 3" DIA, P -TRAP DO NOT VALVE TRAP PRIMER VALVE CONN. COLD WATER BRANCH OR MAIN, PROD. No. 23026 CAy924 iV• iV• r LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS - 9150 SOUTH DADELAND BLVD. "'i'S�ITE 900„ MIAMI, FLORIDA 33156 TELEPHONE: (305) 670-0141 ••+• •lily FAX: (305) 670--0144 ; • • • • i i www.ljocpa.com • MOP HANGER WALL STRUCTURE "PDT" PRESSURE DROP ACTIVATED W/ BACKFLOW PREVENTER NO VALVE DIRECTLY TO DRAIN OUTLET OR DISTRIBUTION UNIT CLEAR TOP • SUPPORT BRACKET 12" A.F.F. MIN. VERTICLE TRAP SUPPLIES bJ ld ld MIN, 3/8" (NO VALVES) 80 E VERTICLE TO HORIZONTAL HORIZONTAL TRAP SUPPLIES MIN 1/2" SLOPE I/8" MIN. WITH NO TRAPS OR NOTE! I_wV r'U11N I b USED WHERE NO SUITABLE WATER CLOSET, ELECTRIC WATER COOLER, OR DRINKING FOUNTAIN IS WITHIN 30 FEET. PRESSURE DROP TRAP PRIMER (P.D.T.) + DISTRIBUTION UNIT (T.P.D.) DETAIL N.T.S. a CC V ? I t Seal 4 irr•irr,,f,�( UJIER J ; A . s >Uj 1�m z • • Rt-LtIkEATIONAL TO DESIGN AND 0— CONSTRUCTION, INC. i 3990 North Powerline Road 51, Ft. Lauderdale, FL 33309 U Voice: 954.566.3885 . Fax: 954.566.3335 _.__.__._._......._..---.._...... -.--... a CC old Seal 4 irr•irr,,f,�( UJIER U ; A . s >Uj 1�m z p M C11) T_ TO M N 0— a.— i N a © U >m DRAVVN : J. E3 Cn rc N� w� CHECKED: R.M. — a CC old Seal 4 irr•irr,,f,�( UJIER Uj 0 SE RANO P,E. Cr 1�m z p M C11) T_ TO 44C LU (� a.— CV) J IL N a © o LO— I DRAVVN : J. E3 Cn rc CHECKED: R.M. T �U) .�..r �, Z a 20CC ISSUE REVISIONS i h. .... a old Seal 4 irr•irr,,f,�( UJIER v 0 SE RANO P,E. LIC x 57864 © PROJECT NUMBER old C rfCH NICAL: UJIER v 0 SE RANO P,E. LIC x 57864 © PROJECT NUMBER O © FILE No. P7.00.dwg LL0 DRAVVN : J. E3 REVIEWED, R.M. CHECKED: R.M. tF— V CL DATE 07-02-13 ISSUE REVISIONS J r h. .... ......... ......... l� O...... . D � O.......................c Ljj i SHEET TITLE _.... C C[ r DETAILS PLUMBING k .... SHEET NUMBER ........ ....... .... . P7.00