13-749-104DISCONNECT SWITCH UL. LIS ELECTRIC CONDUIT----_` GUIDE NEOPRENE GASKET--� (FURNISHED WITH CURB) ACOUSTICAL INSULATION-- (FURNISHED WITH CURB) \ WIRING' BY OTHERS FLEXIBLE—r CONNECTION FAN 1/8" STAINLESS STEEL CABLE W/ TURNBUCKLE (SEE NOTE #2) 3/8" GALVANIZED STEEL, SELF TAPPING EYEBOLT (TOTAL OF 4) SECURE FAN TO CURB WITH NO. 14 S/S SCREWS, 8" O.C. ALL AROUND PREFABRICATED FAN CURB (18" MIN. HEIGHT) CANT STRIP (BY ROOFER) ROOFING ROOF INSULATION ---SEE HILTI EXPANSION ANCHOR KWIK BOLT TZ DETAIL BACKDRAFT DAMPER SEE ARCH. DRAWINGS FOR ROOF CURB EXHAUST FAN ON METAL DECK ROOF N.T.S. WASHER 3/8" DIA. THRU BOLTS, 18" O.C. MAXIMUM ALL AROUND. LOCATE AS CLOSE AS POSSIBLE TO VERTICAL MEMBER. EXHAUST DUCT NOTES: 1. POWER LINES SHOULD BE BROUGHT UP IN ONE CORNER OF CURB AND FED THROUGH THE CLEARANCE HOLE PROVIDED IN THE LOUVER DAMPER, IN TURN, THE POWER LEAD SHOULD THEN BE FED THROUGH THE ROOF VENTILATOR CONDUIT GUIDE OR GROMMENTS. PROVIDEA GENEROUS LOOP OR SLACK IN THE POWER SUPPLY LINE WITHIN THE MOTOR COMPARTMENTTO ALLOW FOR MOTOR DEFLECTION AND FOR BELT TENSION ADJUSTMENT 2. INSTALLATION MUST MSFT MINIMUM WIND LOADING REQUIREMENTS OF THE 2010 FBC. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS PREPARED AND SIGNED/SEALED BY A FLORIDA STRUCTURAL PE FOR APPROVAL PRIOR TO INSTALLATION. INTERIOR WALL SURFACE SECURE UNIT' SLIDE -OUT CHASSIS TO INTERIOR WALL SURFACE PER MANUFACTURER'S RECOMMENDATIONS INTERIOR REFER TO— ARCHITECTURAL DRAWINGS FOR HEIGHT OF A/C UNIT ABOVE FINISHED FLOOR SELF-CONTAINED A/C UNIT INSULATION CAVITY EXTERIOR WALL SEAL WALL PENETRATION OF UNIT WATERTIGHT WITH CAULKING ALL AROUND SLIDE -OUT CHASSIS FURNISHED BY EQUIPMENT MANUFACTURER FRAME OPENING ALL AROUND EXTERIOR INSTALL UNIT HORIZONTALLY LEVELED BY PROVIDING BRACKET SUPPORTS NOTES: 1. THRU-THE-WALL FINISHED OPENING DIMENSIONS SHALL BE AS RECOMMENDED BY UNIT MANUFACTURER, 2. UNIT INSTALLATION MUST COMPLY WITH FLORIDA BUILDING CODE REQUIREMENTS. THRU-THE WALL A/C UNIT INSTALLATION DETAIL N.T.S. A CLOSE OPENING 45 DEGREE ENTRY/0 = 45 HVAC DUCT CONSTRUCTION STANDARDS ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC DUCT CONSTRUCTION STANDARD AS FOLLOWS: LOW PRESSURE DUCTWORK: 2"W.G. W. (4" MIN) TAPP-OFF WITH VOLUME DAMPER N.T.S. A� CLOSE OPENING 45 DEGREE ENTRY/0 = 45 i0 STAINLESS STEEL BOLT CARBON STEEL BOLT STEELSTRENGTH STEEL STRENGTH IN TENSION = 5980 LB IN TENSION = 6500 LB STEELSTRENGTH STEEL STRENGTH IN SHEAR = 4870 LB IN SHEAR = 3595 LB HILTI EXPANSION ANCHOR KWIK BOLT TZ DETAIL N.T.S. ""P. BOARD WALL )INSTRUCTION. 60NIRY WALL )NSTRUCTION. 'PLY ACOUSTIC ALANT ALL A� GYP. BOARD PARTITION - 22 GA SHEET ANGLE FRAN PREFABRICATED FAN CUR CANT STRIP (BY ROOFER) W/FLANGE; 18" MIN. HEIGHT ROOFING PRESSURE TREATED WOOD BLOCKING ROOF INSULATION MASONRY PARTITION WALL DUCT PENETRATION DETAIL N.T.S. IN) TAPP-OFF WITH VOLUME DAMPER N.T.S. r � CONCRETE ROOF SYSTEM 1/2" DIA. EXPANSION BOLT, 8" O.C. ALL AROUND CURB ATTACHMENT TO PRECAST CONCRETE ROOF N.T.S. SHEET METAL RUNNER T^" ^"'^ BOTTOM SECURED TO D WITH SHEET METAL SCR SHEET METAL DOUBLE THICKNESS QUARTER ROUND TURNING VANE LASS `O 6x DENSITY). SHEET M TURNING FASTENE SHEE TO D SCREWS OPPOSED BLADE BALANCING DAMPER WITH CONCEALD LINKAGE, GALVANIZED AS MANUFACTURED BY RUSKIN #MD -35 NOTE: SINGLE BLADE MD -35 DAMPER MAYBE USED ON DUCTS 11" HIGH AND UNDER. VENTFAB #644 FOR INSULATED DUCTS VENTFAB #641 FOR NON -INSULATED DUCTS. - HANDLE WITH LOCKING NUT SHEET METAL SCREW FASTENIGS DUCT BALANCING DAMPER DETAIL N.T.S. SINGLE VANE SCHEDULE DESIGNATION "R" SP GA. SMALL 2" 1/2" 24 LARGE 4" 31/4' 22 NOTE: SINGLE THICKNESS TURNING VANES SHOWN. PROVIDE DOUBLE THICKNESS WHERE SPECIFIED. DUCT TURNING VANE DETAIL NTS F A N S C H E D U L E DESIGNATION EF -1 EF -2 EF -3 3990 North Powerline Road MANUFACTURER GREENHECK GREENHECK GREENHECK L WEIGHT (LBS,) 58 57 57 MODEL NUMBER GB -121-4 GB -071'-6 GB -081-6 TYPE. CENTRIFUGAL ROOF CENTRIFUGAL ROOF CENTRIFUGAL ROOF AREA SERVED TOILETS 103, 104, 105 ELECTRICAL 107 POOL EQUIP. RM. 106 C.F.M. 915 85 300 E.S.P. (INCHES OF WATER) 0.25 0.15 0.15 SONES 6.0 1.7 3.1 R,P,M. 935 686 793 H.P. 1'/4 116 1/6 VOLT - PH - HZ 120-1-60 120-1-60 126-1-60 DRIVE BELT BELT BELT BACKDRAFT DAMPER YES YES YES REMARKS 1, 2; 3, 4, 5 1, 2, 3, 4, 5 1, 2, 3, 4, 5,6 INTERLOCK RUN CONTINUOUSLY T -STAT SET@ 80°F RUN CONTINUOUSLY REMARKS: 1. PROVIDE WITH B IRDSCREEN. 2. PROVIDE WITH INSULATED FACTORY CURB, 18" NIGH. 3. SHALL BE ALUMINUM CONSTRUCTION. 4. ALL FANS OR EQUIPMENT ON ROOF SHALL BE SECURED WITH STRAPS OVER THEM ACCORDING TO FBC 5.301.13 5, PROVIDE WITH SPEED CONTROLLER; MOUNTED ON FAN ATACCESSIBLE LOCATION, 6. SHALL HAVE HIGH PERFORMANCE BAKED EPDXY POWDER COATING FOR PROTECTION AGAINST ACID OR OTHER CORROSIVE CHEMICALS. SCREVI - SCREWS MAY BEJ 1 OMITTED IF HANGER LOOPS STRAP HANGERS ICATED ELBOW PROD. No. 23026 •v`C%924 • r LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS' v • j 9150 SOUTH DADFLAND BLVD. ujt 9�0 4 MIAMI, FLORIDA •." 33156 �Y TELEPHONE: (305) 670-0141 FAX: (305) 670-0144 .... • • • www.ljaapa.com ;�•+` +' CAULK ALL JOINTS WATERTIGHT IN THIS AREA CONNECT DUCT TO PLENUM AS HIGH AS POSSIBLE 1071AEel1V/: 1/2" MESH SCREEN SLOPE DUCT UP IF POSSIBLE PITCH BOTTOM OF PLENUM DOWN 4" PER FOOT TO OUTSIDE (MIN.) ANGLE FRAME TO SECURE PLENUM SECTIONS TO WALL TYPICAL DUCT CONNECTION TO LOUVER UNLESS FOOT OF TRAP IS PLACED UNDER A BOTTOM REINFORCEMENT N.T.S. SIZE BOLT(S) FOR LOAD TRAPEZE HANGERS NOTE: ALL STEEL SUPPORTS AND ASSOCIATED COMPONENTS FOR MECHANICAL EQUIPMENT INSTALLED OUTDOORS OR INSIDE BUILDING'S UWAIR CONDITIONED SPACES (EXPOSED OR CONCEALED) SHALL BE HOT DIP GALVANIZED AFTER FABRICATION WHETHER SHOWN OR NOT SHOWN ON THE DETAILS IN THIS SHEET. FEQUIPMENT UIPMENT DETAILS SHOWN IN THESE DRAWINGS ARE GENERIC. FOR ALL TO BE MOUNTED ON ROOF, GRADE OR EXTERIOR BUILDING WALLS, ACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS DETAILING THE ATTACHMENT H EQUIPMENT TO BUILDING STRUCTURE IN COMPLIANCE WITH 2010 FLORIDA BUILDING CODE REQUIREMENTS. SHOP DRAWINGS SHALL BE SIGNED/SEALED BY A STRUCTURAL FLORIDA P.E. AND SUBMITTED FOR REVIEW AND APPROVAL BY PROJECT'S STRUCTURAL ENGINEER OF RECORD. • y V v, EZ,REA Y IONAL ROD --- UNLESS FOOT OF TRAP IL L— j CONSTRUCTION, INC. SIZE BOLT(S) FOR LOAD TRAPEZE HANGERS NOTE: ALL STEEL SUPPORTS AND ASSOCIATED COMPONENTS FOR MECHANICAL EQUIPMENT INSTALLED OUTDOORS OR INSIDE BUILDING'S UWAIR CONDITIONED SPACES (EXPOSED OR CONCEALED) SHALL BE HOT DIP GALVANIZED AFTER FABRICATION WHETHER SHOWN OR NOT SHOWN ON THE DETAILS IN THIS SHEET. FEQUIPMENT UIPMENT DETAILS SHOWN IN THESE DRAWINGS ARE GENERIC. FOR ALL TO BE MOUNTED ON ROOF, GRADE OR EXTERIOR BUILDING WALLS, ACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS DETAILING THE ATTACHMENT H EQUIPMENT TO BUILDING STRUCTURE IN COMPLIANCE WITH 2010 FLORIDA BUILDING CODE REQUIREMENTS. SHOP DRAWINGS SHALL BE SIGNED/SEALED BY A STRUCTURAL FLORIDA P.E. AND SUBMITTED FOR REVIEW AND APPROVAL BY PROJECT'S STRUCTURAL ENGINEER OF RECORD. • y V v, EZ,REA Y IONAL DESIGN AND CONSTRUCTION, INC. 3990 North Powerline Road Ft. Lauderdale, FL 33309 Voice: 954,5t�6.388 L Fax: 954.566,3335 _.