13-749-100• GENERAL ELECTRICAL NOTES: 1. ELECTRIC RUNS SHOWN ARE DIAGRAMMATIC, ACTUAL ROUTING SHALL BE COORDINATED WITH FIELD CONDITIONS AND OTHER TRADES. DO NOT SCALE ELECTRICAL DRAWINGS. 2, ALL CONDUITS SHALL BE 1/2" MINIMUM ABOVE GRADE (314" UNDERGROUND) UNLESS OTHERWISE NOTED (UON). J. ALL WIRE SHALL BE THHNITHWN COPPER, MINIMUM SIZE 112 (LION). ALUMINUM CONDUCTORS ARE NOT PERMITTED. 4. NAMEPLATES SHALL BE PROVIDED AT ALL MAINS AND SWITCHES AND OTHER CONTROL DEVICES WHERE THE LOAD CONTROLLED IS NOT READILY APPARENT. 5. CONTRACTOR SHALL BALANCE LOADS ACROSS ALL SYSTEM PHASE LEGS AND ON SINGLE PHASE, 3 -WIRE SYSTEMS. 6. ALL MATERIALS, EQUIPMENT AND INSTALLATIONS SHALL COMPLY WITH THE LATEST EDITION OF THE FLORIDA BUILDING CODE (FBC) AND THE 2011 NATIONAL ELECTRICAL CODE (NEC). 7. ELECTRICAL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED ELECTRICAL CONTRACTOR. CONTRACTOR SHALL PROVIDE EVIDENCE OF PROPERTY DAMAGE AND PUBLIC LIABILITY INSURANCES. 8. CONDUITS SHALL BE RUN CONCEALED IN ALL FINISHED AREAS. EXPOSED CONDUITS SHALL BE RUN NEAT AND EITHER PARALLEL OR PERPENDICULAR TO WALLS dc CEILINGS. 9. EMT MAY BE USED ABOVE GRADE AND OUT OF WEATHER WHEN PERMITTED BY CODE. SCH 40 PVC MAY BE USED UNDERGROUND (UG), WHERE NOT SUBJECT TO PHYSICAL DAMAGE, HEAT OR SUNLIGHT. 10. EXPOSED EXTERIOR CONDUIT SHALL BE RIGID METAL (RMC) OR INTERMEDIATE METAL CONDUIT (IMC). SCH 80 PVC MAY BE USED WHERE NOT SUBJECT TO PHYSICAL DAMAGE. 11. ALL EXPOSED TRANSITIONS FROM UNDERGROUND PVC SHALL BE RMC OR IMC CONDUIT FROM 18" BELOW GRADE INCLUDING NINETY. WHERE A RACEWAY ENTERS A BUILDING FROM UNDERGROUND, IT SHALL BE SEALED PER NEC INCLUDING SPARES. 12. ALL ELECTRIC EQUIPMENT ENCLOSURES SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL. 13. OBTAIN ENGINEERS' APPROVAL PRIOR TO PENETRATING STRUCTURAL MEMBERS. 14. IN THE EVENT FIELD CONDITIONS DIFFER FROM CONTRACT DOCUMENTS, FIELD CONDITIONS SHALL GOVERN. 15. THE CONTRACTOR SHALL IMMEDIATELY REPAIR ANY DAMAGE CAUSED TO EXISTING FACILITIES. 16. MISC. ITEMS OBVIOUSLY REQUIRED FOR A COMPLETE AND OPERATING SYSTEM BUT NOT SPECIFICALLY CALLED FOR ON THE DRAWINGS OR IN THE SPECIFICATIONS SHALL BE PROVIDED BY THE CONTRACTOR AT NO EXTRA COST TO THE OWNER. (NUTS, BOLTS, MASONRY ANCHORS, CONDUIT AND EQUIP. SUPPORTS, DRILLING, WELDING, SCAFFOLDING, CRANE SERVICE, ETC.) 17. GROUND ALL SYSTEMS AND EQUIPMENT PER NEC 1250. 18. ANY EXTERIOR RECEPTACLES SHOWN ON THESE PLANS SHALL BE 20 AMP, WEATHER RESISTANT, SIDE WIRED WITH WP ENCLOSURES WITH "EXTRA DUTY" SAFETY COVER PER NEC J406.9(B). 19. ALL DISCONNECT SWITCHES SHALL BE SIZED FOR THE LOAD SERVED AND SHALL BE HP RATED, HEAVY DUTY • (UON). 20. PANELS, PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL CENTERS, ETC. SHALL HAVE COPPER BUS AND SHALL BE MARKED AS REQUIRED BY NEC 110-16, 110.24 AND 408.4(8). 21. ALL FUSES SHALL BE CURRENT LIMITING (UON). USE TIME DELAY FOR MOTOR,CIRCUITS AND NON -TD FOR MAINS. 22. VERIFY EQUIPMENT CURRENT INTERRUPTING RATINGS FOR ALL EQUIPMENT PRIOR TO CONSTRUCTION. 23. CLOSELY COORDINATE ALL SERVICE ENTRANCE WORK WITH ELECTRIC UTILITY COMPANY. 24. CLOSELY COORDINATE TELEPHONE SERVICE WORK WITH TELEPHONE UTILITY COMPANY. 25. UPON COMPLETION OF WORK, CONTRACTOR SHALL FULLY INSTRUCT OWNER'S REPRESENTATIVE IN COMPLETE OPERATION OF ALL ELECTRICAL SYSTEMS. 26. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FOR A MINIMUM OF ONE YEAR FROM DATE OF ACCEPTANCE. • 27. PROVIDE A FUSE HOLDER AND FUSE IN THE PRIMARY SIDE OF EACH UNGROUNDED CONDUCTOR OF ALL BALLASTS OR TRANSFORMERS. HOLDERS IN POLES SHALL BE BUSSMAN "HEB" SERIES, OR EQ. 28. ALL UNDERGROUND CONDUITS SHALL BE BURIED WITH A MINIMUM OF 18" COVER. FPL SERVICES SHALL BE 24" MINIMUM. FPL PRIMARY CONDUITS SHALL BE INSTALLED ACCORDING TO FPL SPECIFICATIONS. 29. DISTANCE BETWEEN PULL BOXES SHALL NOT EXCEED 400' AND MAY BE INSTALLED WHERE REQUIRED BY CONTRACTOR FOR EASE OF INSTALLATION. 30. ALL METAL JUNCTION BOXES AND PULL BOXES SHALL BE GROUNDED. 31. ALL ABOVE GROUND WP JUNCTION BOXES SHALL BE GALVANIZED NEMA 3R. 32. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY AND LOCATE ALL EXISTING UG FACILITIES INCLUDING ELECTRIC POWER, TELEPHONE, CAN, WATER, SEWER, GAS, FLOOD/STORM DRAINAGE, IRRIGATION OR ANY EXISTING UG SYSTEM PRIOR TO ANY EXCAVATIONS. 33. TRENCHES SHALL BE BACKFILLED AND TAMPED TO ORIGINAL DENSITY. 34. RESTORE ALL EXCAVATED k TRENCHED AREAS TO ORIGINAL CONDITIONS, INCLUDING SOD, PAVING, PLANTINGS, ETC. 35. BEFORE FINAL PAYMENT THE CONTRACTOR SHALL PROVIDE TO THE OWNER A COMPLETE SET OF AS -BUILT DRAWINGS. THESE DRAWINGS SHALL INCLUDE MEASUREMENTS OF UG CONDUITS AND PULL BOXES MEASURED TO PERMANENT STRUCTURES OR LANDMARKS. 36. ALL H.I.D. LAMPS SHALL INCLUDE MINIMUM 1 YEAR WARRANTY. 37. CL2, CHEMICAL CONTROLLERS AND BOOSTER PUMPS SHALL BE ELECTRICALLY INTERLOCKED WITH THE FILTER PUMP MOTOR CIRCUIT TO OPERATE ONLY WHEN FILTER PUMP OPERATES. EQUIPMENT ROOM EXH. FAN SHALL BE CONNECTED TO OPERATE CONTINUALLY OR WHEN FILTER PUMP OPERATES. 38. ALL METAL POOL STRUCTURES, FITTINGS, EQUIPMENT, LIGHTING, PUMPS, HEATERS AND ENCLOSURES SHALL BE BONDED WITH A J8 SOLID CU CONDUCTOR PER NEC 1680.26 0c FBC. 39. UNDERGROUND WIRING SHALL NOT BE RUN UNDER OR WITHIN 5' OF INSIDE WALL OF POOL (NEC 680.10). 40. PUMP MOTOR STARTERS SHALL BE EQUIPPED WITH HAND -OFF -AUTOMATIC SWITCHES. 41. ALL 15 AND 20 AMP, 120V PUMP CIRCUITS SHALL BE PROTECTED WITH GFCI (NEC 680.22.B). 314" C. (TYP) 4' x4' x314" BACKBOARD, MARINE PLYWOOD PAINTED GRAY, BOTTOM AT 12" AFF. 16 CU TO GRD. RUN CONDUIT TO ALL OUTLETS is INSTALL PULL STRING 2" PVC w/PULL STRING (TO PROP/LINE) TELEPHONE RISER (COORD. ALL WORK w/ ATT) BROOKS 136 CONC. HANDHOLE & BOLT DOE LID WIRES MUST NOT BEAR (OR APPROVED EQ.) \ ON BOX LID OR SIDES. \ - - GRADE RESIN -CAST WATERPROOF C307_ - SPLICES OR POLARIS BLUE SPLICES (SUITABLE FOR WET LDC). 1 id" MIN. EQUIP. GROUNDING CONDUCTOR o 0 0 0 40 CRUSHED ROCK AT BOTTOM o • + a OF JUNCTION BOX. CONCRETE HANDHOLE TYP. (N.T.S.) • HANDHOLE ENCLOSURES PER NEC1314.30. CONDUCTORS Jc SPLICES SHALL BE SUITABLE FOR WET LOCATIONS (314.30(C)) .1 1 �- (CONTROL) OL) (CKT: L-6) �� PE PE CELL ti PE C1 ELEC. HELD LTG. CONTACTORS (SIZE jc POLES PER SCHEDULE) CI LIGHTING CONTROL DIAGRAM (N.T.S.) LTG. CONTACTOR SCHEDULE Sw. LCI AMP/POLE LOAD CKT. PE 1 30 3 SECURITY LTG. L-6 & d ALL CONTACTORS SHALL BE EQUAL TO SqD CLASS 8903, TYPE L, ELECT HELD WITH 120V COIL, MOUNT IN LTG. CONTROL ENCLOSURE (LCE). P/E -CELL SHALL BE EQUAL TO INTERMATIC IK4200 SERIES AND SHALL FACE NORTH AND BE LOCATED AWAY FROM (OR SHIELDED) FROM ARTIFICIAL LIGHT SOURCES. LTG. CONTROL ENCLOSURE SHALL BE UL LISTED, N-1, HINGED AND LOCKED WITH BACK PANEL FOR MOUNTING EQUIP, F LOAD SUMMARY: TYPE SqD 'NQ' (OR EQ.) PANEL L MAIN BUS 225 AMP SERVICE 120/240V, 10,3W NEUTRAL FULL MOUNTING SURF MAIN 225A MCB POLE 42 AIC 22,000 BKR COND. WIRE REMARKS CK VA CK REMARKS WIRE COND. BKR CONTINUOUS: (INCL) 25X LRGST MTR: ILMJO 2910 2910 ^ C TOTAL 43900 26685 71065 VA SL AS • AT 240V 183 64 r 2011* 1/2" J12 BECS CONTROLS 1 1600 580 2 LIGHTING 112 112" 20/1 2011* 112-1112 CL FEEDER 3 1 19004 580 LIGHTING J12 112" 2011 30/1 1/2" J12 BOOSTER PUMP (314 HP) 5 1920 300 6 EXT. LIGHTING *** J12 112" 2011 20/1 * 314" J12 HEATER CONTROLS 7 500 No 8 POOL LT Tx. (LED) *** J10 3/4" 12011* 2011* 112 HEATER PUMP 9 1650 10 RECEPTS 112 112" 2011 20/1 112" J10 HAND DRYER 11 2300 12 RECEPTS 112 112" 2011 2011 1 112" 110 HAND DRYER 13 2300 540 14 RECEPTS 112 112" 2011 20/1 112" 110 HAND DRYER 15 2300 540 16 RECEPTS 112 112" 2011 2011 3/4" 110 WP DECK RECEPTS. 17 360 18 DRINKING FOUNT. 112 112" 2011 20/1 3/4" 110 WP DECK RECEPTS. 1920 160.0 1 RECEPT. VENDING j12 1/2" 2011 20/1 1/2" 112 RECEPTS. 21 540 22 RECEPT, VENDING 112 112" 2011 2011 112" 112 TELEPHONE 23 360 24 RECEPT. VENDING 112 112" 2011 20/1 112" 112 EX FAN J1 25 700 1300 1050 1300 26 28 AC RECEPT J12 112" 2012 2011 112" 112 EX FANS 2 k 3 27 2011 112" 112 GAS WATER HTR. 29 500 1250 30 SPARE - - 2011 2011 1/2" 112 IRRIG. CTLS. 31 300 1250 32 SPARE - - 2011 20/1 - - SPARE 33 250 1 _ 34 SPACE 2011 - - SPARE 35 1250 36 -- - - SPACE 37 38 39 _ - 40 42 SURGE PROTECTION (INCL) (INCL) 2012 41 TOTAL CONNECTED LOAD: 36200 VA 18050 18150 25% LARGEST MOTOR: 480 CONTINUOUS AT 25%: 59 * GFCI BREAKER TOTAL COMPUTED LOAD: 37270 VA (155 AMPS, 120/24OV) ** HANDLE TIE (NEC 210.4(8)) FEEDER: 3- #4/0, #'2(G) IN 2" NIP. *** THRU LTG. CONTROLS LOADS 19 LOAD 30 LOAD V TOTAL MAIN j1 - 11640 11640 . MAIN J2 6380 12135 18515 PANEL 'L' 38000 - 38000 CONTINUOUS: (INCL) 25X LRGST MTR: ILMJO 2910 2910 TOTAL 43900 26685 71065 VA SL AS • AT 240V 183 64 r 247 AMPS HEATER SERVICE: DISC. A0 do CO: 400 kcml 30 BO (HI -LEG): j1/0 3WP COORDINATE SERVICE WORK WITH FPL CUSTOMER PROJECT ENGINEER. USE POLARIS JIPL SERIES PE CELL (ON WALL OUTSIDE ELEC. RM ) N313HEATER: INTERLOC CHEMICAL CONTROLS, ETC. TO RUN CONTR'L k PUMP Y iii V • " V • YVE6V. • • V V V V • ci u • • Y' i•s coo,, u v •r•i tr • • •" e s Y e U :CTRICAL ENGINEER: •�• �� • CONSTRUCTION -0ONSUI:` ANT5 DF FLCR-IPA ly.i G� u • Ell 5351 RECREATIONAL DESIGN AND CONSULTING ENGINEERS CONSTRUCTION, INC. 1445 S.W. 21st Avenue 3990 North Powerline Road Fort Lauderdale, Florida Ft. Lauderdale, FL 33309 (954) 584-7904 Voice: 954.566.3885 E t DRAmm ARE THE INTELLEMAL Fax: 954.566.3335 OM OF CWWMJC M WMK LTM TS ANO MAY K FKPRoDUCm, wr PART OR IN WHOLE MHMJT M4 PSIMSSION. i D o U w o� JU U s V Ld a>r • s J-- F- W LJ W O L6 U w #** LAJJ I > Li ` 0 z� o N w 0 J W t a z p w ; cf) CL i c Z U Q co)o 0 111114COQ Z W [L CO o U U a LO k aaw�a "Lo ui I-C o r �•+ Z ti oa Cj) U. W 0� a 0 o w Oct LU F_ Z Seel J J ua U� W z V> `' < Z � LL r A } Luz o p cc Z CO u z , � PROJ`CTNUMBER 3- X12 IN 1/2 C. 113-0401 MS. SHINA RANA, 305-387-6653 INSULATED TAPS (OR EQ). ONLY w/CIRC. PUMP PROVIDE EA. w1 1 SPARE PORT (TO PNL 'L')a SD VAC --LACK 0 FILE No. ; O - �REWIREP - UjCr METER WIREWAY: 6" Sq (min), LENGTH AS REQ'D SR_C1RC, IN �4;,`12(G) i -� w i Q ATTACH TO A0, CO, DRAWN V. J. F. UD D E C r NEUT. k GEC ONLY PUMP I PPA SANIT Z I c� REVIEWED: V.J.F. TO FPL HANDHOLE 400A O VFO D15C. SP IDOSTER I (30) 1 CHECKED : V.J.F. AT BASE OF POLE SURGE MAIN #1 MAIN #2 PANEL 120/240V, 30 A L' L ELCETL CONT'L �3P DISC. 1NTERLOC TO I - 18 U 5-22-��` (OPEN DELTA) 0 3F4w B03F4W 1003F4W (LCE) NF I _;�i 1 O DATE 50 100 (MAIN �3) C 30Al2P RUN ONLY I - � i 2 I � w/CIRC. PUMP I iI_' I n z ISSUE[REVISIONS EXTEND GEC TO EACH ~ (CL FUSES) (CL FUSES) Lw N3R w F - -1 D1 D2 D2 10 E1 i __ a iF MAIN, per NEC 250.24(0) A MAIN 11 / MAIN �2 � I Ln '"'" INTERSYSTEM GRD. BUS D 1 E 1 (FURN w/ POOL _ �P50) SOL CU (TO PNL 'L') I ' S I O Z 114 x2 x 12 (NEC 250.94) S/A EQUIP, INSTALL DI I - OL NND'G 12(G) AVAILABLE FAULT CURRENT AT THE SECONDARY OF FPL'S AERIAL J6 CU (MIN) J SP CIRC PUMP YAC PACK FY EC), 2_ 11Z12- - �8 I - 8 0 TRANSF IS 30,684 AMPS(sym). (DATA FURNISHED BY FPL.) IN 1/2" _ _ _ CALC'D. AFC AT METER 1S <11,000 AMPS(sym). C P INSTALL SURGE PROTECTOR, INSTALL SURGE PROTECTOR NOTE:8*-* AND - BASED ON DISTANCES do WIRE SIZE SHOWN. v� EQ. TO SqD JSDSA3650 AT PANEL, EQ. TO SqD SEE POOL EQUIPMENT AND MECHANICAL COMPONENTS MAINS SHALL BE RATED A MINIMUM OF 50K AMPS WITH o jSDSA1175 DRAWINGS FOR LOCATIONS OF ALL WITHIN REJECTION CLIPS k CURRENT LIMITING (FUSETRON) FUSES. o BURIED EQUIPMENT, PUMPS, ETC. FOUNDATION (PER NEC 430) CZ PANEL L SHALL BE RATED FOR 22,O00A (sym). METAL " ,n CWP (**) STEEL A 2- 400 kcml, 11/0 (60), J410(N) IN 3 C. POOL: 6' 2- 400 kcml,1 f0, X4/0 IN 2" NIP. 10 HP, 240V, 30, FLC = 28A (TBL 430.250) MIN. 28A x 1.25 = 35A (J8 THWN) 0 C (SEE PANEL SCHEDULE) 25A x 1.75 = 49 -> 50A DE FUSE (430.52.C) GROUND SERVICE TO FOUND'N. STEEL, 6 18(G) IN 1" NIP. P- H K (VAK PACK): 5/8"x10' CU -CLAD GRD. ROD AND METAL D 4- O FLC = 22A O S H E E T T I T L E 7.5 HP, 240V, 30, C.W.P. (** IF AVAILABLE) D1 4- J8, 110(G) IN 1" C. 22A x 1.25 = 28A (J10 THWN) ELECTRICAL RISER D2 3- J8, j1o(G) IN 1" C. 22A x 2.5 = 55 -> 60A C.B. 0 ELECTRIC NOTES, 2 HP, 40V, 10, - SCHEDULES and 2 FLC - 12A (7 -BL 430.248) (N.TS.) E 4- J2, 16(G) IN 1-1/4" NIP. 12A x 1.25 = 15A (114 THWN) RISERS PP 12A x 2.5 = 30A C. B. El 4- J2, #8((;) IN 1-1/2 C. F 4- 112, J12(G) IN 1/2" C. G 11/0 CU r- n1irr•r KI ii henr-n