13-749-100• GENERAL ELECTRICAL NOTES:
1. ELECTRIC RUNS SHOWN ARE DIAGRAMMATIC, ACTUAL ROUTING SHALL BE COORDINATED WITH FIELD CONDITIONS
AND OTHER TRADES. DO NOT SCALE ELECTRICAL DRAWINGS.
2, ALL CONDUITS SHALL BE 1/2" MINIMUM ABOVE GRADE (314" UNDERGROUND) UNLESS OTHERWISE NOTED (UON).
J. ALL WIRE SHALL BE THHNITHWN COPPER, MINIMUM SIZE 112 (LION). ALUMINUM CONDUCTORS ARE NOT
PERMITTED.
4. NAMEPLATES SHALL BE PROVIDED AT ALL MAINS AND SWITCHES AND OTHER CONTROL DEVICES WHERE THE LOAD
CONTROLLED IS NOT READILY APPARENT.
5. CONTRACTOR SHALL BALANCE LOADS ACROSS ALL SYSTEM PHASE LEGS AND ON SINGLE PHASE, 3 -WIRE SYSTEMS.
6. ALL MATERIALS, EQUIPMENT AND INSTALLATIONS SHALL COMPLY WITH THE LATEST EDITION OF THE FLORIDA
BUILDING CODE (FBC) AND THE 2011 NATIONAL ELECTRICAL CODE (NEC).
7. ELECTRICAL WORK SHALL BE PERFORMED BY A LICENSED AND INSURED ELECTRICAL CONTRACTOR. CONTRACTOR
SHALL PROVIDE EVIDENCE OF PROPERTY DAMAGE AND PUBLIC LIABILITY INSURANCES.
8. CONDUITS SHALL BE RUN CONCEALED IN ALL FINISHED AREAS. EXPOSED CONDUITS SHALL BE RUN NEAT AND
EITHER PARALLEL OR PERPENDICULAR TO WALLS dc CEILINGS.
9. EMT MAY BE USED ABOVE GRADE AND OUT OF WEATHER WHEN PERMITTED BY CODE. SCH 40 PVC MAY BE
USED UNDERGROUND (UG), WHERE NOT SUBJECT TO PHYSICAL DAMAGE, HEAT OR SUNLIGHT.
10. EXPOSED EXTERIOR CONDUIT SHALL BE RIGID METAL (RMC) OR INTERMEDIATE METAL CONDUIT (IMC). SCH 80
PVC MAY BE USED WHERE NOT SUBJECT TO PHYSICAL DAMAGE.
11. ALL EXPOSED TRANSITIONS FROM UNDERGROUND PVC SHALL BE RMC OR IMC CONDUIT FROM 18" BELOW GRADE
INCLUDING NINETY. WHERE A RACEWAY ENTERS A BUILDING FROM UNDERGROUND, IT SHALL BE SEALED PER NEC
INCLUDING SPARES.
12. ALL ELECTRIC EQUIPMENT ENCLOSURES SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL.
13. OBTAIN ENGINEERS' APPROVAL PRIOR TO PENETRATING STRUCTURAL MEMBERS.
14. IN THE EVENT FIELD CONDITIONS DIFFER FROM CONTRACT DOCUMENTS, FIELD CONDITIONS SHALL GOVERN.
15. THE CONTRACTOR SHALL IMMEDIATELY REPAIR ANY DAMAGE CAUSED TO EXISTING FACILITIES.
16. MISC. ITEMS OBVIOUSLY REQUIRED FOR A COMPLETE AND OPERATING SYSTEM BUT NOT SPECIFICALLY CALLED FOR
ON THE DRAWINGS OR IN THE SPECIFICATIONS SHALL BE PROVIDED BY THE CONTRACTOR AT NO EXTRA COST TO
THE OWNER. (NUTS, BOLTS, MASONRY ANCHORS, CONDUIT AND EQUIP. SUPPORTS, DRILLING, WELDING,
SCAFFOLDING, CRANE SERVICE, ETC.)
17. GROUND ALL SYSTEMS AND EQUIPMENT PER NEC 1250.
18. ANY EXTERIOR RECEPTACLES SHOWN ON THESE PLANS SHALL BE 20 AMP, WEATHER RESISTANT, SIDE WIRED WITH
WP ENCLOSURES WITH "EXTRA DUTY" SAFETY COVER PER NEC J406.9(B).
19. ALL DISCONNECT SWITCHES SHALL BE SIZED FOR THE LOAD SERVED AND SHALL BE HP RATED, HEAVY DUTY •
(UON).
20. PANELS, PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL CENTERS, ETC. SHALL HAVE COPPER BUS AND SHALL
BE MARKED AS REQUIRED BY NEC 110-16, 110.24 AND 408.4(8).
21. ALL FUSES SHALL BE CURRENT LIMITING (UON). USE TIME DELAY FOR MOTOR,CIRCUITS AND NON -TD FOR
MAINS.
22. VERIFY EQUIPMENT CURRENT INTERRUPTING RATINGS FOR ALL EQUIPMENT PRIOR TO CONSTRUCTION.
23. CLOSELY COORDINATE ALL SERVICE ENTRANCE WORK WITH ELECTRIC UTILITY COMPANY.
24. CLOSELY COORDINATE TELEPHONE SERVICE WORK WITH TELEPHONE UTILITY COMPANY.
25. UPON COMPLETION OF WORK, CONTRACTOR SHALL FULLY INSTRUCT OWNER'S REPRESENTATIVE IN COMPLETE
OPERATION OF ALL ELECTRICAL SYSTEMS.
26. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FOR A MINIMUM OF ONE YEAR FROM DATE OF
ACCEPTANCE.
• 27. PROVIDE A FUSE HOLDER AND FUSE IN THE PRIMARY SIDE OF EACH UNGROUNDED CONDUCTOR OF ALL BALLASTS
OR TRANSFORMERS. HOLDERS IN POLES SHALL BE BUSSMAN "HEB" SERIES, OR EQ.
28. ALL UNDERGROUND CONDUITS SHALL BE BURIED WITH A MINIMUM OF 18" COVER. FPL SERVICES SHALL BE 24"
MINIMUM. FPL PRIMARY CONDUITS SHALL BE INSTALLED ACCORDING TO FPL SPECIFICATIONS.
29. DISTANCE BETWEEN PULL BOXES SHALL NOT EXCEED 400' AND MAY BE INSTALLED WHERE REQUIRED BY
CONTRACTOR FOR EASE OF INSTALLATION.
30. ALL METAL JUNCTION BOXES AND PULL BOXES SHALL BE GROUNDED.
31. ALL ABOVE GROUND WP JUNCTION BOXES SHALL BE GALVANIZED NEMA 3R.
32. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY AND LOCATE ALL EXISTING UG FACILITIES INCLUDING ELECTRIC
POWER, TELEPHONE, CAN, WATER, SEWER, GAS, FLOOD/STORM DRAINAGE, IRRIGATION OR ANY EXISTING UG
SYSTEM PRIOR TO ANY EXCAVATIONS.
33. TRENCHES SHALL BE BACKFILLED AND TAMPED TO ORIGINAL DENSITY.
34. RESTORE ALL EXCAVATED k TRENCHED AREAS TO ORIGINAL CONDITIONS, INCLUDING SOD, PAVING, PLANTINGS, ETC.
35. BEFORE FINAL PAYMENT THE CONTRACTOR SHALL PROVIDE TO THE OWNER A COMPLETE SET OF AS -BUILT
DRAWINGS. THESE DRAWINGS SHALL INCLUDE MEASUREMENTS OF UG CONDUITS AND PULL BOXES MEASURED TO
PERMANENT STRUCTURES OR LANDMARKS.
36. ALL H.I.D. LAMPS SHALL INCLUDE MINIMUM 1 YEAR WARRANTY.
37. CL2, CHEMICAL CONTROLLERS AND BOOSTER PUMPS SHALL BE ELECTRICALLY INTERLOCKED WITH THE FILTER
PUMP MOTOR CIRCUIT TO OPERATE ONLY WHEN FILTER PUMP OPERATES. EQUIPMENT ROOM EXH. FAN SHALL BE
CONNECTED TO OPERATE CONTINUALLY OR WHEN FILTER PUMP OPERATES.
38. ALL METAL POOL STRUCTURES, FITTINGS, EQUIPMENT, LIGHTING, PUMPS, HEATERS AND ENCLOSURES SHALL BE
BONDED WITH A J8 SOLID CU CONDUCTOR PER NEC 1680.26 0c FBC.
39. UNDERGROUND WIRING SHALL NOT BE RUN UNDER OR WITHIN 5' OF INSIDE WALL OF POOL (NEC 680.10).
40. PUMP MOTOR STARTERS SHALL BE EQUIPPED WITH HAND -OFF -AUTOMATIC SWITCHES.
41. ALL 15 AND 20 AMP, 120V PUMP CIRCUITS SHALL BE PROTECTED WITH GFCI (NEC 680.22.B).
314" C. (TYP)
4' x4' x314" BACKBOARD,
MARINE PLYWOOD PAINTED
GRAY, BOTTOM AT 12" AFF.
16 CU TO GRD.
RUN CONDUIT TO ALL
OUTLETS is INSTALL
PULL STRING 2" PVC w/PULL STRING
(TO PROP/LINE)
TELEPHONE RISER
(COORD. ALL WORK w/ ATT)
BROOKS 136
CONC. HANDHOLE & BOLT DOE LID WIRES MUST NOT BEAR
(OR APPROVED EQ.) \ ON BOX LID OR SIDES.
\ - - GRADE
RESIN -CAST WATERPROOF C307_ -
SPLICES OR POLARIS BLUE SPLICES
(SUITABLE FOR WET LDC). 1
id" MIN.
EQUIP. GROUNDING CONDUCTOR o 0 0 0
40
CRUSHED ROCK AT BOTTOM o • + a
OF JUNCTION BOX.
CONCRETE HANDHOLE TYP.
(N.T.S.)
• HANDHOLE ENCLOSURES PER NEC1314.30. CONDUCTORS Jc SPLICES
SHALL BE SUITABLE FOR WET LOCATIONS (314.30(C))
.1
1 �-
(CONTROL)
OL) (CKT: L-6) ��
PE PE CELL
ti PE
C1
ELEC. HELD LTG. CONTACTORS (SIZE
jc POLES PER SCHEDULE)
CI
LIGHTING CONTROL DIAGRAM
(N.T.S.)
LTG. CONTACTOR SCHEDULE
Sw. LCI AMP/POLE LOAD CKT.
PE 1 30 3 SECURITY LTG. L-6 & d
ALL CONTACTORS SHALL BE EQUAL TO SqD CLASS 8903,
TYPE L, ELECT HELD WITH 120V COIL, MOUNT IN LTG.
CONTROL ENCLOSURE (LCE).
P/E -CELL SHALL BE EQUAL TO INTERMATIC IK4200 SERIES
AND SHALL FACE NORTH AND BE LOCATED AWAY FROM (OR
SHIELDED) FROM ARTIFICIAL LIGHT SOURCES.
LTG. CONTROL ENCLOSURE SHALL BE UL LISTED, N-1,
HINGED AND LOCKED WITH BACK PANEL FOR MOUNTING EQUIP,
F
LOAD SUMMARY:
TYPE SqD 'NQ' (OR EQ.) PANEL L MAIN BUS 225 AMP
SERVICE 120/240V, 10,3W NEUTRAL FULL
MOUNTING SURF MAIN 225A MCB
POLE 42 AIC 22,000
BKR
COND.
WIRE
REMARKS
CK
VA
CK
REMARKS
WIRE
COND.
BKR
CONTINUOUS: (INCL)
25X LRGST MTR: ILMJO 2910
2910
^
C
TOTAL 43900 26685
71065 VA
SL AS
• AT 240V 183 64 r
2011*
1/2"
J12
BECS CONTROLS
1
1600
580
2
LIGHTING
112
112"
20/1
2011*
112-1112
CL FEEDER
3
1
19004
580
LIGHTING
J12
112"
2011
30/1
1/2"
J12
BOOSTER PUMP (314 HP)
5
1920
300
6
EXT. LIGHTING ***
J12
112"
2011
20/1 *
314"
J12
HEATER CONTROLS
7
500
No
8
POOL LT Tx. (LED) ***
J10
3/4" 12011*
2011*
112
HEATER PUMP
9
1650
10
RECEPTS
112
112"
2011
20/1
112"
J10
HAND DRYER
11
2300
12
RECEPTS
112
112"
2011
2011 1
112"
110
HAND DRYER
13
2300
540
14
RECEPTS
112
112"
2011
20/1
112"
110
HAND DRYER
15
2300
540
16
RECEPTS
112
112"
2011
2011
3/4"
110
WP DECK RECEPTS.
17
360
18
DRINKING FOUNT.
112
112"
2011
20/1
3/4"
110
WP DECK RECEPTS.
1920
160.0
1 RECEPT. VENDING
j12
1/2"
2011
20/1
1/2"
112
RECEPTS.
21
540
22
RECEPT, VENDING
112
112"
2011
2011
112"
112
TELEPHONE
23
360
24
RECEPT. VENDING
112
112"
2011
20/1
112"
112
EX FAN J1
25
700 1300
1050
1300
26
28
AC RECEPT
J12
112"
2012
2011
112"
112
EX FANS 2 k 3
27
2011
112"
112
GAS WATER HTR.
29
500
1250
30
SPARE
-
-
2011
2011
1/2"
112
IRRIG. CTLS.
31
300
1250
32
SPARE
-
-
2011
20/1
-
-
SPARE
33
250
1 _
34
SPACE
2011
-
-
SPARE
35
1250
36
--
-
-
SPACE
37
38
39
_
-
40
42
SURGE PROTECTION
(INCL)
(INCL)
2012
41
TOTAL CONNECTED LOAD: 36200 VA 18050 18150
25% LARGEST MOTOR: 480
CONTINUOUS AT 25%: 59 * GFCI BREAKER
TOTAL COMPUTED LOAD: 37270 VA (155 AMPS, 120/24OV) ** HANDLE TIE (NEC 210.4(8))
FEEDER: 3- #4/0, #'2(G) IN 2" NIP. *** THRU LTG. CONTROLS
LOADS 19 LOAD 30 LOAD
V
TOTAL
MAIN j1 - 11640
11640
.
MAIN J2 6380 12135
18515
PANEL 'L' 38000 -
38000
CONTINUOUS: (INCL)
25X LRGST MTR: ILMJO 2910
2910
TOTAL 43900 26685
71065 VA
SL AS
• AT 240V 183 64 r
247 AMPS
HEATER
SERVICE:
DISC.
A0 do CO: 400 kcml
30
BO (HI -LEG): j1/0
3WP
COORDINATE SERVICE WORK WITH
FPL CUSTOMER PROJECT ENGINEER. USE POLARIS JIPL SERIES
PE CELL (ON WALL
OUTSIDE ELEC. RM )
N313HEATER:
INTERLOC CHEMICAL
CONTROLS, ETC. TO RUN
CONTR'L
k PUMP
Y
iii V • " V • YVE6V.
• • V V
V V • ci u • • Y'
i•s coo,, u v •r•i tr • •
•" e s Y e U
:CTRICAL ENGINEER: •�• �� •
CONSTRUCTION
-0ONSUI:` ANT5
DF FLCR-IPA ly.i G� u •
Ell 5351
RECREATIONAL
DESIGN AND
CONSULTING ENGINEERS CONSTRUCTION, INC.
1445 S.W. 21st Avenue 3990 North Powerline Road
Fort Lauderdale, Florida Ft. Lauderdale, FL 33309
(954) 584-7904 Voice: 954.566.3885
E t DRAmm ARE THE INTELLEMAL Fax: 954.566.3335
OM OF CWWMJC M WMK LTM TS ANO MAY
K FKPRoDUCm, wr PART OR IN WHOLE MHMJT
M4 PSIMSSION. i
D
o
U
w
o�
JU U
s V
Ld a>r • s
J--
F- W
LJ
W O
L6 U
w #**
LAJJ
I > Li `
0 z�
o N
w
0
J W
t
a
z p
w ; cf)
CL i
c Z U Q
co)o
0 111114COQ
Z W
[L CO
o U U a
LO
k aaw�a "Lo ui
I-C o
r �•+ Z
ti oa
Cj) U.
W
0� a
0
o
w Oct
LU
F_
Z Seel
J
J ua
U� W
z V> `' < Z
� LL
r A }
Luz
o p
cc
Z CO u
z ,
� PROJ`CTNUMBER
3- X12 IN 1/2 C.
113-0401
MS. SHINA RANA, 305-387-6653 INSULATED TAPS (OR EQ). ONLY w/CIRC. PUMP
PROVIDE EA. w1 1 SPARE PORT (TO PNL 'L')a SD VAC --LACK 0 FILE No. ;
O - �REWIREP - UjCr
METER WIREWAY: 6" Sq (min), LENGTH AS REQ'D SR_C1RC, IN �4;,`12(G) i -� w i Q
ATTACH TO A0, CO, DRAWN V. J. F.
UD D E C r
NEUT. k GEC ONLY PUMP I PPA SANIT Z I c� REVIEWED: V.J.F.
TO FPL HANDHOLE 400A O VFO D15C. SP IDOSTER I (30) 1 CHECKED : V.J.F.
AT BASE OF POLE SURGE MAIN #1 MAIN #2 PANEL
120/240V, 30 A L' L ELCETL CONT'L �3P DISC.
1NTERLOC TO I - 18 U 5-22-��`
(OPEN DELTA) 0 3F4w B03F4W 1003F4W (LCE) NF I _;�i 1 O DATE
50 100 (MAIN �3) C 30Al2P RUN ONLY I - � i 2 I �
w/CIRC. PUMP I iI_' I n z ISSUE[REVISIONS
EXTEND GEC TO EACH ~ (CL FUSES) (CL FUSES)
Lw N3R w
F - -1 D1 D2 D2 10 E1 i __ a iF
MAIN, per NEC 250.24(0) A MAIN 11 / MAIN �2 � I Ln '"'"
INTERSYSTEM GRD. BUS D 1 E 1 (FURN w/ POOL _ �P50)
SOL CU (TO PNL 'L') I ' S I O Z
114 x2 x 12 (NEC 250.94) S/A EQUIP, INSTALL DI I
- OL NND'G 12(G)
AVAILABLE FAULT CURRENT AT THE SECONDARY OF FPL'S AERIAL J6 CU (MIN) J SP CIRC PUMP YAC PACK FY EC), 2_ 11Z12- - �8 I - 8 0
TRANSF IS 30,684 AMPS(sym). (DATA FURNISHED BY FPL.) IN 1/2" _ _ _
CALC'D. AFC AT METER 1S <11,000 AMPS(sym). C P INSTALL SURGE PROTECTOR, INSTALL SURGE PROTECTOR NOTE:8*-* AND -
BASED ON DISTANCES do WIRE SIZE SHOWN. v� EQ. TO SqD JSDSA3650 AT PANEL, EQ. TO SqD SEE POOL EQUIPMENT AND MECHANICAL COMPONENTS
MAINS SHALL BE RATED A MINIMUM OF 50K AMPS WITH o jSDSA1175 DRAWINGS FOR LOCATIONS OF ALL WITHIN
REJECTION CLIPS k CURRENT LIMITING (FUSETRON) FUSES. o BURIED EQUIPMENT, PUMPS, ETC.
FOUNDATION (PER NEC 430) CZ
PANEL L SHALL BE RATED FOR 22,O00A (sym). METAL "
,n CWP (**) STEEL A 2- 400 kcml, 11/0 (60), J410(N) IN 3 C. POOL:
6' 2- 400 kcml,1 f0, X4/0 IN 2" NIP. 10 HP, 240V, 30, FLC = 28A (TBL 430.250)
MIN. 28A x 1.25 = 35A (J8 THWN) 0
C (SEE PANEL SCHEDULE) 25A x 1.75 = 49 -> 50A DE FUSE (430.52.C)
GROUND SERVICE TO FOUND'N. STEEL, 6 18(G) IN 1" NIP. P- H K (VAK PACK):
5/8"x10' CU -CLAD GRD. ROD AND METAL D 4- O FLC = 22A O S H E E T T I T L E
7.5 HP, 240V, 30,
C.W.P. (** IF AVAILABLE) D1 4- J8, 110(G) IN 1" C. 22A x 1.25 = 28A (J10 THWN)
ELECTRICAL RISER D2 3- J8, j1o(G) IN 1" C. 22A x 2.5 = 55 -> 60A C.B. 0 ELECTRIC NOTES,
2 HP, 40V, 10, - SCHEDULES and
2 FLC - 12A (7 -BL 430.248)
(N.TS.) E 4- J2, 16(G) IN 1-1/4" NIP. 12A x 1.25 = 15A (114 THWN) RISERS
PP 12A x 2.5 = 30A C. B.
El 4- J2, #8((;) IN 1-1/2 C.
F 4- 112, J12(G) IN 1/2" C.
G 11/0 CU
r- n1irr•r KI ii henr-n