13-749-041LIFE -SAFETY LEGEND
�� -- ILLUMINATED EXIT LIGHT
( > DIRECTION OF TRAVEL)
-- FIRE EXTINGUISHER -WALL MOUNTED
F.EX
FEWC -- FIRE EXTINGUISHER
CABINET WALL MOUNTED
-- EMERGENCY WALL MOUNTED LIGHT
EM.� -- EMERGENCY DISCONNECT
- FIRE SIAMESE CONNECTION
(WALL OR HYDRANT)
--
2X4 EMERGENCY FLUORESCENT
MARK
LIGHT FIXTURE
--
1X4 EMERGENCY FLUORESCENT
LLJ
LIGHT FIXTURE
FEC A
EMERGENCY FLUORESCENT STRIP
H0
LIGHT FIXTURE
„� --
EMERGENCY WALL MTD.
Q102
FLUORESCENT STRIP LIGHT FIXTURE
--
RECESSED EMERGENCY
z
HIGH HAT LIGHT FIXTURE
1 1- NUMBER OF OCCUPANTS LEAVING
2- REQUIRED WIDTH (inches)
3- PROVIDED WIDTH (inches)
I I mem I I m2w 2 -HOUR WALL
SEPARATION RATING
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII EXIT PATH
ROOM Room Name Top Room
NAME Name Bot Room Number
RN Program SF/Actual SF
SF Life Safety SF Life
(#SF/OCCUPANT) Safety SF/Occupants
# OCCUPANTS Life Safety Occupants
TABLE 602
EXTERIOR NON BEARING WALLS:
BUILDING SEPARATION:
PROTECTION OF VERTICAL OPENINGS
STAIRS
PROTECTION OF VERTICAL OPENINGS
W MAXIMUM TRAVEL DISTANCE -
W UNSPRINKLED
cc EGRESS WIDTH PER PERSON:
w
TABLE 601
0" TO 10'-0" = 1 HOUR RATING
10'-0" > = 0 HOUR RATING
N/A
N/A
200 FEET
TABLE 1015.1)
(TABLE 1005.1)
0.2" / PERSON x 340 OCC. = 68"
(2) 48" GATES PROVIDED = 96"
EIRE
FLORIDA BUILDING CODE 2010
MARK
Q
FLORIDA FIRE PREVENTION CODE
GENERAL MULTI- 2A -108C A,B,C
LLJ
FBC PLUMBING CODE 2010
FEC A
08 .05.13
H0
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER SHALL NOT EXCEED 75'-0"
Q
RE: 7-6.3.2.5 (PER F.F.P.C.-'01)
Q102
ELECTRICAL CARBON 20 BC B,C
BUILDING: ASSEMBLY - GROUP A-5
ROOMS DIOXIDE
z
SHALL BE REQUIRED WHERE ALL ENERGIZED ELECTRICAL EQUIPMENT CAN BE
U Q
ENCOUNTERED. RE: 7--6.3.5 (PER F.F.P.C.-'01)
MAXIMUM HEIGHT:
ACTUAL HEIGHT:
0
55' TOTAL HEIGHT AT UNLIMITED STORIES
13'--9 1/2" ACTUAL HEIGHT AT 1 STORY
TOTAL OCCUPANT LOAD - 340 OCC.
TYPE OF CONSTRUCTION:
TYPE IIB (TABLE 503)
z
POOL TOTAL AREA: 4,220 SF
MALE
FEMALE
1 STORY, UNSPRINKLERED: 1,358 SIF
SIZE
C'3
CMU WALLS WITH STUCCO, PREFABRICATED
METAL JOIST WITH METAL DECK ROOF
z
STRUCTURE
4
2,501 SF - 5,000 SF (REQUIRED)
2
1
OJ
BUILDING AREA:
1
D
INTERIOR AREA: 1,246 S.F. (ROOMS: 1,111
SF) (WALLS: 204 SF)
❑
EXTERIOR OVERHANGS: 310 SF
UNISEX
EXTERIOR PATIOS: 6,202 SF
FEMALE
DETAILED CONSTRUCTION REQUIREMENTS: TABLE 601
W.C.
TYPE IIB
URINAL
W.C.
FIRE RESISTANEC RATINGS OF STRUCTURAL
MEMBERS:
LAVATORY
INTERIOR BEARING WALLS:
0 HRS.
1
COLUMNS:
0 HRS.
2
BEAMS:
0 HRS.
3
FLOORS:
0 HRS.
U _j
ROOF:
0 HRS.
EXTERIOR BEARING WALLS:
0 HRS. (NON COMBUSTIBLE)
NON BEARING INTERIOR WALLS:
0 HRS. (NON COMBUSTIBLE)
TABLE 602
EXTERIOR NON BEARING WALLS:
BUILDING SEPARATION:
PROTECTION OF VERTICAL OPENINGS
STAIRS
PROTECTION OF VERTICAL OPENINGS
W MAXIMUM TRAVEL DISTANCE -
W UNSPRINKLED
cc EGRESS WIDTH PER PERSON:
w
TABLE 601
0" TO 10'-0" = 1 HOUR RATING
10'-0" > = 0 HOUR RATING
N/A
N/A
200 FEET
TABLE 1015.1)
(TABLE 1005.1)
0.2" / PERSON x 340 OCC. = 68"
(2) 48" GATES PROVIDED = 96"
EIRE
EXTINGUISHER LEGEND
MARK
USE TYPE U/L RATING CLASS OF FIRE
❑
GENERAL MULTI- 2A -108C A,B,C
Oz
PURPOSE PURPOSE
FEC A
08 .05.13
H0
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER SHALL NOT EXCEED 75'-0"
RE: 7-6.3.2.5 (PER F.F.P.C.-'01)
Q102
ELECTRICAL CARBON 20 BC B,C
d.D
ROOMS DIOXIDE
FFC O
SHALL BE REQUIRED WHERE ALL ENERGIZED ELECTRICAL EQUIPMENT CAN BE
U Q
ENCOUNTERED. RE: 7--6.3.5 (PER F.F.P.C.-'01)
NOTE: FIRE EXTINGUISHERS SHALL BE MOUNTED AT MAX HEIGHT OF 48" TO THE
TOP OF THE EXTINGUISHER.
1 LIFE SAFETY FLOOR PLAN
LS -200
SCALE: 1/41 =1'-0'
Cf?
4 2 0 4 8 "�-
L�.^I
SCALE: 1/4"=l' -O"
UNIT OF MEASURE: FEET ZD
U
LIFE SAFETY NOTES
1. ALL NEW CONSTRUCTION IS CONSIDERED ASSEMBLY OCCUPANCY, TYPE II B CONSTRUCTION
2. ALL NEW CONSTRUCTION, WORK SHALL COMPLY WITH FLORIDA BUILDING CODE 2010
3. MAXIMUM TRAVEL DISTANCE = 20OFT.
4. MAXIMUM DEAD END = 20FT.
5. MAXIMUM CONTINUOUS PATH OF TRAVEL = 75FT.
6. MINIMUM DOOR WIDTH = 32 INCHES
7. ALL EXISTING BUILDING RATINGS SHALL BE MAINTAINED IN CONFORMANCE WITH EXISTING
CONDITIONS. ALL AREAS WHERE DISCREPANCIES ARE DISCOVERED DURING CONSTRUCTION
SHALL BE REPAIRED.
8. PROVIDE "MAXIMUM OCCUPANCY - XX" SIGN AT ALL LOCATIONS WHERE OCCUPANT LOAD
EXCEED 50, SEE LS DRAWINGS, REFER TO LS AND ID DRAWINGS FOR SIGN LOCATIONS.
9. ALL SMOKE DETECTORS IN TOILET ROOMS TO BE TAMPER PROOF. ALL FIRE ALARM
DEVICES IN OCCUPIED AREAS AND EXTERIOR TO BE PROVIDED WITH APPROVED PROTECTIVE
COVER.
10. NO LOUVERS ARE TO BE PROVIDED IN DOORS AT SMOKE PARTITIONS PER FBC.
11. PROVIDE REQUIRED GASKET AT ALL DOORS IN SMOKE PARTITIONS PER FBC, CH. 7 SECT.
710.5.2.
12, PROVIDE SMOKE DETECTORS IN ALL NON -OCCUPIED SPACES.
r
RECREATIONAL
DESIGN AND
CONSTRUCTION, INC.
3990 North Powerline Ror d
Ft. Lauderdale, FL 33309
Voice: 954.566.3885
Fax: 954.566.3335
AREA NAME TOTAL S.l S.F. OCC. OCCUPANCY OCC. LOAD
EE
POOL 4,220 ASSEMBLY 90
❑
POOL DECK 6,202 30 ASSEMBLY 207
Oz
SPLASH DECK 1,062/30 ASSEMBLY 36
X _C
V V
08 .05.13
H0
ROOM No. ROOM NAME TOTAL S.F. S.F. OCC. OCCUPANCY OCC. LOAD
101 VENDING AREA 42 100 ASSEMBLY 1
Q102
TICKETS LIFE GUARDS OFFIC 290/100 BUSINESS 3
d.D
103 MALE TOILET 256 ASSEMBLY -
❑ C)
104 UNISEX TOILET 49 ASSEMBLY -
U Q
105 FEMALE TOILET 291 ASSEMBLY -
(� V
106 POOL EQUIPMENT ROOM 148 100 INDUSTRIAL 1 2
0
107 ELECTRICAL ROOM 40/100 INDUSTRIAL 1 1
c3
TOTAL OCCUPANT LOAD - 340 OCC.
PLUMBING FIXTURE CALCULATIONS PER POOL AREA
TABLE 424.1.6.1 SWIMMING POOL
z
POOL TOTAL AREA: 4,220 SF
MALE
FEMALE
0
SIZE
URINAL
W.C.
LAVATORY
W.C.
LAVATORY
4
2,501 SF - 5,000 SF (REQUIRED)
2
1
1
5
1
0
J
Q
0
AS PER FBC 424.1.6.1.1 FIXTURES SHALL BE PROVIDED AS INDICATED ON TABLE 424.1.6.1.
THE FIXTURE COUNT ON THIS CHART IS DEEMED TO BE ADEQUATE FOR THE POOL AND
POOL DECK AREA THAT IS UP TO THREE TIMES THE AREA OF THE POOL SURFACE
PROVIDED. (POOL DECK IS 7,595 S.F.)
0
z
TOTAL PLUMBING FIXTURES PROVIDED
Ln
UNISEX
MALE
FEMALE
W.C.
LAVATORY
URINAL
W.C.
LAVATORY
W.C.
LAVATORY
J
a
TOTAL PROVIDED
1
1
2
2
3
5
3
SERVICE SINK: 1 PROVIDED (POOL EQUIPMENT ROOM)
Cf?
4 2 0 4 8 "�-
L�.^I
SCALE: 1/4"=l' -O"
UNIT OF MEASURE: FEET ZD
U
LIFE SAFETY NOTES
1. ALL NEW CONSTRUCTION IS CONSIDERED ASSEMBLY OCCUPANCY, TYPE II B CONSTRUCTION
2. ALL NEW CONSTRUCTION, WORK SHALL COMPLY WITH FLORIDA BUILDING CODE 2010
3. MAXIMUM TRAVEL DISTANCE = 20OFT.
4. MAXIMUM DEAD END = 20FT.
5. MAXIMUM CONTINUOUS PATH OF TRAVEL = 75FT.
6. MINIMUM DOOR WIDTH = 32 INCHES
7. ALL EXISTING BUILDING RATINGS SHALL BE MAINTAINED IN CONFORMANCE WITH EXISTING
CONDITIONS. ALL AREAS WHERE DISCREPANCIES ARE DISCOVERED DURING CONSTRUCTION
SHALL BE REPAIRED.
8. PROVIDE "MAXIMUM OCCUPANCY - XX" SIGN AT ALL LOCATIONS WHERE OCCUPANT LOAD
EXCEED 50, SEE LS DRAWINGS, REFER TO LS AND ID DRAWINGS FOR SIGN LOCATIONS.
9. ALL SMOKE DETECTORS IN TOILET ROOMS TO BE TAMPER PROOF. ALL FIRE ALARM
DEVICES IN OCCUPIED AREAS AND EXTERIOR TO BE PROVIDED WITH APPROVED PROTECTIVE
COVER.
10. NO LOUVERS ARE TO BE PROVIDED IN DOORS AT SMOKE PARTITIONS PER FBC.
11. PROVIDE REQUIRED GASKET AT ALL DOORS IN SMOKE PARTITIONS PER FBC, CH. 7 SECT.
710.5.2.
12, PROVIDE SMOKE DETECTORS IN ALL NON -OCCUPIED SPACES.
r
RECREATIONAL
DESIGN AND
CONSTRUCTION, INC.
3990 North Powerline Ror d
Ft. Lauderdale, FL 33309
Voice: 954.566.3885
Fax: 954.566.3335
I
C)
7—"
" (Y) Q
00
LO
.E
cc,'
Q
to
I
r
Seal
•.*` •� Y
G x..2013
Jose M r9uido, RA
Re . o. AR -10670
PROJECT NUMBER
1320MPCP
FILE No. :
EE
DRAWN
DRAWN
REVIEWED:
CHECKED
X.X.X.
X.X.X.
X.X.X.
i,
u u
07-02-13
ISSUE / REVISIONS
X _C
V V
08 .05.13
FIRE DEPARTM _NT
FNTS
V V
IL
H N
lL 19
6 3
3
U,
�J
c3
u 3
U-1
n .-
ry N
Li 'q
M N
0 0
O O
I
t �
I
M n
V M
C M
U _j
II
I
C)
7—"
" (Y) Q
00
LO
.E
cc,'
Q
to
I
r
Seal
•.*` •� Y
G x..2013
Jose M r9uido, RA
Re . o. AR -10670
PROJECT NUMBER
1320MPCP
FILE No. :
--------
----_---
DRAWN
DRAWN
REVIEWED:
CHECKED
X.X.X.
X.X.X.
X.X.X.
i,
D A T E
07-02-13
ISSUE / REVISIONS
08 .05.13
FIRE DEPARTM _NT
FNTS
SHEET TITLE
LIFE SAFFT""
FLOOR PLA;1
I' SHEET NUMBER
LS—lulu