13-749-0401 - - ri -- PROJECT LIMIT LINE „ PROJECT LIMIT LINE.-- ', L2 m r Lu J= 1 0.2 O i 0 w LL_ LIFE SAFETY NOTES CODES: 2010 FLORIDA BUILDING CODE 2010 FLORIDA FIRE PROTECTION CODE 1. NEW BUILDING IS ASSEMBLY OCCUPANCY. 2. NEW BUILDING IS TYPE II -B CONSTRUCTION. 3. FIRE RESISTANCE CRITERIA : ALL BUILDING ELEMENTS MUST MEET CRITERIA AS PER TABLE 601 FBC. EXTERIOR -AND INT RIOR COLUMNS AND BEARING WALLS SUPPORTING MORE THAN ONE FLOOR OR ROOF SHALL BE 0 HOUR PROTECTED. EXTERIOR AND INTERIOR COLUMNS AND BEARING WALLS SUPPORTING ONE FLOOR OR ROOF SHALL BE 0 HOUR PROTECTED. BEAMS AND FLOOR SYSTEM BETWEEN LEVELS SHALL BE 0 HOUR PROTECTED. 4. LONGEST EXIT DISTANCES PER BUILDING ONLY, ARE SHOWN FOR CLARITY. REFER TO 1/8" LIFE -SAFETY DRAWINGS FOR DETAILS ON ALL SIGNAL DEVICES. 5. NEW BUILDING IS ASSEMBLY OCCUPANCY. OCCUPANCY CALCULATIONS SHOWN ARE BASED ON FBC CHAPTER 424 AND NFPA 101 2010; OFFICE 100 SF/ OCCUPANT POOL DECK 30 SF/ OCCUPANT POOL BY BATHING LOAD SPLASH DECK 30 SF/ OCCUPANT STORAGE / ELECTRICAL 300 SF/ OCCUPANT 6. DRAWINGS LS -100 AND LS -201 ARE OVERALL EXIT PLANS ONLY. PLEASE REFER TO ENLARGED PLANS FOR ALL EMERGENCY DEVICES AND FIRE-EXTINGUISHER LOCATIONS. 3. MAXIMUM ALLOWABLE AREA PER TABLE 500 IS 2 STORIES, 14,500 SQUARE FEET PER FLOOR WITHOUT MODIFIERS. PER 504.2 THE ALLOWABLE HEIGHT IS 3 STORIES AND PER 506.3 THE ALLOWABLE AREA IS 43,500 SQUARE FEET FOR SINGLE STORY CONSTRUCTION AND 29,000 PER FLOOR FOR MULTI STORY. 4. CONSTRUCTION TO CONFORM TO FLORIDA BUILDING CODE CURRENT EDITION AND STATE STATUTES FOR EDUCATIONAL FACILITIES. 5. FIRE ALARM - SEE ELECTRICAL DRAWINGS BUIL©INS SEPAf�ATION: FLORIDA BUILDING CODE 2010 OPENINGS CALCULATIONS FLORIDA FIRE PREVENTION CODE FBC PLUMBING CODE 2010 O BUILDING: ASSEMBLY - GROUP A-5 Q MAXIMUM HEIGHT: ACTUAL HEIGHT: W XXXX TOTAL HEIGHT AT XXXX STORIES 13'-9 1/2" ACTUAL HEIGHT AT 1 STORY EXCEPTION: QTYPE OF CONSTRUCTION: TYPE XXX (TABLE 503) Z 1 STORY, UNSPRINKLERED: 1,358 SF FIRE -RESISTANCE RATED SHALL BE PERMITTED TO HAVE UNLIMITED UNPROTECTED OPENINGS". CMU WALLS WITH STUCCO, PREFABRICATED METAL JOIST WITH METAL DECK ROOF STRUCTURE KEY NOTES: Q FIRE HYDRANT BUILDING AREA: FIRE LANE INTERIOR AREA: 1,246 S.F. (ROOMS: 1,111 SF) (WALLS: 204 SF) ch EXTERIOR OVERHANGS: 310 SF EXTERIOR PATIOS: 6,202 SF (5 OCCUPANT LOAD: BUILDING: 6 m POOL: 90 m POOL DECK: 207 SPLASH DECK: 36 TOTAL OCCUPANT LOAD: 339 MAXIMUM TRAVEL DISTANCE- 200 FEET U) in UNSPRINKLED (TABLE 1015.1) Lu EGRESS WIDTH PER PERSON: (TABLE 1005.1) a 0.2" / PERSON x 339 OCC. = 67.8" W (2) 36" GATES PROVIDED = 72" 3. MAXIMUM ALLOWABLE AREA PER TABLE 500 IS 2 STORIES, 14,500 SQUARE FEET PER FLOOR WITHOUT MODIFIERS. PER 504.2 THE ALLOWABLE HEIGHT IS 3 STORIES AND PER 506.3 THE ALLOWABLE AREA IS 43,500 SQUARE FEET FOR SINGLE STORY CONSTRUCTION AND 29,000 PER FLOOR FOR MULTI STORY. 4. CONSTRUCTION TO CONFORM TO FLORIDA BUILDING CODE CURRENT EDITION AND STATE STATUTES FOR EDUCATIONAL FACILITIES. 5. FIRE ALARM - SEE ELECTRICAL DRAWINGS BUIL©INS SEPAf�ATION: CHECKED X.X.X. OPENINGS CALCULATIONS J DATE 07-02-13 O NOT APPLICABLE J ISSUE / REVISIONS M } f� I a w EXCEPTION: PER FBC 2010 - CH. 7 TABLE 704.8 NOTE G, "BUILDINGS WHOSE EXTERIOR BEARING WALL, EXTERIOR NONBEARING WALL AND EXTERIOR STRUCTURAL FRAME ARE NOT REQUIRED TO BE 1-9 FIRE -RESISTANCE RATED SHALL BE PERMITTED TO HAVE UNLIMITED UNPROTECTED OPENINGS". KEY NOTES: Q FIRE HYDRANT �n FIRE LANE � aa CHECKED X.X.X. J DATE 07-02-13 O J ISSUE / REVISIONS M } w z w CDO �n a � O C=> SHEET TITLE LIFE SAFETYf'?� SITE PLAT . , SHEET NUMB''ER LSml 0