Loading...
09-97-039GENER�� PLUMBING NOTES 1. PLANS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING AND SHALL INVESTIGATE ALL CONDITIONS THAT AFFECT HIS WORK, SHALL VERIFY LOCATIONS, SIZES, DIMENSIONS, AND INVERT ELEVATIONS OF ALL ON-SITE SANITARY SEWERS, WATER MAINS AND NATURAL GAS MAINS, AND MAKE CERTAIN THAT ALL CONNECTIONS CAN BE MADE. THE CONTRACTOR SHALL MAKE THE ARCHITECT/ENGINEER AWARE OF ALL CONFLICTS. COORDINATE THE INSTALLATION OF THIS SYSTEM WITH OTHER TRADES. ALL PIPING SHALL BE CLOSELY COORDINATED INCLUDING MECHANICAL DUCTWORK, PIPING, LIGHTING FIXTURES, CONDUITS, ARCHITECTURAL AND STRUCTURAL LIMITATIONS PRIOR TO INSTALLATION OF ANY PIPE. RESOLVE ALL QUESTIONS OR CONFLICTS WITH THE ENGINEER BEFORE ANY EQUIPMENT IS ORDERED, MATERIALS FABRICATED OR SYSTEMS INSTALLED. CONSULT THE ARCHITECT'S DRAWINGS FOR ALL GRADE AND FINISH FLOOR ELEVATIONS. DO NOT SCALE THE DRAWINGS. CONSULT THE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR DIMENSIONS. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES AND DRAINS. 2. WORK SHALL COMPLY WITH FLORIDA PLUMBING CODE -2004. MATERIALS AND EQUIPMENT SHALL BE NEW AND GUARANTEED FOR ONE YEAR FROM DATE OF ACCEPTANCE. CONTRACTOR SHALL SUBMIT FOR REVIEW PRIOR TO ORDERING, AND AT JOB COMPLETION, RECORD DRAWINGS AND OPERATION AND MAINTENANCE MANUALS, QUANTITY AS REQUIRED BY ARCHITECT. 3. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 4. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES. 5. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER ARRESTERS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED. 6. SAW CUTTING, PATCHING AND CONCRETE WORK ASSOCIATED WITH PLUMBING SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE SPECIFICATIONS. 7. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO INSTALL ALL SLEEVES THROUGH FLOORS AND WALLS AND TO MAKE ALL FINAL CONNECTIONS. PIPING THROUGH FLOORS SHALL BE SLEEVED, CAULKED AND FLASHED TO PREVENT LEAKAGE. SEAL ALL WALL PENETRATIONS WATERTIGHT WITH SILICONE CAULKING AND BACKER ROD, OR COVERED WITH ESCUTCHEON PLATES. 8. LAYOUT PIPES TO FALL (CONCEALED) WITHIN PARTITION WALL OR CHASES. NOTIFY ARCHITECT IF ADDITIONAL PIPE SPACE IS REQUIRED. COORDINATE PIPE DROP WITH FOOTINGS, STRUCTURAL STEEL, FIRE WALLS, RATED WALLS, ETC., WHICH MAY FALL BELOW PARTITION WALL OR CHASE. MAKE NECESSARY ADJUSTMENT TO PIPING TO AVOID CONFLICT WITH BUILDING OBSTRUCTIONS. DO NOT INSTALL PIPES WITHIN FIRE RATED WALLS. CONSULT WITH ARCHITECT AND CONTRACT DOCUMENTS FOR LOCATION OF ALL RATED WALLS, CEILINGS, FLOORS AND ROOF. FURNISH AND INSTALL APPROPRIATED AND APPROVED FIRE BARRIER AT ALL PENETRATION, INSTALLATION SHALL BE PER MANUFACTURES SPECIFICATIONS. 9. NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES WHERE USED AS RETURN AIR PLENUMS. 10. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR EQUIPMENT ROOMS. 11. CONTRACTOR SHALL COORDINATE ALL OWNER SUPPLIED EQUIPMENT PIPING REQUIREMENTS PRIOR TO INSTALLATION OF PIPING SYSTEMS. 12. PROVIDE PIPE HANGERS FOR ALL PIPING. HANGER RODS AND DEVICES SHALL BE USED FOR SUPPORT OF ALL PIPING. MAKESHIFT DEVICES WILL NOT BE ACCEPTABLE. HANGER DEVICES SHALL BE SIZED TO FIT AROUND INSULATION. PROVIDE GALVANIZED STEEL SADDLES AS REQUIRED. PIPING SUPPORT SPACING SHALL COMPLY WITH THE FLORIDA PLUMBING CODE -2004. 13. TRENCHING, BACKFILL AND CONCRETE WORK ASSOCIATED WITH PLUMBING SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE SPECIFICATIONS. 14. SANITARY, VENT PIPING AND DOMESTIC WATER PIPING SHALL BE TESTED IN ACCORDANCE WITH SEC. 312 OF THE FLORIDA PLUMBING CODE -2004. 15. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND EQUIPMENT CONNECTIONS. 16. IN AREAS OF EXPOSED CMU, ALL PIPING SHALL BE WITHIN CMU WALL. NO EXPOSED PIPING WILL BE ALLOWED. COORDINATION WITH OTHER TRADES WILL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR. TOTAL = 26.0 NOTE: ALL FIXTURES SHALL COMPLY WITH FPC -2004 TABLE 709.1 AND FEC -2004 FOR FLOW RESTRICTION. 7 FI 3 v, a W v- 00 C� E c L� M X � u N .0 -_ ro k� rl Co a of O oM 1�1 Y FLOOR TRAP PRIMER DETA'� NMI,-E� °DING SYSTEM NOTES 1. WATER PIPING ABOVE GRADE SHALL BE TYPE "L", HARD DRAWN COPPER WITH WROUGHT OR FORGED COPPER FITTINGS. WATER VALVES 2" AND SMALLER SHALL BE NIBCO S-22. WATER PIPING BELOW GRADE SHALL BE TYPE "K", ENCLOSED IN POLYETHELYNE PIPE SLEEVE WITH NO JOINTS. FITTINGS ABOVE GRADE SHALL BE BRAZED WITH SILVER SOLDER. ALL EXPOSED PIPING SHALL BE CHROME PLATED. 2. INSTALL VACUUM BREAKERS ON ALL HOSE BIBBS AND HYDRANTS. 3. DOMESTIC WATER PIPING SHALL BE DISINFECTED. CERTIFICATION CONFIRMING TESTING AND COMPLIANCE WITH LOCAL REGULATIONS SHALL BE SUBMITTED TO THE ARCHITECT. 4. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION. 5. PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL SHUT-OFF. 6. WATER PIPING INSULATION SHALL BE 1" THICK ARMAFLEX INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS FOR ALL HOT WATER AND RETURN PIPING. 7. WATER HAMMER ARRESTOR ON ALL WATER SUPPLY LINES SERVING FLUSH VALVE PLUMBING FIXTURES, SOLENOID VALVES, ETC. INCLUDING OTHER FIXTURES OR EQUIPMENT WITH QUICK CLOSING VALVES (ICE MAKERS, & DISHWASHERS). PROVIDE ACCESS TO EACH WATER HAMMER ARRESTOR, UNLESS OTHERWISE DIRECTED BY CODE OFFICIAL. 8. PROVIDE AUTOMATIC TRAP PRIMER ON COLD WATER CONNECTION TO LAVATORY FIXTURE WITH COLD WATER TUBE TO FLOOR DRAIN AUXILIARY INLET FITTING. S,OBUM' PZY. VENT ACONDENSHTE 1. SANITARY, VENT, AND STORM DRAIN PIPING SHALL BE SCHED. 40 PVC BELOW GRADE. SANITARY, VENT AND STORM DRAIN PIPING SHALL BE HUBLESS CAST IRON, OR DWV COPPER ABOVE SLAB. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH MANUFACTURER'S REQUIREMENTS. 2. PROVIDE CHROME PLATED COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS PANEL FOR ALL WALL CLEANOUTS. 3. MAINTAIN A MINIMUM SLOPE OF 1/4" PER. FT. FOR THE SANITARY SEWER AND DRAIN PIPING 2-1/2" OR LESS, AND 1/8" PER FOOT FOR PIPES 3" AND LARGER. 4. ALL INDIRECT WASTE PIPING SHALL DISCHARGE THROUGH AN AIR GAP INTO A WASTE RECEPTOR. ALL WASTE RECEPTORS SHALL BE TRAPPED & VENTED. ALL INDIRECT WASTE PIPING THAT EXCEEDS 24" IN DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 48" IN TOTAL DEV. LENGTH SHALL BE TRAPPED. 5. VENT FLASHING AND COUNTER FLASHING SHALL BE EQUAL TO ELMDOR/STONEMAN 1100-4 WITH 8" SKIRT. 6. ALL FLOOR DRAINS SHALL HAVE DEEP SEALTRAP RESEAL FITTINGS. 7. WATER HEATER RELIEF AND DRAIN LINE SHALL BE TYPE "L" COPPER, 3/4"0 MINIMUM. 8. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH 1" THICK ARMAFLEX INSULATION WHERE USED IN A RETURN AIR PLENUM. PVC PIPING WITH 1" THICK ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES. SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING. 9. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH SOIL, WASTE AND STORM STACK. 10. PROVIDE NECESSARY OFFSET OF VENT STACK TO CLEAR ROOF TOP UNITS, FRESH AIR INTAKES, DOORS, ETC. BY A MINIMUM OF 10 FEET MEASURED HORIZONTALLY. �_F'�_TA& IM1E [001TiEES� 1. GAS PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH MALLEABLE THREADED FITTINGS. ALL PIPING LOCATED INDOORS IN INACCESSIBLE AREAS (SUCH AS CEILING SPACES) SHALL HAVE WELDED FITTINGS. 2. CONTRACTOR SHALL PAY ALL FEES AND OBTAIN ALL PERMITS REQUIRED FOR THE INSTALLATION OF GAS SERVICE TO BUILDING, SEPARATE GAS PERMIT WILL BE REQUIRED. 3. ALL NATURAL GAS LINES SHALL BE BLOWN CLEAN OF DEBRIS AND FOREIGN MATTER WITH COMPRESSED AIR PRIOR TO FINAL CONNECTION TO EQUIPMENT. 4. FROM GAS HEADER INSTALL PIPE DROP WITH A 6" LONG SEDIMENT TRAP. PROVIDE GAS SHUT OFF VALVE ACCESSIBLE FOR MANUAL SHUT-OFF OF GAS TO EQUIPMENT. 5. COORDINATE WITH KITCHEN HOOD FIRE SUPPRESSION SYSTEM CONTRACTOR FOR LOCATION OF INTERLOCK CONTROL WIRING FOR AUTOMATIC SHUT OFF OF GAS VALVE. 6. REFER TO FOOD SERVICE DRAWINGS AND EQUIPMENT MANUFACTURE DATA SHEETS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. 7. FROM GAS VALVE INSTALL APPROVED FLEXIBLE HOSE AND QUICK DISCONNECT WITH RESTRAINING DEVICE AND MAKE FINAL CONNECTION TO EQUIPMENT. 8. CONTINUE GAS SERVICE AND PROVIDE CONNECTION TO MAIN GAS SERVICE LINE. 9. LOCATION OF CONNECTION„ INCLUDING GAS METER, MAIN SHUT-OFF VALVE, ETC., SHALL BE COORDINATED WITH CIVIL DOCUMENTS AND LOCAL GAS COMPANY. %s s A WEATHER PROOF SIGN RED/WHITE COLOR CONTRAST 2" MIN. LETTERS MUST BE PROVIDED AND PERMANENTLY INSTALLED OUTSIDE ABOVE OAS VALVE TO INDICATE (GAS SHUT-OFF FOR 9480). �s 4 aC m �y s c,�o� -P�o ss sow Y O CONTRACTOR TO VERIFY ALL EQUIPMENT SPECIFICATIONS PRIOR OF INSTALLATION. �- 5 NOTES: ALL LP AND NATURAL OAS LINES SHALL BE PAINTED RUSTOLEUM # 944 YELLOW FROM ORIGINATION TO TERMINATION OF LINE. GAS LINES SHALL BE LABELED EVERY 15 FEET FROM POINT OF ORIOINATION TO TERMINATION OF LINE. GAS PIPINC3 TO BE INSTALLED BY LISCENSED CONTRACTOR TOTAL DEVELOPED OAS PIPE LENGTH - 73' TOTAL BTUH LOAD -379,000 BTUH. GAS S.O.V. SHALL COMPLY WITH NFPA 54 5.5.4. RISER DIAGRAM - GAS N.T.S. /- /. � °� ��Z� • �\ / ti <1 � 00, \�Q ` - PJ^� J RISER DIAGRAM - WATER N.T.S. / I / 0 / I �N 5-(2FU) / I / / d G-� GW G "(4Fu) I \ \ / c5%,- �CP � \ � ^�o 91 I dell, G� CD V GW RISER DIAGRAM - GRASE & SANITARY N.T.S. ALL IDEAS, DESIGNS, ARRANGEMENTS, AND PLANS INDICATED OR REPRESENTED BY THIS DRAWING ARE OWNED BY, AND THE PROPERTY OF TECTONICS ASSOCIATES, INC. AND WERE CREATED, EVOLVED AND DEVELOPED FOR USE ON, AND IN CONNECTION WITH THE SPECIFIED PROJECT. NONE OF SUCH IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL BE USED BYOR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF TECTONICS ASSOCIATES, INC. WRITTEN DIMENSIONS OF THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY, AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS. SHOP DETAILS MUST BE SUBMITTED TO THIS OFFICE FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION. a W 0 N ILa W N W") a M J Q LL Q � cl asMill UJ �cc ^ CO Z..1 NI,U CC > + J Hm QLLo W + �'n� cc Qpm 40 ��+ 3N ��z W m 00 Zmo a W (o I` 0Za+z =Q In CLO 705020 I -- PLUM WNG NXTURE SCHEDULE MARK FIXTURE PIPE SIZE C.W. H.W. WASTE FIXTUREO UNIT TOTAL REMARKS FIXTURE UNIT HLAV HANDICAPPED LAVATORY 1/2" 1/2" 2" 1 2 1 2 HWC HANDICAPPED WATER CLOSET 1/2" - 4" 4 2 8 SK SINK 1/2" 1/2" 2" 2 3 6 FT FLOOR TROUGH - - 3" 2 1 2 FD FLOOR DRAIN 1/2" - 3" 0 6 0 FS FLOOR SINK - - 3" 2 4 8 TOTAL = 26.0 NOTE: ALL FIXTURES SHALL COMPLY WITH FPC -2004 TABLE 709.1 AND FEC -2004 FOR FLOW RESTRICTION. 7 FI 3 v, a W v- 00 C� E c L� M X � u N .0 -_ ro k� rl Co a of O oM 1�1 Y FLOOR TRAP PRIMER DETA'� NMI,-E� °DING SYSTEM NOTES 1. WATER PIPING ABOVE GRADE SHALL BE TYPE "L", HARD DRAWN COPPER WITH WROUGHT OR FORGED COPPER FITTINGS. WATER VALVES 2" AND SMALLER SHALL BE NIBCO S-22. WATER PIPING BELOW GRADE SHALL BE TYPE "K", ENCLOSED IN POLYETHELYNE PIPE SLEEVE WITH NO JOINTS. FITTINGS ABOVE GRADE SHALL BE BRAZED WITH SILVER SOLDER. ALL EXPOSED PIPING SHALL BE CHROME PLATED. 2. INSTALL VACUUM BREAKERS ON ALL HOSE BIBBS AND HYDRANTS. 3. DOMESTIC WATER PIPING SHALL BE DISINFECTED. CERTIFICATION CONFIRMING TESTING AND COMPLIANCE WITH LOCAL REGULATIONS SHALL BE SUBMITTED TO THE ARCHITECT. 4. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION. 5. PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL SHUT-OFF. 6. WATER PIPING INSULATION SHALL BE 1" THICK ARMAFLEX INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS FOR ALL HOT WATER AND RETURN PIPING. 7. WATER HAMMER ARRESTOR ON ALL WATER SUPPLY LINES SERVING FLUSH VALVE PLUMBING FIXTURES, SOLENOID VALVES, ETC. INCLUDING OTHER FIXTURES OR EQUIPMENT WITH QUICK CLOSING VALVES (ICE MAKERS, & DISHWASHERS). PROVIDE ACCESS TO EACH WATER HAMMER ARRESTOR, UNLESS OTHERWISE DIRECTED BY CODE OFFICIAL. 8. PROVIDE AUTOMATIC TRAP PRIMER ON COLD WATER CONNECTION TO LAVATORY FIXTURE WITH COLD WATER TUBE TO FLOOR DRAIN AUXILIARY INLET FITTING. S,OBUM' PZY. VENT ACONDENSHTE 1. SANITARY, VENT, AND STORM DRAIN PIPING SHALL BE SCHED. 40 PVC BELOW GRADE. SANITARY, VENT AND STORM DRAIN PIPING SHALL BE HUBLESS CAST IRON, OR DWV COPPER ABOVE SLAB. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH MANUFACTURER'S REQUIREMENTS. 2. PROVIDE CHROME PLATED COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS PANEL FOR ALL WALL CLEANOUTS. 3. MAINTAIN A MINIMUM SLOPE OF 1/4" PER. FT. FOR THE SANITARY SEWER AND DRAIN PIPING 2-1/2" OR LESS, AND 1/8" PER FOOT FOR PIPES 3" AND LARGER. 4. ALL INDIRECT WASTE PIPING SHALL DISCHARGE THROUGH AN AIR GAP INTO A WASTE RECEPTOR. ALL WASTE RECEPTORS SHALL BE TRAPPED & VENTED. ALL INDIRECT WASTE PIPING THAT EXCEEDS 24" IN DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 48" IN TOTAL DEV. LENGTH SHALL BE TRAPPED. 5. VENT FLASHING AND COUNTER FLASHING SHALL BE EQUAL TO ELMDOR/STONEMAN 1100-4 WITH 8" SKIRT. 6. ALL FLOOR DRAINS SHALL HAVE DEEP SEALTRAP RESEAL FITTINGS. 7. WATER HEATER RELIEF AND DRAIN LINE SHALL BE TYPE "L" COPPER, 3/4"0 MINIMUM. 8. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH 1" THICK ARMAFLEX INSULATION WHERE USED IN A RETURN AIR PLENUM. PVC PIPING WITH 1" THICK ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES. SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING. 9. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH SOIL, WASTE AND STORM STACK. 10. PROVIDE NECESSARY OFFSET OF VENT STACK TO CLEAR ROOF TOP UNITS, FRESH AIR INTAKES, DOORS, ETC. BY A MINIMUM OF 10 FEET MEASURED HORIZONTALLY. �_F'�_TA& IM1E [001TiEES� 1. GAS PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH MALLEABLE THREADED FITTINGS. ALL PIPING LOCATED INDOORS IN INACCESSIBLE AREAS (SUCH AS CEILING SPACES) SHALL HAVE WELDED FITTINGS. 2. CONTRACTOR SHALL PAY ALL FEES AND OBTAIN ALL PERMITS REQUIRED FOR THE INSTALLATION OF GAS SERVICE TO BUILDING, SEPARATE GAS PERMIT WILL BE REQUIRED. 3. ALL NATURAL GAS LINES SHALL BE BLOWN CLEAN OF DEBRIS AND FOREIGN MATTER WITH COMPRESSED AIR PRIOR TO FINAL CONNECTION TO EQUIPMENT. 4. FROM GAS HEADER INSTALL PIPE DROP WITH A 6" LONG SEDIMENT TRAP. PROVIDE GAS SHUT OFF VALVE ACCESSIBLE FOR MANUAL SHUT-OFF OF GAS TO EQUIPMENT. 5. COORDINATE WITH KITCHEN HOOD FIRE SUPPRESSION SYSTEM CONTRACTOR FOR LOCATION OF INTERLOCK CONTROL WIRING FOR AUTOMATIC SHUT OFF OF GAS VALVE. 6. REFER TO FOOD SERVICE DRAWINGS AND EQUIPMENT MANUFACTURE DATA SHEETS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. 7. FROM GAS VALVE INSTALL APPROVED FLEXIBLE HOSE AND QUICK DISCONNECT WITH RESTRAINING DEVICE AND MAKE FINAL CONNECTION TO EQUIPMENT. 8. CONTINUE GAS SERVICE AND PROVIDE CONNECTION TO MAIN GAS SERVICE LINE. 9. LOCATION OF CONNECTION„ INCLUDING GAS METER, MAIN SHUT-OFF VALVE, ETC., SHALL BE COORDINATED WITH CIVIL DOCUMENTS AND LOCAL GAS COMPANY. %s s A WEATHER PROOF SIGN RED/WHITE COLOR CONTRAST 2" MIN. LETTERS MUST BE PROVIDED AND PERMANENTLY INSTALLED OUTSIDE ABOVE OAS VALVE TO INDICATE (GAS SHUT-OFF FOR 9480). �s 4 aC m �y s c,�o� -P�o ss sow Y O CONTRACTOR TO VERIFY ALL EQUIPMENT SPECIFICATIONS PRIOR OF INSTALLATION. �- 5 NOTES: ALL LP AND NATURAL OAS LINES SHALL BE PAINTED RUSTOLEUM # 944 YELLOW FROM ORIGINATION TO TERMINATION OF LINE. GAS LINES SHALL BE LABELED EVERY 15 FEET FROM POINT OF ORIOINATION TO TERMINATION OF LINE. GAS PIPINC3 TO BE INSTALLED BY LISCENSED CONTRACTOR TOTAL DEVELOPED OAS PIPE LENGTH - 73' TOTAL BTUH LOAD -379,000 BTUH. GAS S.O.V. SHALL COMPLY WITH NFPA 54 5.5.4. RISER DIAGRAM - GAS N.T.S. /- /. � °� ��Z� • �\ / ti <1 � 00, \�Q ` - PJ^� J RISER DIAGRAM - WATER N.T.S. / I / 0 / I �N 5-(2FU) / I / / d G-� GW G "(4Fu) I \ \ / c5%,- �CP � \ � ^�o 91 I dell, G� CD V GW RISER DIAGRAM - GRASE & SANITARY N.T.S. ALL IDEAS, DESIGNS, ARRANGEMENTS, AND PLANS INDICATED OR REPRESENTED BY THIS DRAWING ARE OWNED BY, AND THE PROPERTY OF TECTONICS ASSOCIATES, INC. AND WERE CREATED, EVOLVED AND DEVELOPED FOR USE ON, AND IN CONNECTION WITH THE SPECIFIED PROJECT. NONE OF SUCH IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL BE USED BYOR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF TECTONICS ASSOCIATES, INC. WRITTEN DIMENSIONS OF THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTORS SHALL VERIFY, AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS. SHOP DETAILS MUST BE SUBMITTED TO THIS OFFICE FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION. a W 0 N ILa W N W") a M J Q LL Q � cl asMill UJ �cc ^ CO Z..1 NI,U CC > + J Hm QLLo W + �'n� cc Qpm 40 ��+ 3N ��z W m 00 Zmo a W (o I` 0Za+z =Q In CLO 705020 I -- Q U LO 2 H 0 L- T U 1� ♦/) VJ O Cf) r r U2 a) <� Q W CN W o N WWW D 00 WO�a 0 LL 0 E R d c 0 date 12-10-08 REVISED BY: ONE D+B project number 08146 sheet P-2 of Q 2 H 0 U O Cf) O Z LU W <� Q W CN W o N D 00 0 E R d c 0 date 12-10-08 REVISED BY: ONE D+B project number 08146 sheet P-2 of