08-40-226REDUCING COUPLING
1" SUPPLY UNE--,
UPPER SL
PIECE
WALL ESCUTCHEON
FINISHED WALL LINE
SIDEWALL SPRINKLER HEAD
MOUNTING DETAIL
N.T.S.
FINISHED CEILING LINE
.Y UNE
COUPLING
DEFLECTOR
(DISTANCE BELOW CEILING SHALL
eE IN ACCORDANCE WITH MFR'S,
LISTING)
CEILINGD__/ CEILING ESCUTCHEON
LINE
DEFLECTOR
RECESSED PENDENT TYPE SPRINKLER
HEAD MOUNTING DETAIL
N.T.S.
DRAIN RISER � I
TO DRAIN -
BLACK STEEL
PIPE WELDED
OR VICTAULIC
COUPLING
- STANDPIPE RISER
INDICATING TYPE FLOOR CONTROL
- VALVE W/ SUPERVISORY SWITCH
PRESSURE GAUGE
WATER FLOW SWITCH
r FEED MAIN TO
SPRINKLER
SYSTEM
SIGHT GLASS
AUXILIARY
DRAIN VALVE
INSPECTOR'S
TEST VALVE
1" UNION W/BRASS
ORIFICE DISK W/ HOLE
EQUAL TO DISCHARGE FROM
A SPRINKLER ORIFICE
SPRINKLER TEST & FLOOR CONTROL VALVE
N.T.S.
SPRINKLER HEAD SCHEDULE
AREA SERVED
MFR. &
ORIFICE
I CONFIGURATION
TEMP.
FINISH
DESIGN
FIRE MAIN
MODEL NO.
K -FACTOR
8
RATING
-0-
INFO.
AREAS WITH
VIKING
-�
UPRIGHT PENDENT
12
WHITE
pQ
EXPOSED
STRUCTURE
MICROFAST�2"G
VK300/VK302
5.
QUICK RESPONSE
STANDARD
ORDINARY
POLYESTER
-"`
-�-
CH.V.
15
COVERAGE
O
COATING
MODEL 1800
AREAS WITH
VIKING
F.H.
RECESSED PENDENT
FIRE HYDRANT
WHITE
F.H.C.
DROPPED
MICROFAST1
2"
QUICK RESPONSE
ORDINARY
FIRE HOSE RACK
CEILINGS
VK302
-5.G
STANDARD
F.STP.
POLYESTER
--`
FLSW.
COVERAGE
�H
COATING
AREAS WITH
VIKING
R.M.V.
SIDEWALL
ROOF MANIFOLD VALVE
WHITE
T.SW.
SIDEWALL
SPRINKLERS
MICROFAST
VK305
112"
K 5.B
QUICK RESPONSE
STANDARD
ORDINARY
POLYESTER
---
COVERAGE
COATING
PIT OF
ELEVATOR
VIKING
MICROFAST
1/2'
SIDEWALL
QUICK RESPONSE
INTERMEDIATE
WHITE
HOISTWAY
VK305
IICC 5.B
STANDARD
POLYESTER
---
COVERAGE
COATING
TOP OF
VIKING
MICROFAST112"
UPRIGHT/PENDENT
QUICK H ESPONSE
WHITE
ELEVATOR
HOISTWAY
VK30O/VK302
1{ 5.i
STANDARD
INTERMEDIATE
POLYESTER
---
COVERAGE
COATING
NOTES:
1. ALL SPRINKLERS TO BE U.L LISTED QUICK RESPONSE UNLESS NOTED OTHERWISE.
2. WHITE POLYESTER SPRINKLER FINISH TO BE U.L. LISTED CORROSION RESISTANT.
TYPICAL VERTICAL PIPE
SUPPORT DETAIL
N.T.S.
DEFLECTOR TO BE MAXIMUM
12" BELOW BOTTOM OF ROOF/
FLOOR DECK IN ACCORDANCE
WITH N.F.P.A. 13 REQUIREMENTS
(UNOBSTRUCTED CONSTRUCTION)
AX. 22" ALLOWED FOR
OBSTRUCTED CONSTRUCTION
BRANCH
LINE
TEE
PIPE RISER
RISER CLAMP ANVIL/
GRINNELL NO. 261
OR EQUAL
NEOPRENE TYPE
ISOMODE PAD
CONC. SPACER
CONIC. SLAB
PIPE SLEEVE
REFER TO FIRESTOPPING
DETAIL THIS SHEET
ROOF OR FLOOR MOVE
FIRE
PROTECTION LEGEND
SYMBOL A BREV.
DESCRIPTION
.____ - - - -
- F-
2
I
� I
FIRE MAIN
-Q-
G
8
PENDENT SPRINKLER HEAD
-0-
12
2 1/2" GATE
UPRIGHT SPRINKLER HEAD
-�
12
12
SIDEWALL SPRINKLER HEAD
pQ
BFV
FIRE VALVE
INDICATING TYPE NUTTERFLY VALVE
12
OSxY
15
OUTSIDE SCREW AND YOKE GATE VALVE
-�-
CH.V.
15
CHECK VALVE
O
F.E.
MODEL 1800
FIRE EXTINGUISHER
LUGS
F.H.
THREADS
FIRE HYDRANT
BY
F.H.C.
FIRE DEPT.
FIRE HOSE CABINET
C�
F.H.R.
FIRE HOSE RACK
F.S.
FIRE SIAMESE
C)+--
F.STP.
FIRE STANDPIPE
FLSW.
FLOW SWITCH
�H
P.I.V.
POST INDICATOR VALVE
R.M.V.
ROOF MANIFOLD VALVE
T.SW.
TAMPER SWITCH
0
HYDRAULIC REFERENCE POINT
-----DEFLECTORTDP' CONC. SW
EAM
CLAMP W/ LOCK NUT
UPRIGHT TYPE SPRINKLER HEAD STEEL I BEAM ,,; " #
OR BAR JOIST • �;� ' " „,
CENTER I BEAM �� . r ` m
LOAD CLAW All THREADED -
�J HANGER ROD
DROP IN ANCHOR
ALL THREADED ALL THREADED
HANGER ROD HANGER ROD
UPRIGHT TYPE SPRINKLER HEAD
MOUNTING DETAIL
N.T.S.
2 1/2- GAT
VALVE IN
STAIR WELL7
-�
2 162" X 1 1!
RED CER (TYP.
1 1/2" CAP -
FIRE DEPT. VALVES TO BE LOCATED
AT 4'-0" A.F.F.
TYPICAL STANDPIPE EIRE
DEPARTMENT CONNECTION
N.T.S.
CROSSMAIN
BRANCH
LINE
RISER
NIPPLE
SCREW GROOVE
TYPE CAP TYPE CAP
NOTE:
ALL CRDSSMAINS SHALL TERMINATE IN
MIN. 1 1/4" PIPEALL BRANCH LINES ON GRIDDED
SYSTEMS SHALL BE ARRANGED TO FACILITATE
FLUSHING OF THE SYSTEM.
TYPICAL FLUSHING CONNECTION
CROSSMAIN
N.T.S.
ALL THRER
HANGER R
NUT
CLEVIS HAN,
PIPE 0.0
PIPE
FASTENERS POWDER DRIVEN STUDS MAY
USED IN LIEU OF LISTED CONCRETE
N.T.S. INSERTS WHERE APPROVED BY
STRUCNRAL ENGINEER
ALL FASTENERS SHALL BE LSnD
FOR THEIR INTENDED SERVICE
ALL HANGERS, HANGER RODS,
CLAWS, COUPLINGS, ETC. SHALL
ALL THREADED _ BE PROVIDED WITH FACTORY
HANGER ROD APPLIED HOT DIWO GALVANIZED
FINISH FOR CORROSION PROTECTION
NUT
ADJUSTAILE SWIVEL
LOOP HANGER
PIPE
ROD TO XTE]ND ROD TO
IF MPE TOP OF MPE
PIPE HANGERS
N.T.S.
ALL HANGERS SHALL BE LISTED
FOR THEIR INTENDED SERVICE
HANGER ROD SIZES
UP TO 4" PIPE 3/8" DIA.
5" TO 8" PIPE 1/2" DIA.
10 12" PIPE 5/8" DIA.
MAXIMUM HANGER SPACING (FT.)
STANDPIPE RISER
3/4
.._....
fr
I
.____ - - - -
1 1/2
2
I
� I
3
4
G
8
THREADED LIGHTWALL
STEEL PIPE
N/A
12
2 1/2" GATE
12
12
12
12
VALVE
N/A
N/A
FIRE VALVE
N/A
12
CABINET WHERE
15
15
I ON DWGS.)
15
15
-SHOWN
POTTER-ROEMER
15
L
MODEL 1800
LUGS
_ _ _ _ -J
FOR SPANNER SERIES
THREADS
AS APPROVED
BY
LOCAL
FIRE DEPT.
FIRE DEPT. VALVES TO BE LOCATED
AT 4'-0" A.F.F.
TYPICAL STANDPIPE EIRE
DEPARTMENT CONNECTION
N.T.S.
CROSSMAIN
BRANCH
LINE
RISER
NIPPLE
SCREW GROOVE
TYPE CAP TYPE CAP
NOTE:
ALL CRDSSMAINS SHALL TERMINATE IN
MIN. 1 1/4" PIPEALL BRANCH LINES ON GRIDDED
SYSTEMS SHALL BE ARRANGED TO FACILITATE
FLUSHING OF THE SYSTEM.
TYPICAL FLUSHING CONNECTION
CROSSMAIN
N.T.S.
ALL THRER
HANGER R
NUT
CLEVIS HAN,
PIPE 0.0
PIPE
FASTENERS POWDER DRIVEN STUDS MAY
USED IN LIEU OF LISTED CONCRETE
N.T.S. INSERTS WHERE APPROVED BY
STRUCNRAL ENGINEER
ALL FASTENERS SHALL BE LSnD
FOR THEIR INTENDED SERVICE
ALL HANGERS, HANGER RODS,
CLAWS, COUPLINGS, ETC. SHALL
ALL THREADED _ BE PROVIDED WITH FACTORY
HANGER ROD APPLIED HOT DIWO GALVANIZED
FINISH FOR CORROSION PROTECTION
NUT
ADJUSTAILE SWIVEL
LOOP HANGER
PIPE
ROD TO XTE]ND ROD TO
IF MPE TOP OF MPE
PIPE HANGERS
N.T.S.
ALL HANGERS SHALL BE LISTED
FOR THEIR INTENDED SERVICE
HANGER ROD SIZES
UP TO 4" PIPE 3/8" DIA.
5" TO 8" PIPE 1/2" DIA.
10 12" PIPE 5/8" DIA.
MAXIMUM HANGER SPACING (FT.)
PIPE SIZE (IN.)
3/4
1
1 1/4
1 1/2
2
2 1/2
3
4
G
8
THREADED LIGHTWALL
STEEL PIPE
N/A
12
12
12
12
12
12
N/A
N/A
N/A
STEEL PIPE EXCEPT
THREADED LIGHTWALL
N/A
12
12
15
15
15
15
15
15
15
NOTES:
1. MAXIMUM DISTANCE BETWEEN END UPRIGHT SPRINKLER AND LAST HANGER ON BRANCH LINES SHALL NOT EXCEED 36" FOR 1"
PIPE, 48" FOR 1 1/4" PIPE AND CO" FOR 1 1/2" OR LARGER PIPE SIZE. EXTEND BRANCH LINE AND PROVIDE ADDITIONAL
HANGER WHERE REQUIRED.
2. MAXIMUM HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A SPRINKLER, SPRINKLER DROP OR SPRIG -UP SHALL
NOT EXCEED 24"
3. MINIMUM DISTANCE BETWEEN A HANGER AND CENTERLINE OF AN UPRIGHT SPRINKLER TO BE 311
.
4. WALL MOUNTED SIDEWALL SPRINKLERS SHALL BE RESTRAINED TO PREVENT MOVEMENT.
5. HANGERS FOR MAINS SHALL BE IN ACCORDANCE WITH SPACING TABLE ABOVE OR BETWEEN EACH BRANCHLINE, WHICHEVER
IS THE LESSER DIMENSION.
MIN. SIZE
LINE
TEE SIZE REMOVEMLE CAP
TRAPPED WATER VOLUME >5 GAL. < 50 GAL.: 3/4" MIN DRAIN VALVE REQ'D.
TRAPPED WATER VOLUME >50 GAL.: 1" MIN. DRAIN VALVE PIPED TO
AN ACCESSIBLE LOCATION REQ'D.
AUXILIARY DRAIN DETAIL
N.T.S.
FIRE PROTECTION NOTES & DETAILS
N.T.S.
GENERAL NOTES
1. ALL PIPING,HANGERS,SUPPORT METHODS AND SPRINKLER HEADS TO BE 1
INSTALLED IN STRICT ACCORDANCE WITH N.F.P.A. 13, AND ALL LOCAL
CODES AND ORDINANCES.
2. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN 1
ACCORDANCE WITH N.F.P.A. 13 AND N.F.P.A. 13R.
3. ALL RATED WALLS AND FLOORS TO BE PROPERLY SLEEVED AND SEALED
WITH APPROVED FIRE/SMOKE STOP MATERIAL
4. HYDRAULIC DATA PLACE CARD TO BE PLACED ON SYSTEM RISER(S).
20
5. ALL SPRINKLER HEADS IN ELEVATOR MACHINE ROOMS,ELECTRICAL ROOMS
AND MECHANICAL ROOMS SHALL BE PROVIDED WITH HEAD GUARDS.
G. PROVIDE INSPECTOR'S TEST CONNECTION AND DRAIN AS PER N.F.PA 13
REQUIREMENTS.
7. TEMPERATURE CLASSIFICATION FOR ALL SPRINKLER HEADS SHALL BE
ORDINARY UNLESS NOTED OTHERWISE IN THE DRAWINGS.
SPRINKLERS IN ELEVATOR HOISTWAYS AND ELEVATOR MACHINE ROOMS
SHALL BE INTERMEDIATE TEMPERATURE RATING (175-225 DEGREES). 2
8. DESIGN CRITERIA:
DESIGN CRITERIA SHALL BE BASED ON N.F.P.A. 13, ORDINARY HAZARD
GR. I, .15 GPM PER SQ. FT., 250 GPM HOSE ALLOWANCE, 1500 SQ. FT.
REMOTE AREA, MAX. 130 SQ. FT. COVERAGE PER SPRINKLER HEAD
(PARKING GARAGE, MECH. ROOMS)
DESIGN CRITERIA SHALL IE BASED ON N.F.P.A. 13, LIGHT HAZARD
.10 GPM PER SQ. FT., 100 GPM HOSE ALLOWANCE, 1500 SQ. FT.
REMOTE AREA, MAX. 225 SQ. FT. COVERAGE PER SPRINKLER HEAD.
(ALL OTHER PUBLIC SPACE AREAS, TENANT AREAS)
22
DESIGN CRITERIA SHALL BE BASED ON N.F.P.A. 13, ORDINARY HAZARD
GROUP 2, .20 GPM PER SQ. FT., 250 GPM HOSE ALLOWANCE, 1500 S.F.
REMOTE AREA.
(TENANT AREAS) 23
STANDPIPE SYSTEM TO BE A MANUAL WET TYPE, CLASS I, AS ALLOWED
BY NEPA 14 FOR BUILDINGS NOT CLASSIFIED AS HIGH RISE BUILDINGS.
PROVIDE SIGNAGE AT EACH HOSE CONNECTION "MANUAL STANDPIPE FOR 2
FIRE DEPARTMENT USE ONLY".
9. ALL VALVES CONTROLLING WATER SUPPLY SHALL BE PROVIDED WITH
A SUPERVISORY (TAMPER) SWITCH.000RDINATE LOCATION OF ALL FLOW
AND TAMPER SWITCHES WITH ELECTRICAL CONTRACTOR. 2
10.ALL PIPING ABOVE GROUND SHALL BE LIGHTWALL THREADABLE STEEL
PIPE FOR 2" AND SMALLER, GROOVED SCHEDULE 10 STEEL PIPE
FOR PIPING 2 1/2" AND LARGER. ALLIED XL AND ALLIED SCH. 10 OR
APPROVED EQUAL
FITTINGS FOR PIPING 2" AND SMALLER SHALL BE MALLEABLE IRON,
150 PSI BANDED,THREADED,BLACKANSI B 16.3.
JOINT COMPOUND OR TAPE SHALL BE APPLIED ONLY TO MALE THREADS.
SCREWED UNIONS SHALL NOT BE USED ON PIPE LARGER THAN 2 INCH.
FITTINGS FOR PIPING 2 1/2" AND URGER SHALL BE MECHANICAL COUPLING
SYSTEM AS MANUFACTURED BY VICTAULIC CORP.OR GRINNELL CORP.
"GRUVLOCK'.
ALL GROOVED FITTINGS SHALL BE FROM SAME MANUFACTURER.
ALL PIPING AT EXTERIOR OR OPEN TO EXTERIOR TO BE FACTORY GALVANIZED
PIPE AND FITTINGS.
(TYP. AT PARKING GARAGE AND ALL AREAS WHERE APPLICABLE).
UNDERGROUND PIPING SHALL BE CEMENT LINED DUCTILE IRON PIPE AND
FITTINGS WITH ASPHALTIC EXTERIOR COATING CONFORMING TO ANSI/AWWA
C151/A21.51 AND C104/A21.4. RUBBER GASKET JOINTS SHALL CONFORM
TO ANSI/AWWA C111/A21.11,
ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH N.F.P.A. 24.
PROVIDE RESTRAINING FOR FIRE MAINS CONSISTING OF THRUST BLOCKS,
TIE RODS, LOCKED MECHANICAL OR PUSH -ON JOINTS IN ACCORDANCE
WITH N.F.P.A. 24 REQUIREMENTS.
UNDERGROUND PIPING SHALL BE BURIED WITH MINIMUM 36" COVER.
REFER TO CIVIL ENGINEER DRAWINGS.
ALL PIPING SHALL BE CONTINUOUSLY MARKED ALONG IT'S LENGTH BY
THE MANUFACTURER'S NAME, MODEL DESIGNATION AND/OR SCHEDULE
IN ACCORDANCE WITH N.F.P.A. 13.
11.PRESSURE TEST AND FLUSH THE SYSTEM IN ACCORDANCE WITH N.F.P.A. 13
AND N.F.P.A. 14 REQUIREMENTS. SUBMIT CONTRACTOR'S MATERIAL AND
TEST CERTIFICATE FOR UNDERGROUND AND ABOVEGROUND PIPING.
ALL WATERFLOW SWITCHES AND SUPERVISORY SWITCHES SHALL BE
TESTED FOR PROPER OPERATION AND ANNUCIATION.
FURNISH TO OWNER'S REPRESENTATIVE ALL LITERATURE AND INSTRUCTIONS
FOR THE PROPER OPERATION AND MAINTENANCE OF ANY EQUIPMENT AND
DEVICES INSTALLED AND A COPY OF N.F.P.A. 25 -"STANDARD FOR THE
INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION
SYSTEM".
12.PROVIDE AUXILIARY DRAIN CONNECTION FOR ALL TRAPPED PIPING SECTIONS
IN ACCORDANCE WITH N.F.PA 13,PROVIDE FLUSHING CONNECTIONS AS REQUIRED.
REMOVEABL.E FITTINGS SHALL BE PROVIDED AT END OF CROSSMAINS.
PROVIDE MINIMUM 1/4 IN. RELIEF VALVE AT GRIDDED SYSTEMS (SET AT 165 PSI)
IN ACCORDANCE WITH N.F.PA 13.
ALI_ BRANCH LINES ON GRIDDED SYSTEMS SHALL BE ARRANGED TO FACILITATE
FLUSHING OF THE PIPING.
13.ALL FIRE PROTECTION PIPING, EQUIPMENT AND DEVICES SHALL BE U.L. LISTED
AND FACTORY MUTUAL GLOBAL APPROVED.
14.GATE VALVES 2" AND SMALLER SHALL BE O.S.&Y. THREADED BRONZE,
RISING STEM,WEDGE DISC,175 WWP.GATE VALVES 2 1/2" AND LARGER SHALL BE
O.S.&Y. FLANGED IBBM RISING STEM,SQLID WEDGE DISC,175 WWP.ALL GATE
VALVES SHALL BE U.L. LISTED AND F.M. APPROVED.
BUTTERFLY VALVES WITH OR WITHOUT INTEGRAL SUPERVISORY SWITCH MAY
BE USED WHERE PERMITTED BY N.F.P.A. 13.
15.CHECK VALVES 2 1/2" AND LARGER SHALL BE FLANGED IBBM SWING TYPE,BRONZE
MOUNTED,175 WWP CLASS,U.L. LISTED AND F.M. APPROVED.
16.SUPERVISORY SWITCHES SHALL BE 120 VOLT CLOSED CIRCUIT TAMPER SWITCH,
U,L LISTED AND F.M. APPROVED.FLOW SWITCHES SHALL BE PADDLE TYPE,SINGLE POLE,
DOUBLE THROW WITH ADJUSTMENT FOR SENSITIVITY TO FLOW WITH TIME DELAY,
U.L LISTED AND F.M. APPROVED. SUPERVISORY AND WATERFLOW SWITCH TO BE
POTTER ELECTRIC SIGNAL CO. OR APPROVED EQUAL.
17.HOSE THREADS AT FIRE DEPARTMENT CONNECTIONS SHALL CONFORM WITH
LOCAL FIRE DEPARTMENT STANDARDS. FIRE DEPARTMENT CONNECTIONS SHALL BE
AS MANUFACTURED BY POTTER-ROEMER OR EQUAL
•rY� ••• • • •uYri
V i Y Y W V
•• i Y Y i • Y
U Y N • r
• Y y • r
" r• I" Y W M • Y • •. i y,
r c y •
r u rr Y a• u yup
• r • • r V Y V i 4 V
• Y • • • u U
Y • ♦ • • 4 V V
V•• • i f i• V y V I
• • N y!
• V•• V V u V
i i • Y V
Y r ,, •
• U• U • Y Y Y i V i V• • i.
l.THE WORK THAT IS TO BE DONE UNDER THIS CONTRACT INCLUDES THE FURNISHING
OF ALL LABOR,MATERIALS AND EQUIPMENT,PERMffS,FEES,INSPECTIONS,TESTS,
INSURANCE,ETC. REQUIRED FOR THE COMPLETION OF FIRE PROTECTION SYSTEM
SHOWN ON THE DRAWINGS AND LISTED HEREIN.
9.THE DRAWINGS ARE GENERALLY DIAGRAMMATIC.THEY DO NOT SHOW EVERY
NEND,OFFSET OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION
IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES.
VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO
FAMRICATION OF PIPING AND INSTALLATION OF EQUIPMENT AND MATERIALS.
. SPRINKLER HEADS SHALL RE AUTOMATIC, CAST BRASS GLASS NULLA OR
FUSIBLE LINK TYPE, ORDINARY TEMPERATURE RATING UNLESS
NOTED OTHERWISE, CONFIGURATION AS NOTED ON DRAWINGS. FACTORY
COATING OR FINISH SHALL BE AS NOTED ON SPRINKLER HEAD SCHEDULE.
ALL SPRINKLERS SHALL BE PROVIDED WITH MARKINGS DESIGNATING
ORIFICE SIZE, DEFLECTOR CHARACTERISTIC AND THERMAL SENSITIVITY.
INSTALLATION SHALL BE IN ACCORDANCE WITH N.F.P.A. 13 AND WITH
MANUFACTURER'S INSTRUCTIONS. REFER TO SPRINKLER HEAD SCHEDULE
THIS SHEET.
1. PROVIDE IDENTIFICATION FOR ALL PIPING, VALVES, ETC. ASSOCIATED WITH THE
FIRE PROTECTION SYSTEM. COLOR BANDS, LEGEND AND FLOW
ARROWS AT PIPE MARKERS SHALL IE IN ACCORDANCE WITH ANSI A13.1
A. PROVIDE SIGNAGE WITH MIN. 1 INCH HIGH LETTERING AT FIRE
DEPARTMENT CONNECTIONS.
1. PROVIDE HYDRAULIC DESIGN INFORMATION SIGNS) AT SPRINKLER
SYSTEMS IN ACCORDANCE WITH N.F.P.A. 13
C. ALL MAIN AND SECTIONAL CONTROL VALVES, DRAIN VALVES, TEST
CONNECTION VALVES SHALL BE PROVIDED WITH PERMANENTLY MARKED
WEATHERPROOF IDENTIFICATION SIGNS IN ACCORDANCE WITH N.F.PA 13
. ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
N.F.P.A. 13, 14, 20, 24, 25 , 101 AND IN ACCORDANCE WITH ALL
LOCAL CODES AND ORDINANCES.
. ALL WORK SHALL BE PERFORMED BY STATE LICENSED AND CERTIFIED PERSONNEL IN
ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE 4A-46 is 4A-48.
SUBMIT TO OWNER'S REPRESENTATIVE AS BUILT DRAWINGS, OWNER'S MANUALS,
MAINTENANCE MANUALS.
4. FIRE PUMP SYSTEM SHALL BE IN ACCORDANCE WITH N.F.PA 20
REQUIREMENTS. TESTING OF FIRE PUMP SYSTEM SHALL BE IN
ACCORDANCE WITH CHAPTER 11 OF N.F.P.A. 20.
PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THE FIRE PUMP
SYSTEM SHALL BE IN ACCORDANCE WITH N.F.P.A. 25.
5. RUN FIRE PROTECTION PIPING AS HIGH AS POSSIBLE TO MAINTAIN MAXIMUM
HEADROOM IN ALL AREAS. COORDINATE ALL WORK WITH OTHER TRADES.
C.ti.`s' �;t �nUTt•4
-t)jr,c,
I-OTlON
ApPp'J\1ED 13Y'.:' -
�. az
e
�JAT1n: __-----
'.7115
Q7
�1
suu
Y
Y
Y Y r r Y #26000522
O
.J U
t ; I
O �
c H
y o W I
cn
y LL _H
V4
U
u � C
� t
O �
N �
2
W
o I
w
N
m
o
d N
t o
M
U
o
p N
n' h
. m
it W
ti
i
W O
i
r
U O I
C U
r z
ARCHITECTURE INTERIOR DESIGN PLANNING
SEAL.
MONEY J. MATEU
AR 0002220
JMM CONSULTING ENGINEERS, LLC
M.E.P.
12651 S DIXIE HIGHWAY, SUITE 209
MIAMI, FLORIDA 33156
M.A. SUAREZ CONSULTING ENGINEERS
STRUCTURAL ENGINEERING
4869 SW 75TH AVENUE
MIAMI, FLORIDA 33155
PISTQRINO b ALAM CONSULTING ENG. INC.
CIVIL ENGINEERING
7171 SW 62ND AVENUE, 4TH FLOOR
MIAMI, FLORIDA 33143
OXFORD UNIVERSAL
4311 PONCE DE LEON BLVD.
CORAL GABLES, FLORIDA 33146
5966 BOUTH
DIXIE BUILDING
5966 & 5970
SOUTH DIXIE HIGHWAY
MIAMI, FLORIDA 33133
�If B�II•�a�17BiB1�1lI1.1B1I�[•.
THIS DRAWING IS THE PROPERTY OF MATEU
ARCHITECTUREINC.UNLESS OTHERWISEPROVIDED
FOR BY CONTRACT- THE CONTENTS OF THIS
DRAWING ARE CONFIDENTIAL AND SHALL NOT
BE TRANSMITTED TO ANY PARTY EXCEPT AS
AUTHORRFO BY THE ARCHITECT/ENGINEERS OF
RECORD.
PHASE
PERMIT DRAWINGS
FILE NAME.
M A0605\CD\SHEET\ARCH\A-101.bWG
PROJECT NO
MA0605
DRAWN BY:
JMM
CHECKED BY:
JMM
ISSUE DATE:
DECEMBER 10, 2007
REVISIONS
SHEET TITLE
FIRE PROTECTION NOTES
& DETAILS