08-40-226REDUCING COUPLING 1" SUPPLY UNE--, UPPER SL PIECE WALL ESCUTCHEON FINISHED WALL LINE SIDEWALL SPRINKLER HEAD MOUNTING DETAIL N.T.S. FINISHED CEILING LINE .Y UNE COUPLING DEFLECTOR (DISTANCE BELOW CEILING SHALL eE IN ACCORDANCE WITH MFR'S, LISTING) CEILINGD__/ CEILING ESCUTCHEON LINE DEFLECTOR RECESSED PENDENT TYPE SPRINKLER HEAD MOUNTING DETAIL N.T.S. DRAIN RISER � I TO DRAIN - BLACK STEEL PIPE WELDED OR VICTAULIC COUPLING - STANDPIPE RISER INDICATING TYPE FLOOR CONTROL - VALVE W/ SUPERVISORY SWITCH PRESSURE GAUGE WATER FLOW SWITCH r FEED MAIN TO SPRINKLER SYSTEM SIGHT GLASS AUXILIARY DRAIN VALVE INSPECTOR'S TEST VALVE 1" UNION W/BRASS ORIFICE DISK W/ HOLE EQUAL TO DISCHARGE FROM A SPRINKLER ORIFICE SPRINKLER TEST & FLOOR CONTROL VALVE N.T.S. SPRINKLER HEAD SCHEDULE AREA SERVED MFR. & ORIFICE I CONFIGURATION TEMP. FINISH DESIGN FIRE MAIN MODEL NO. K -FACTOR 8 RATING -0- INFO. AREAS WITH VIKING -� UPRIGHT PENDENT 12 WHITE pQ EXPOSED STRUCTURE MICROFAST�2"G VK300/VK302 5. QUICK RESPONSE STANDARD ORDINARY POLYESTER -"` -�- CH.V. 15 COVERAGE O COATING MODEL 1800 AREAS WITH VIKING F.H. RECESSED PENDENT FIRE HYDRANT WHITE F.H.C. DROPPED MICROFAST1 2" QUICK RESPONSE ORDINARY FIRE HOSE RACK CEILINGS VK302 -5.G STANDARD F.STP. POLYESTER --` FLSW. COVERAGE �H COATING AREAS WITH VIKING R.M.V. SIDEWALL ROOF MANIFOLD VALVE WHITE T.SW. SIDEWALL SPRINKLERS MICROFAST VK305 112" K 5.B QUICK RESPONSE STANDARD ORDINARY POLYESTER --- COVERAGE COATING PIT OF ELEVATOR VIKING MICROFAST 1/2' SIDEWALL QUICK RESPONSE INTERMEDIATE WHITE HOISTWAY VK305 IICC 5.B STANDARD POLYESTER --- COVERAGE COATING TOP OF VIKING MICROFAST112" UPRIGHT/PENDENT QUICK H ESPONSE WHITE ELEVATOR HOISTWAY VK30O/VK302 1{ 5.i STANDARD INTERMEDIATE POLYESTER --- COVERAGE COATING NOTES: 1. ALL SPRINKLERS TO BE U.L LISTED QUICK RESPONSE UNLESS NOTED OTHERWISE. 2. WHITE POLYESTER SPRINKLER FINISH TO BE U.L. LISTED CORROSION RESISTANT. TYPICAL VERTICAL PIPE SUPPORT DETAIL N.T.S. DEFLECTOR TO BE MAXIMUM 12" BELOW BOTTOM OF ROOF/ FLOOR DECK IN ACCORDANCE WITH N.F.P.A. 13 REQUIREMENTS (UNOBSTRUCTED CONSTRUCTION) AX. 22" ALLOWED FOR OBSTRUCTED CONSTRUCTION BRANCH LINE TEE PIPE RISER RISER CLAMP ANVIL/ GRINNELL NO. 261 OR EQUAL NEOPRENE TYPE ISOMODE PAD CONC. SPACER CONIC. SLAB PIPE SLEEVE REFER TO FIRESTOPPING DETAIL THIS SHEET ROOF OR FLOOR MOVE FIRE PROTECTION LEGEND SYMBOL A BREV. DESCRIPTION .____ - - - - - F- 2 I � I FIRE MAIN -Q- G 8 PENDENT SPRINKLER HEAD -0- 12 2 1/2" GATE UPRIGHT SPRINKLER HEAD -� 12 12 SIDEWALL SPRINKLER HEAD pQ BFV FIRE VALVE INDICATING TYPE NUTTERFLY VALVE 12 OSxY 15 OUTSIDE SCREW AND YOKE GATE VALVE -�- CH.V. 15 CHECK VALVE O F.E. MODEL 1800 FIRE EXTINGUISHER LUGS F.H. THREADS FIRE HYDRANT BY F.H.C. FIRE DEPT. FIRE HOSE CABINET C� F.H.R. FIRE HOSE RACK F.S. FIRE SIAMESE C)+-- F.STP. FIRE STANDPIPE FLSW. FLOW SWITCH �H P.I.V. POST INDICATOR VALVE R.M.V. ROOF MANIFOLD VALVE T.SW. TAMPER SWITCH 0 HYDRAULIC REFERENCE POINT -----DEFLECTORTDP' CONC. SW EAM CLAMP W/ LOCK NUT UPRIGHT TYPE SPRINKLER HEAD STEEL I BEAM ,,; " # OR BAR JOIST • �;� ' " „, CENTER I BEAM �� . r ` m LOAD CLAW All THREADED - �J HANGER ROD DROP IN ANCHOR ALL THREADED ALL THREADED HANGER ROD HANGER ROD UPRIGHT TYPE SPRINKLER HEAD MOUNTING DETAIL N.T.S. 2 1/2- GAT VALVE IN STAIR WELL7 -� 2 162" X 1 1! RED CER (TYP. 1 1/2" CAP - FIRE DEPT. VALVES TO BE LOCATED AT 4'-0" A.F.F. TYPICAL STANDPIPE EIRE DEPARTMENT CONNECTION N.T.S. CROSSMAIN BRANCH LINE RISER NIPPLE SCREW GROOVE TYPE CAP TYPE CAP NOTE: ALL CRDSSMAINS SHALL TERMINATE IN MIN. 1 1/4" PIPEALL BRANCH LINES ON GRIDDED SYSTEMS SHALL BE ARRANGED TO FACILITATE FLUSHING OF THE SYSTEM. TYPICAL FLUSHING CONNECTION CROSSMAIN N.T.S. ALL THRER HANGER R NUT CLEVIS HAN, PIPE 0.0 PIPE FASTENERS POWDER DRIVEN STUDS MAY USED IN LIEU OF LISTED CONCRETE N.T.S. INSERTS WHERE APPROVED BY STRUCNRAL ENGINEER ALL FASTENERS SHALL BE LSnD FOR THEIR INTENDED SERVICE ALL HANGERS, HANGER RODS, CLAWS, COUPLINGS, ETC. SHALL ALL THREADED _ BE PROVIDED WITH FACTORY HANGER ROD APPLIED HOT DIWO GALVANIZED FINISH FOR CORROSION PROTECTION NUT ADJUSTAILE SWIVEL LOOP HANGER PIPE ROD TO XTE]ND ROD TO IF MPE TOP OF MPE PIPE HANGERS N.T.S. ALL HANGERS SHALL BE LISTED FOR THEIR INTENDED SERVICE HANGER ROD SIZES UP TO 4" PIPE 3/8" DIA. 5" TO 8" PIPE 1/2" DIA. 10 12" PIPE 5/8" DIA. MAXIMUM HANGER SPACING (FT.) STANDPIPE RISER 3/4 .._.... fr I .____ - - - - 1 1/2 2 I � I 3 4 G 8 THREADED LIGHTWALL STEEL PIPE N/A 12 2 1/2" GATE 12 12 12 12 VALVE N/A N/A FIRE VALVE N/A 12 CABINET WHERE 15 15 I ON DWGS.) 15 15 -SHOWN POTTER-ROEMER 15 L MODEL 1800 LUGS _ _ _ _ -J FOR SPANNER SERIES THREADS AS APPROVED BY LOCAL FIRE DEPT. FIRE DEPT. VALVES TO BE LOCATED AT 4'-0" A.F.F. TYPICAL STANDPIPE EIRE DEPARTMENT CONNECTION N.T.S. CROSSMAIN BRANCH LINE RISER NIPPLE SCREW GROOVE TYPE CAP TYPE CAP NOTE: ALL CRDSSMAINS SHALL TERMINATE IN MIN. 1 1/4" PIPEALL BRANCH LINES ON GRIDDED SYSTEMS SHALL BE ARRANGED TO FACILITATE FLUSHING OF THE SYSTEM. TYPICAL FLUSHING CONNECTION CROSSMAIN N.T.S. ALL THRER HANGER R NUT CLEVIS HAN, PIPE 0.0 PIPE FASTENERS POWDER DRIVEN STUDS MAY USED IN LIEU OF LISTED CONCRETE N.T.S. INSERTS WHERE APPROVED BY STRUCNRAL ENGINEER ALL FASTENERS SHALL BE LSnD FOR THEIR INTENDED SERVICE ALL HANGERS, HANGER RODS, CLAWS, COUPLINGS, ETC. SHALL ALL THREADED _ BE PROVIDED WITH FACTORY HANGER ROD APPLIED HOT DIWO GALVANIZED FINISH FOR CORROSION PROTECTION NUT ADJUSTAILE SWIVEL LOOP HANGER PIPE ROD TO XTE]ND ROD TO IF MPE TOP OF MPE PIPE HANGERS N.T.S. ALL HANGERS SHALL BE LISTED FOR THEIR INTENDED SERVICE HANGER ROD SIZES UP TO 4" PIPE 3/8" DIA. 5" TO 8" PIPE 1/2" DIA. 10 12" PIPE 5/8" DIA. MAXIMUM HANGER SPACING (FT.) PIPE SIZE (IN.) 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 G 8 THREADED LIGHTWALL STEEL PIPE N/A 12 12 12 12 12 12 N/A N/A N/A STEEL PIPE EXCEPT THREADED LIGHTWALL N/A 12 12 15 15 15 15 15 15 15 NOTES: 1. MAXIMUM DISTANCE BETWEEN END UPRIGHT SPRINKLER AND LAST HANGER ON BRANCH LINES SHALL NOT EXCEED 36" FOR 1" PIPE, 48" FOR 1 1/4" PIPE AND CO" FOR 1 1/2" OR LARGER PIPE SIZE. EXTEND BRANCH LINE AND PROVIDE ADDITIONAL HANGER WHERE REQUIRED. 2. MAXIMUM HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A SPRINKLER, SPRINKLER DROP OR SPRIG -UP SHALL NOT EXCEED 24" 3. MINIMUM DISTANCE BETWEEN A HANGER AND CENTERLINE OF AN UPRIGHT SPRINKLER TO BE 311 . 4. WALL MOUNTED SIDEWALL SPRINKLERS SHALL BE RESTRAINED TO PREVENT MOVEMENT. 5. HANGERS FOR MAINS SHALL BE IN ACCORDANCE WITH SPACING TABLE ABOVE OR BETWEEN EACH BRANCHLINE, WHICHEVER IS THE LESSER DIMENSION. MIN. SIZE LINE TEE SIZE REMOVEMLE CAP TRAPPED WATER VOLUME >5 GAL. < 50 GAL.: 3/4" MIN DRAIN VALVE REQ'D. TRAPPED WATER VOLUME >50 GAL.: 1" MIN. DRAIN VALVE PIPED TO AN ACCESSIBLE LOCATION REQ'D. AUXILIARY DRAIN DETAIL N.T.S. FIRE PROTECTION NOTES & DETAILS N.T.S. GENERAL NOTES 1. ALL PIPING,HANGERS,SUPPORT METHODS AND SPRINKLER HEADS TO BE 1 INSTALLED IN STRICT ACCORDANCE WITH N.F.P.A. 13, AND ALL LOCAL CODES AND ORDINANCES. 2. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN 1 ACCORDANCE WITH N.F.P.A. 13 AND N.F.P.A. 13R. 3. ALL RATED WALLS AND FLOORS TO BE PROPERLY SLEEVED AND SEALED WITH APPROVED FIRE/SMOKE STOP MATERIAL 4. HYDRAULIC DATA PLACE CARD TO BE PLACED ON SYSTEM RISER(S). 20 5. ALL SPRINKLER HEADS IN ELEVATOR MACHINE ROOMS,ELECTRICAL ROOMS AND MECHANICAL ROOMS SHALL BE PROVIDED WITH HEAD GUARDS. G. PROVIDE INSPECTOR'S TEST CONNECTION AND DRAIN AS PER N.F.PA 13 REQUIREMENTS. 7. TEMPERATURE CLASSIFICATION FOR ALL SPRINKLER HEADS SHALL BE ORDINARY UNLESS NOTED OTHERWISE IN THE DRAWINGS. SPRINKLERS IN ELEVATOR HOISTWAYS AND ELEVATOR MACHINE ROOMS SHALL BE INTERMEDIATE TEMPERATURE RATING (175-225 DEGREES). 2 8. DESIGN CRITERIA: DESIGN CRITERIA SHALL BE BASED ON N.F.P.A. 13, ORDINARY HAZARD GR. I, .15 GPM PER SQ. FT., 250 GPM HOSE ALLOWANCE, 1500 SQ. FT. REMOTE AREA, MAX. 130 SQ. FT. COVERAGE PER SPRINKLER HEAD (PARKING GARAGE, MECH. ROOMS) DESIGN CRITERIA SHALL IE BASED ON N.F.P.A. 13, LIGHT HAZARD .10 GPM PER SQ. FT., 100 GPM HOSE ALLOWANCE, 1500 SQ. FT. REMOTE AREA, MAX. 225 SQ. FT. COVERAGE PER SPRINKLER HEAD. (ALL OTHER PUBLIC SPACE AREAS, TENANT AREAS) 22 DESIGN CRITERIA SHALL BE BASED ON N.F.P.A. 13, ORDINARY HAZARD GROUP 2, .20 GPM PER SQ. FT., 250 GPM HOSE ALLOWANCE, 1500 S.F. REMOTE AREA. (TENANT AREAS) 23 STANDPIPE SYSTEM TO BE A MANUAL WET TYPE, CLASS I, AS ALLOWED BY NEPA 14 FOR BUILDINGS NOT CLASSIFIED AS HIGH RISE BUILDINGS. PROVIDE SIGNAGE AT EACH HOSE CONNECTION "MANUAL STANDPIPE FOR 2 FIRE DEPARTMENT USE ONLY". 9. ALL VALVES CONTROLLING WATER SUPPLY SHALL BE PROVIDED WITH A SUPERVISORY (TAMPER) SWITCH.000RDINATE LOCATION OF ALL FLOW AND TAMPER SWITCHES WITH ELECTRICAL CONTRACTOR. 2 10.ALL PIPING ABOVE GROUND SHALL BE LIGHTWALL THREADABLE STEEL PIPE FOR 2" AND SMALLER, GROOVED SCHEDULE 10 STEEL PIPE FOR PIPING 2 1/2" AND LARGER. ALLIED XL AND ALLIED SCH. 10 OR APPROVED EQUAL FITTINGS FOR PIPING 2" AND SMALLER SHALL BE MALLEABLE IRON, 150 PSI BANDED,THREADED,BLACKANSI B 16.3. JOINT COMPOUND OR TAPE SHALL BE APPLIED ONLY TO MALE THREADS. SCREWED UNIONS SHALL NOT BE USED ON PIPE LARGER THAN 2 INCH. FITTINGS FOR PIPING 2 1/2" AND URGER SHALL BE MECHANICAL COUPLING SYSTEM AS MANUFACTURED BY VICTAULIC CORP.OR GRINNELL CORP. "GRUVLOCK'. ALL GROOVED FITTINGS SHALL BE FROM SAME MANUFACTURER. ALL PIPING AT EXTERIOR OR OPEN TO EXTERIOR TO BE FACTORY GALVANIZED PIPE AND FITTINGS. (TYP. AT PARKING GARAGE AND ALL AREAS WHERE APPLICABLE). UNDERGROUND PIPING SHALL BE CEMENT LINED DUCTILE IRON PIPE AND FITTINGS WITH ASPHALTIC EXTERIOR COATING CONFORMING TO ANSI/AWWA C151/A21.51 AND C104/A21.4. RUBBER GASKET JOINTS SHALL CONFORM TO ANSI/AWWA C111/A21.11, ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH N.F.P.A. 24. PROVIDE RESTRAINING FOR FIRE MAINS CONSISTING OF THRUST BLOCKS, TIE RODS, LOCKED MECHANICAL OR PUSH -ON JOINTS IN ACCORDANCE WITH N.F.P.A. 24 REQUIREMENTS. UNDERGROUND PIPING SHALL BE BURIED WITH MINIMUM 36" COVER. REFER TO CIVIL ENGINEER DRAWINGS. ALL PIPING SHALL BE CONTINUOUSLY MARKED ALONG IT'S LENGTH BY THE MANUFACTURER'S NAME, MODEL DESIGNATION AND/OR SCHEDULE IN ACCORDANCE WITH N.F.P.A. 13. 11.PRESSURE TEST AND FLUSH THE SYSTEM IN ACCORDANCE WITH N.F.P.A. 13 AND N.F.P.A. 14 REQUIREMENTS. SUBMIT CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND AND ABOVEGROUND PIPING. ALL WATERFLOW SWITCHES AND SUPERVISORY SWITCHES SHALL BE TESTED FOR PROPER OPERATION AND ANNUCIATION. FURNISH TO OWNER'S REPRESENTATIVE ALL LITERATURE AND INSTRUCTIONS FOR THE PROPER OPERATION AND MAINTENANCE OF ANY EQUIPMENT AND DEVICES INSTALLED AND A COPY OF N.F.P.A. 25 -"STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEM". 12.PROVIDE AUXILIARY DRAIN CONNECTION FOR ALL TRAPPED PIPING SECTIONS IN ACCORDANCE WITH N.F.PA 13,PROVIDE FLUSHING CONNECTIONS AS REQUIRED. REMOVEABL.E FITTINGS SHALL BE PROVIDED AT END OF CROSSMAINS. PROVIDE MINIMUM 1/4 IN. RELIEF VALVE AT GRIDDED SYSTEMS (SET AT 165 PSI) IN ACCORDANCE WITH N.F.PA 13. ALI_ BRANCH LINES ON GRIDDED SYSTEMS SHALL BE ARRANGED TO FACILITATE FLUSHING OF THE PIPING. 13.ALL FIRE PROTECTION PIPING, EQUIPMENT AND DEVICES SHALL BE U.L. LISTED AND FACTORY MUTUAL GLOBAL APPROVED. 14.GATE VALVES 2" AND SMALLER SHALL BE O.S.&Y. THREADED BRONZE, RISING STEM,WEDGE DISC,175 WWP.GATE VALVES 2 1/2" AND LARGER SHALL BE O.S.&Y. FLANGED IBBM RISING STEM,SQLID WEDGE DISC,175 WWP.ALL GATE VALVES SHALL BE U.L. LISTED AND F.M. APPROVED. BUTTERFLY VALVES WITH OR WITHOUT INTEGRAL SUPERVISORY SWITCH MAY BE USED WHERE PERMITTED BY N.F.P.A. 13. 15.CHECK VALVES 2 1/2" AND LARGER SHALL BE FLANGED IBBM SWING TYPE,BRONZE MOUNTED,175 WWP CLASS,U.L. LISTED AND F.M. APPROVED. 16.SUPERVISORY SWITCHES SHALL BE 120 VOLT CLOSED CIRCUIT TAMPER SWITCH, U,L LISTED AND F.M. APPROVED.FLOW SWITCHES SHALL BE PADDLE TYPE,SINGLE POLE, DOUBLE THROW WITH ADJUSTMENT FOR SENSITIVITY TO FLOW WITH TIME DELAY, U.L LISTED AND F.M. APPROVED. SUPERVISORY AND WATERFLOW SWITCH TO BE POTTER ELECTRIC SIGNAL CO. OR APPROVED EQUAL. 17.HOSE THREADS AT FIRE DEPARTMENT CONNECTIONS SHALL CONFORM WITH LOCAL FIRE DEPARTMENT STANDARDS. FIRE DEPARTMENT CONNECTIONS SHALL BE AS MANUFACTURED BY POTTER-ROEMER OR EQUAL •rY� ••• • • •uYri V i Y Y W V •• i Y Y i • Y U Y N • r • Y y • r " r• I" Y W M • Y • •. i y, r c y • r u rr Y a• u yup • r • • r V Y V i 4 V • Y • • • u U Y • ♦ • • 4 V V V•• • i f i• V y V I • • N y! • V•• V V u V i i • Y V Y r ,, • • U• U • Y Y Y i V i V• • i. l.THE WORK THAT IS TO BE DONE UNDER THIS CONTRACT INCLUDES THE FURNISHING OF ALL LABOR,MATERIALS AND EQUIPMENT,PERMffS,FEES,INSPECTIONS,TESTS, INSURANCE,ETC. REQUIRED FOR THE COMPLETION OF FIRE PROTECTION SYSTEM SHOWN ON THE DRAWINGS AND LISTED HEREIN. 9.THE DRAWINGS ARE GENERALLY DIAGRAMMATIC.THEY DO NOT SHOW EVERY NEND,OFFSET OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES. VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FAMRICATION OF PIPING AND INSTALLATION OF EQUIPMENT AND MATERIALS. . SPRINKLER HEADS SHALL RE AUTOMATIC, CAST BRASS GLASS NULLA OR FUSIBLE LINK TYPE, ORDINARY TEMPERATURE RATING UNLESS NOTED OTHERWISE, CONFIGURATION AS NOTED ON DRAWINGS. FACTORY COATING OR FINISH SHALL BE AS NOTED ON SPRINKLER HEAD SCHEDULE. ALL SPRINKLERS SHALL BE PROVIDED WITH MARKINGS DESIGNATING ORIFICE SIZE, DEFLECTOR CHARACTERISTIC AND THERMAL SENSITIVITY. INSTALLATION SHALL BE IN ACCORDANCE WITH N.F.P.A. 13 AND WITH MANUFACTURER'S INSTRUCTIONS. REFER TO SPRINKLER HEAD SCHEDULE THIS SHEET. 1. PROVIDE IDENTIFICATION FOR ALL PIPING, VALVES, ETC. ASSOCIATED WITH THE FIRE PROTECTION SYSTEM. COLOR BANDS, LEGEND AND FLOW ARROWS AT PIPE MARKERS SHALL IE IN ACCORDANCE WITH ANSI A13.1 A. PROVIDE SIGNAGE WITH MIN. 1 INCH HIGH LETTERING AT FIRE DEPARTMENT CONNECTIONS. 1. PROVIDE HYDRAULIC DESIGN INFORMATION SIGNS) AT SPRINKLER SYSTEMS IN ACCORDANCE WITH N.F.P.A. 13 C. ALL MAIN AND SECTIONAL CONTROL VALVES, DRAIN VALVES, TEST CONNECTION VALVES SHALL BE PROVIDED WITH PERMANENTLY MARKED WEATHERPROOF IDENTIFICATION SIGNS IN ACCORDANCE WITH N.F.PA 13 . ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, N.F.P.A. 13, 14, 20, 24, 25 , 101 AND IN ACCORDANCE WITH ALL LOCAL CODES AND ORDINANCES. . ALL WORK SHALL BE PERFORMED BY STATE LICENSED AND CERTIFIED PERSONNEL IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE 4A-46 is 4A-48. SUBMIT TO OWNER'S REPRESENTATIVE AS BUILT DRAWINGS, OWNER'S MANUALS, MAINTENANCE MANUALS. 4. FIRE PUMP SYSTEM SHALL BE IN ACCORDANCE WITH N.F.PA 20 REQUIREMENTS. TESTING OF FIRE PUMP SYSTEM SHALL BE IN ACCORDANCE WITH CHAPTER 11 OF N.F.P.A. 20. PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THE FIRE PUMP SYSTEM SHALL BE IN ACCORDANCE WITH N.F.P.A. 25. 5. RUN FIRE PROTECTION PIPING AS HIGH AS POSSIBLE TO MAINTAIN MAXIMUM HEADROOM IN ALL AREAS. COORDINATE ALL WORK WITH OTHER TRADES. C.ti.`s' �;t �nUTt•4 -t)jr,c, I-OTlON ApPp'J\1ED 13Y'.:' - �. az e �JAT1n: __----- '.7115 Q7 �1 suu Y Y Y Y r r Y #26000522 O .J U t ; I O � c H y o W I cn y LL _H V4 U u � C � t O � N � 2 W o I w N m o d N t o M U o p N n' h . m it W ti i W O i r U O I C U r z ARCHITECTURE INTERIOR DESIGN PLANNING SEAL. MONEY J. MATEU AR 0002220 JMM CONSULTING ENGINEERS, LLC M.E.P. 12651 S DIXIE HIGHWAY, SUITE 209 MIAMI, FLORIDA 33156 M.A. SUAREZ CONSULTING ENGINEERS STRUCTURAL ENGINEERING 4869 SW 75TH AVENUE MIAMI, FLORIDA 33155 PISTQRINO b ALAM CONSULTING ENG. INC. CIVIL ENGINEERING 7171 SW 62ND AVENUE, 4TH FLOOR MIAMI, FLORIDA 33143 OXFORD UNIVERSAL 4311 PONCE DE LEON BLVD. CORAL GABLES, FLORIDA 33146 5966 BOUTH DIXIE BUILDING 5966 & 5970 SOUTH DIXIE HIGHWAY MIAMI, FLORIDA 33133 �If B�II•�a�17BiB1�1lI1.1B1I�[•. THIS DRAWING IS THE PROPERTY OF MATEU ARCHITECTUREINC.UNLESS OTHERWISEPROVIDED FOR BY CONTRACT- THE CONTENTS OF THIS DRAWING ARE CONFIDENTIAL AND SHALL NOT BE TRANSMITTED TO ANY PARTY EXCEPT AS AUTHORRFO BY THE ARCHITECT/ENGINEERS OF RECORD. PHASE PERMIT DRAWINGS FILE NAME. M A0605\CD\SHEET\ARCH\A-101.bWG PROJECT NO MA0605 DRAWN BY: JMM CHECKED BY: JMM ISSUE DATE: DECEMBER 10, 2007 REVISIONS SHEET TITLE FIRE PROTECTION NOTES & DETAILS