08-40-225LIGHTING FIXTURE SCHEDULE
Type
Luminaire
Description
Manufacturer and
Catalog Number
Volts
Lgmp InfqrmationMounting
��� W..
V • ' U
` '
Finish
Remarks
No.
Type /Base/Color/CRI
A
4' SURFACE FLUORESCENT
KENALL
MLHA8 48 -R -MW -PP -2 -32 -ED -1 -DV
DUAL
2
32W T-8 MED. BI -PIN
4100082 CRI
SURFACE
WHITE
UL LISTED FOR WET LOCATION
B
ELEVATOR PIT LIGHT
HUBBELL
ZVW-100TW
120
1
10OW A-19
FROSTED
WALL
WHITE
UL LISTED FOR WET LOCATION
C
4' ENCLOSED FLUORESCENT
COLUMBIA
UNIV
2
32W T-8 MED. BI -PIN
SURFACE
WHITE
UL LISTED FOR WET LOCATION
D
4' FLUORESCENT STRIP
TEMPORARY
COLUMBIA
CS4-232-E-U-CSW
UNIV
2
32W 1-8 MED. BI -PIN
41000 82 CRI
SURFACE
WHITE
E
EMERGENCY LIGHT
COMPASS
SEU2
DUAL
2
5.0 HALOGEN
INCLUDED
WALL 7 AFF
WHITE
F
EXTERIOR DECORATIVE LIGHT
KIM
120
1
32W TT 4P GX24q-3
WALL 7 AFF
WHITE
UL LISTED FOR WET LOCATION
G
5" PL DOWNLIGHT
PEACHTREE
PEF-52 6-C- 120
120
1
26W TT 4P GX24q-3
100K A9 CRI
RECESSED
CLEAR
ALUMINUM
H
4' LOW PROFILE WEATHER-PROOF
FLUORESCENT
THE LIGHT EDGE
MON/154/120/WB/PEND
120
1
54W T-5/HO MINI BI -PIN
41000 82 CRI
PENDANT
WHITE
EVEN WITH BOTTOM OF TEES AND/OR
XPOSED B MS
H1
4 LOW PROFILE WEATHER-PROOF
FLUORESCENT WITH BATT PACK
THE LIGHT EDGE
MON 154 120 WB EM PEND
120
1
54W T'-5/HO MINI BI -PIN
41000 82 CRI
PENDANT
WHITE
EVEN WITH BOTTOM OF TEES AND/OR
EXPOSED BEAMS
H2
HID GARAGE LUMINAIRE
KIM
120
1
10OW PMH ED -17 MED. BASE
PENDANT OR
WHITE
WEATHER-PROOF IP66 RATED
H3
HID GARAGE LUMINAIRE
KIM
PGL53 100PMH120 A PW2
120
1
10OW PMH ED -17 MED. BASE
PENDANT OR
SURFACE
WHITE
WEATHER-PROOF IP66 RATED
THRU POWERCLONE INVERTER
I
SMALL DECORATIVE FLOOD LIGHT
KIM
CFL1 Z42PL120 CC -P J -27N
120
1
42W TT 4P GX24q-3
41OOK 82 CRI
SURFACE WITH
J- 7N
COLOR BY
ARCHITECT
UL LISTED FOR WET LOCATION
J
8" PL PENDANT CYLINDER
PEACHTREE
- - 20 -WL -PND -XX
120
2
32W TT 4P GX24q-3
410Q 92
PENDANT
WHITE
K
CONCEALED EMERGENCY LIGHT
WITH REMOTE EMERG. PANELS
SIGNTEX
CVRE-50-24-DP-SM
120/12
2
-CRI
50W MR -16
INCLUDED
PENDANT ON
SURFACE BOX
WHITE
EVEN WITH BOTTOM OF TEES AND/OR
EXPOSED
L
HID CUT-OFF DECORATIVE WALL
PACK
KIM
WD14x4 75MH120 WH -P HS
120
1
175W MH ED -17 MED. BASE
38000 65 CRI
WALL ABOVE 12
ON SIDE OF MLDG
WHITE
UL LISTED FOR WET LOCATION
M
2X4 TROFFER
COLUMBIA
UNIV
232W
T-8 MED. BI -PIN
LAY -IN
WHITE
N
5" PL DOWNLIGHT
PEACHTREE
PFF532-C-120
120
1
32W TT 4P GX24q-3
41nm/A9 CRI
RECESSED
CLEAR
ALUMINUM
0
4' LOW PROFILE WEATHER-PROOF
FLUORESCENT
THE LIGHT EDGE
MON 154 XX WB EM
120
1
54W T-6/HO MINI BI -PIN
41000 82 CRI
SURFACE
WHITE
1250 LUMENS BATTERY PACK
P
41" FLUORESCENT VANITY LIGHT
VISA
CB6440-2F39-120-BA
120
2
39W T5 21311
41000 82 CRI
6" ABOVE MIRROR
BRUSHED
ALUMINUM
Q
AIRCRAFT WARNING LIGHT
TWR
120
2116A-21/TS
SURFACE
GREY
FAA APPROVED
R
PL WALL PACK
KENALL
H612EM-C-MW-32P-2-DV
DUAL
2
32W TT 4P GX24q-3
41000 82 CRI
SURFACE
WHITE
S
LOW WATTAGE HID CUT-OFF
WALL PACK
KENALL
FN15D-IV-8G-MB-70M-1 S
120
1
70W MH ED -17 MED. BASE
42000 82 CRI
WALL +10 AFF
ON BLDG WALL
WHITE
UL LISTED FRO WET LOCATION
T
FLOURESCENT STEP LIGHT WITH
INTF('RAI FMERG. BATTERY PACK
COLE
2156-E2156-2 J -W -TP -EM -XXX
120
2
13W TT 2P GX23 PH
R2 CRI
WALL 3 AFF
COLOR BY
ARCHITECT -
UL LISTED FOR WET LOCATION
X
THERMOPLASTIC LED EXIT SIGN
___4100
COMPASS
DUAL
NIA
RED LED'S
UNIVERSAL
WHITE
SINGLE AND DOUBLE FACE EXIT SIGN
X1
_.._.
WP LED EXIT SIGN WITH EMERG.
BATTER
COLE
120
NIA
RED LED'S
LNl(11 UDFD
TOP
WHITE
UL LISTED FOR WET LOCATION
NEC 300-19 (b) SUPPORT BUSHING, LOCATED AT THE TOP OF
A VERTICAL CONDUIT AT CABINET OR PULL NOS, PREVENTS THE
WEIGHT OF THE CONDUCTORS FROM DAMAGING THE INSULATION
OR RACING A STRAIN ON TERMINATION POINTS.
BUSHING SUPPORT DETAIL
N.T.S.
CLAMP
RISER CLAMP
FEEDER SUPPORT 3/16"X1-1/2"
GALVANIZED STEEL
SECURE CLAMP WITH TWO
1/2-0 X 1/2- LONG BOLTS
LOCKWASHER, AND NUT
FEEDER/RISER CONDUIT
FINISHED FLOOR
FLOOR:CONCRETE FLOOR
% �'.:' i' �' • ' '' SLAB DIMENSION
VARIES
METAL FLOOR I FILL SPACE BETWEEN
SLEEVE SLEEVE h CONDUIT
WITH SEALING COMPOUND
FOR FULL DEPTH
FEEDER CONDUIT SLEEVE DETAIL
N.T.S.
ELEVATOR ELECTRICAL NOTES
1. PROVIDE ELEVATOR DISCONNECT INSIDE ELEVATOR MACHINE ROOM WITH TIME
DELAY FUSES (RK5) WITH REJECTION CLIPS. FUSES ARE TO BE SIZED AS
REQUIRED BY ELEVATOR COMPANY SHOP DRAWINGS. (NEC 620-51).
2. PROVIDE A DEDICATED 120V, 20A, BRANCH CIRCUIT PER NEC 620-22 FOR
ELEVATOR CAR LIGHTS WITH A DISCONNECTING MEANS, (MUST RE LOCKABLE IN
THE OPEN POSITION AND WIRED TO ELEVATOR CONTROLLER).
3. LIGHT FIXTURE INSIDE ELEVATOR MACHINE ROOM SHALL BE LENSED TYPE; OR
IF INDUSTRIAL TYPE, SHALL BE PROVIDE WITH WIRE CARDS AND TUBE GARD.
4. PROVIDE A 20A, 125V, GFI RECEPTACLE IN ELEVATOR MACHINE ROOM AND PIT.
5. PROVIDE A DEDICATED TELEPHONE LINE TO ELEVATOR CONTROLLER. (ONE
DEDICATE LINE PER ELEVATOR).
6. ELEVATOR CAB(S) SHALL BE PROVIDED WITH A TELEPHONE OR A MEANS OF
TWO-WAY COMMUNICATION.
7. PROVIDE TWO VAPOR TIGHT LIGHT FIXTURES CONTROLLED BY A SWITCH INSIDE
EACH ELEVATOR PIT.
8. WHEN A HYDRAULIC ELEVATOR HAS PROVISIONS FOR LOWERING BY BATTERY,
THE MACHINE ROOM DISCONNECT, WHILE IN THE "OFF' POSITION (OPEN), MUST
PREVENT THE ELEVATOR FROM LOWERING UNDER BATTERY POWER TO SHUT
DOWN THE BATTERY LOWERING FEATURE WITH THE ELEVATOR DISCONNECT
SWITCH, THE CONTRACTOR SHALL PROVIDE AN AUXILIARY SET OF CONTACTS IN
THAT SWITCH AND A PAIR OF #16 WIRES TO THE ELEVATOR CONTROLLER TO
DISABLE THE BATTERY LOWERING FUNCTION. THE BATTERY LOWERING FUNCTION
SHALL ALSO BE DISABLED UNDER SHUNT TRIP OPERATION, SEE BELOW.
9. WHEN A BUILDING IS PROTECTED BY A WET PIPE SPRINKLER SYSTEM AND
SPRINKLER HEADS ARE INSTALLED IN THE ELEVATOR SHAFT, THE ELEVATOR PIT,
AND THE ELEVATOR MACHINE ROOM. PROVIDE FIXED TEMPERATURE HEAT
DETECTOR NEXT TO EACH SPRINKLER HEAD ON THE TOP OF THE SHAFT, SIDE
OF THE ELEVATOR PIT, AND ELEVATOR MACHINE ROOM. HEAT DETECTOR
TEMPERATURE SHALL BE LOWER THAN SPRINKLER HEAD TEMPERATURE, VERIFY
WITH FIRE PROTECTION CONTRACTOR PRIOR TO ORDERING. THESE HEAT
DETECTORS ARE NOT CONNECTED TO THE BUILDING'S FIRE ALARM SYSTEM,
BUT ARE USED EXCLUSIVELY FOR TIRING OF THE ELEVATOR SERVICE
DISCONNECT AT THE MAIN ELECTRICAL ROOM. PROVIDE SHUNT TRIP BREAKER
AT EACH ELEVATOR SERVICE DISCONNECT.
IF ELEVATOR IS EQUIPPED WITH A BATTERY LOWERING FEATURE, AN ADDITIONAL
SET OF AUXILIARY CONTACTS MUST BE PROVIDED AT THE HEAT DETECTOR AND
2#16 WIRES SHALL BE PROVIDED TO THE ELEVATOR CONTROLLER TO DISABLE
THE BATTERY LOWERING FEATURE. IN LIEU OF ADDITIONAL CONTACTS AT THE
HEAT DETECTORS, THE CONTRACTOR SHALL PROVIDE ADDITIONAL WIRING FROM
THE SHUNT TRIP BREAKER TO THE ELEVATOR CONTROLLER TO DISABLE THE
BATTERY LOWERING FEATURE. THIS WIRING WILL BE INSTALLED IN SERIES WITH
THE AUXILIARY DISCONNEf SWITCH CONTACTS. THE DRY CONTACTS CONTAINED
IN THE AUXILIARY SWITCHES ARE CLOSED WHEN EITHER THE SHUNT TRIP OR
DISCONNECT IS IN THE "ON" POSITION AND WILL BE OPEN WHEN THE
DISCONNECT IS OPENED OR SHUNT TRIP/HEAT DETECTOR ACTIVATED.
ELECTRICAL SYMBOL LEGEND
FLUORESCENT LIGHT FIXTURE,
'Ef' EMERGENCY LIGHT W/BATTERY
1�0 WALL LIGHT
HM i WALL OR CEILING MOUNTED EXIT LIGHT FIXTURE WITH BATTERY BACK-UP.
ARROWS, NUMBER OF FACES AND MOUNTING AS REQUIRED TO INDICATE
A CLEAN PATH TO EXIT.
$ 120/277 V., 20 AMP., SINGLE POLE LIGHT SWITCH.
$3 120/277V., 20 AMP., THREE WAY SWITCH.
$M MANUAL MOTOR STARTER.
m ELECTRICAL PANEL
o -I FUSED DISCONNECT SWITCH SIZED PER EQUIPMENT NAMEPLATE.
® MAGNETIC MOTOR STARTER, PROVIDED BY MECHANICAL
CONTRACTOR, INSTALLED BY ELECTRICAL CONTRACTOR.
4 ELECTRIC MOTOR.
.IV\r EQUIPMENT CONNECTION WITH FLEXIBLE CONDUIT.
20A., 120 V., QUADRUPLEX RECEPTACLE, TWO DUPLEX IN
TWO BOX. 18" A.F.F.
20 A., 120., V., DUPLEX RECEPTACLE, GROUNDING ME,
U.Q.N. MOUNTED 11" A.F.F.
CEILING OR WALL MOUNTED JUNCTION BOX.
TELEPHONE OUTLET AT 11" A..F.F. (4" SQ. J. BOX)
' HOME RUN TO PANEL
ACCESSIBLE JUNCTION BRANCH CIRCUIT FINISH SLAB
BOX
f- J
GRID SUPPORT
3/8- FLEXIBLE CONDUIT. NEXT TO FIXTURE
MAX 6FT. AS PER NEC 3411aHTING FIXTURE J �-- FINISHED CEILING
RECESSED FLORESCENT LT. FIXTURE CONNECTION DETAIL
N.T.S.
NOTES:
1.- ALL RECESSED LIGHT FIXTURES ARE TO BE CONNECTED AS DETAILED.
2.- ALL JUNCTION BOXES ARE TO BE READILY ACCESIBLE.
3.- PROVIDE FIRE PROOF TENT AS REQUIRED TO KEEP UL CEILING RATING.
ADDRESSABLE FIRE ALARM SYSTEM NOTES
1. FURNISH AND INSTALL ALL LABOR, MATERIAL, AND EQUIPMENT NECESSARY FOR
AND DEVICES NEW ADDRESSABLE FIRE ALARM
PANEL AS SPECIFIED HEREIN AND AS SHOWN ON THE ELECTRICAL
DRAWINGS. THIS SYSTEM SHALL BE ZONED, ELECTRICALLY SUPERVISED,
HAVE CLOSED CIRCUITS, AND SHALL BE CONNECTED, TESTED
AND LEFT IN FIRST CLASS OPERATING CONDITION.
2. FIRE ALARM SYSTEM SHALL BE U.L LISTED NFPA 72 APPROVED.
3. UPON ACTIVATION OF FIRE ALARM SYSTEM BY MANUAL STATION, THE FOLLOWING SHALL TAKE PLACE:
A ENERGIZE ALARM SIGNALING DEVICES
I SOUND AUDIBLE ALARMS AND FLASH VISUAL SIGNALS
C ALERT LOCAL FIRE DEPARTMENT OR PROPRIETARY SYSTEM
D CAUSE ZONE IN ALARM TO BE DISPLAYED ON THE ANNUNCIATOR
4. ALL WIRING AND CONDUIT SIZE SHALL BE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION, AND
REQUIREMENTS OF NEC, LOCAL CODES AND NFPA IN NO CASE, SHALL THE WIRING ME SMALLER THAN #16
5. ALL CONDUCTORS SHALL BE COOPER AND SHALL BE SIZED FOR A MAXIMUM LOSS OF Id1. MINIMUM WIRE
SIZE SHALL BE AS REQUIRED BY MANUFACTURER IN NO CASE. SHALL THE WIRING BE SMALLER THAN J16
F.P.L. CU IN. 3/4 CONDUIT
6. QUANTITY OF WIRES PER DEVICES SHALL BE AS REQUIRED NY MANUFACTURER.
7. SYSTEM TO BE POWER LIMITED.
8. VISUAL ALARMS PER ANSI A117.1,4.26, FMC AND ADA
9. CONDUIT FOR FIRE ALARM SHALL BE METALLIC TYPE.
10. CONTRACTOR IS RESPONSIBLE FOR PROVIDING SIGNED A SEALED FIRE ALARM
PERMIT DRAWINGS BY A FLORIDA REGISTERED ENGINEER. JMM CONSULTING
ENGINEERS LLC IS NOT RESPONSIBLE FOR F/A PERMIT DWGS.
11. COORDINATE EXACT LOCATION OF ALL TAMPER k FROM SWITCHES WITH SPRINKLERS
DRAWINGS. ALL TAMPER is FROM SWITCHES SHALL ME MONITORED BY FACP.
12. ACTIVATION OF A SMOKE DETECTOR IN ANY ELEVATOR LOBBY OR ASSOCIATED ELEVATOR MACHINE
ROOM, OTHER THAN AT THE DESIGNATED LEVEL, SHALL CAUSE ALL CARS THAT SERVE THAT LOBBY
TO RETURN NON-STOP TO THE DESIGNATED LEVEL THE OPERATION SHALL CONFORM TO THE
REQUIREMENTS OF RULE 211.3A OF ASME/ANSI A17.1-1987 AS ADOPTED BY CHAPTER 4A-47 OF
THE DEPARTMENT OF INSURANCE, STATE FIRE MARSHAL.
NO DEVICE, OTHER THAN PHASE I SWITCH (RULE 211.3A) OR THE DETECTORS IN THE ELEVATOR
LOBBY OR ASSOCIATED MACHINE ROOM SHALL INITIATE PHASE I OPERATION.
IF THE SMOKE DETECTOR AT THE DESIGNATED LEVEL IS ACTIVATED, THE CARS SHALL RETURN TO
ALERNATE LEVEL APPROVED BY THE ENFORCING AUTHORITY, UNLESS THE PHASE I SWITCH (RULE
211.3A) IS IN THE "ON" POSITION. SMOKE DETECTOR ACTIVATION SHALL ONLY BE RESET MANUALLY.
FIRE ALARM LEGEND
E
]ETC.,
NOTIFIER NFS-640 ADDRESSABLE FIRE ALARM PANEL
PROVIDED DIALER, POWER SUPPLIES, ACCESORIES AND RELAYS AS REQUIRED.
AS REQUIRED.
H< ADA HORN/STROBE SYSTEM SENSOR jP21R (SEE FLOOR PLAN FOR CANDELA)
5D PHOTOELECTRIC SMOKE DETECTOR NOTIFIER #FSP -151 W/BASE 171OLID
sD SMOKE DUCT DETECTOR NOTIFIER #FSD-751PL WITH SAMPLING TUBES
HD HEAT DETECTOR NOTIFIER #FST -851 W/RASE 171OLP
R PULL STATION NOTIFIER #NIG-12LX
ADA STORME LIGHT SYSTEM SENSOR SR (SEE FLOOR PLAN FOR CANDELA)
(WP) UL LABELED WEATHER PROOF
REMOTE ANNUNCIATOR NOTIFIER LCD80
WQ-I ELEVATOR WARNING LIGHT 'DO NOT USE"
10. ALL SHALL BE THWN.
11. ALL CONDUCTORS SHALL BE COPPER RUN IN METALLIC CONDUIT.
12. ALL CONDUCTORS SHALL BE RUN IN CONDUIT METALLIC TYPE). IF PVC SCHEDULE 40 IS
USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN
ACCORDANCE WITH N.E.C. 250-122 MUST 8E INSTALLED AND CONDUIT SIZE INCREASED AS
REQUIRED.
13, ALL MATERIALS SHALL BE U.L. APPROVED.
14. NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED.
15. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
111. ALL NON POWER RELATED WIRING I N CEILING AIR CONDITIONING PLENUM RUNNING
WITHOUT CONDUIT SHALL RE TEFLON COATED CLASSIFIED FOR USE IN PLENUMS.
17. PROVIDE TRAPEZE HANGER AS ASSEMBLE FOR PLENUM COMMUNICATION CABLE WITH
3/8' DIAMETER. THREADED ROD AND CHANNEL ASSEMBLY TO SUPPORT CABLE BUNDLES
EVERY 4 FTO.C. (MAXIMUM CABLES SHALL NOT LIE ON TOP OF CEILING TILE OR
LUMINARIES).
11. LIGHT SWITCHES OPERATING CIRCUIT OTHER THAN 120 V SHALL NOT RE GANGED IN SAME
BOX UNLESS SWITCHES ARE CONNECTED TO SAME CIRCUIT.
19. ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS
PER N.E.C. 250.122.
20. ALL EMPTY CONDUITS TO ME PROVIDED WITH NYLON PULL STRINGS.
21. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
22. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING, CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE
MENTIONED CHANGES AT NO EXTRA COST.
23. CONTACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONG DRAWING REFER TO MANUFACTURER ALL
REQUIREMENT AND INCLUDE ALL RELATED WORK IN HAS CONTACT.
24. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS.
25. RISERS ARE DIAGRAMMATIC ONLY, THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE
INSTALLATION.
26. THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLTION, THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
27. ALL CABLES SHALL ME RUN WITHOUT SPLICES EXCEPT IF OTHERWISE INDICATED.
28. ALL PULL AND JUNCTION BOXES SHAL IE ACCESSIBLE AT ALL TIMES.
29. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
30. ALL WORK SHALL NE DONE IN A NEAT AND WORKMANLIKE MANNER.
31. BRANCH CIRCUIT BREAKERS SHALL BE OF THE BOU N TYPE. PLUG IN CIRCUIT
BREAKERS WILL NOT BE ACCEPTED.
32. SUMMIT DETAILED LAYOUT OF ALL ELECTRICAL ROOMS WITH EQUIPMENT REQUIRING
ELECTRICAL SERVICE, LAYOUT SHALL SHOW PROPOSED LOCATION OF ELECTRICAL
SERVICE ITEMS SUCH AS DISCONNECTS, RELAY, PANELBOARDS, ETC. AND DIMENSIONS
SHOWING CODE CLEARANCES TO ADJACENT SURFACES,
33. ALL ROUGH IN DIMENSIONS ARE TO CENTER LINE OF DEVICE UNLESS OTHERWISE NOTED.
34, ALL PULL BOXES, HAND HOLES AND MAN HOLES TO HAVE COVER PLATE BOLTED TO
FRAME AND BONDED TO THE EQUIPMENT GROUND SYSTEM.
35. CONTRACTOR SHALL INCLUDE IN HIS BID ALL COST RELATED TO THE WIND LOAD
COMPLIANCE, THE CERTIFICATION OF THE EXTERIOR POLE/LUMINARY ASSEMBLIES BY A
STRUCTURAL ENGINEER.
36. ALL CONDUCTOR SPLICES IN EXTERIOR LOCATED JUNCTION / PULL BOXES EXPOSED TO
THE WEATHER TO ME WEATHER SEALED BY USING AN APPROVED METHOD SUCH AS 3M,
SCOTHLOCK CONNECTOR EPDXY SEALING, PACK OR SIMILAR.
37. CONTRACTOR SHALL PROVIDE TEMPORARY PANEL, LIGHTS & OUTLETS THROUGHOUT
THE BUILDING DURING COMPLETE CONSTRUCTION (ALL POWER MUST BE MADE TO SATISFY
CONSULTANT NEEDS FOR ALL EQUIPMENT.)
CI1'Y OF SOUT, !-1 I''S7V+i`.'Ii
BUILDING DEPT.
ELE:CTril(".AL. ST-CT10i,J
APPROVE 3Y: _,_. __. __
DATE:
,
#26000522
ARCHITECTURE INTERIOR DESIGN PLANNING
SEAL
RONEY J. MATEU
AR 0008220
JMM CONSULTING ENGINEERS, LLC
M.E.P.
12651 S DIXIE HIGHWAY, SUITE 209
MIAMI, FLORIDA 33156
M.A. SUAREZ CONSULTING ENGINEERS
STRUCTURAL ENGINEERING
4869 SW 75TH AVENUE
MIAMI, FLORIDA 33155
PISTORIND & ALAM CONSULTING ENG, INC,
CIVIL ENGINEERING
7171 SW 62ND AVENUE, 4TH FLOOR
MIAMI, FLORIDA 33143
OXFORD UNIVERSAL
4311 PONCE DE LEON BLVD.
CORAL GABLES, FLORIDA 33146
5966 SOUTH
DIXIE BUILDING
5966 & 5970
SOUTH DIXIE HIGHWAY
MIAMI, FLORIDA 33133
M A TE U ARCH ITECTURE INC.
THIS DRAWING 15 THE PROPERTY OF MATEU
ARCHITECTURE INC. UNLESS OTHERWISE PROVIDED
FOR BY CONTRACT THE CONTENTS OF THIS
DRAWING ARE CONFIDENTIAL AND SHALL NOT
IE TRANSMITTED TO ANY PARTY EXCEPT AS
AUTHORIZED BY THE ARCHITECT/ENGINEERS OF
RECORD
PHASE
-AT. LT1j"Ififfla i
FILE NAME:
E -204 -DWG
PROJECT NO
MA0605
DRAWN NY:
JMM
CHECKED BY:
JMM
ISSUE DATE.
DECEMBER 10, 2007
diH691U�169
SHEET TITLE
NOTES & DETAILS
SHEET- OF.
E-204 19
• M f r V• i
i • •
• u • r r
•
G • i y V E
•G •Y V
• • Y •
V Y Y
iVu uuV u
GENERAL ELECTRICAL NOTES �`
• V
y • 4,"V
��� W..
V • ' U
` '
`GY • .�
• V y V
1.
ALL WORK SHALL ME IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE, " " .
" •
. • G r
FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS.
2. a)
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS ANQ
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE 11`
b)
N.E.C.
WHEN CONFLICTS ARISE IN LOCATIONS WIRING DEVICES, ELECTRICAL EQUIPMENT,'
DISCONNECTS, PANELBOARDS, ETC. DUE TO FIELD CONDITION OR IMPROPER FIELDo •+•
i v • 4 G
COORDINATION CONTRACTOR SHALL BRING IT TO THE A/E'S ATTENTION AND AT NO
EXTRA COST RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM
WHICH IS IN CONFLICT, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING
LOCATION OF ALL COMPONENTS PRIOR TO ROUGH IN WITH ALL TRADES NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO DO SO.
3.
THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING THE
SITE PRIOR TO COMMENCING / BIDDING WORK.
4.
THE CONTRACTOR SHALL SATISFACTORILY REPAIR! REPLACE EQUIPMENT OR PART OF
STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS
SHALL BE RESTORED TO MATCH ADJACENT AREAS.
5.
APPROVAL SHALL BE OBTAINED FROM A STRUCTURAL ENGINEER PRIOR TO CUTTING OR
DRILLING ANY STRUCTUALSUPPORT MEMBER.
G.
ALL DEVICE BOXES SHALL ME INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN
FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/NOTED OTHERWISE.
7.
INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR AIR
CONDITIONING SYSTEM AS SHOWN/NOTED ON THESE DRAWINGS AND PER OTHER
APPLICILE DRAWINGS / INSTRUCTTIONS. SEE AIR CONDITIONING DRAWING.
8.
ALL MATERIAL REMOVED SHALL BE SISPQSED OF AS DIRECTED BY OWNER.
9.
MINIMUN WIRE SIZE SHALL BE # 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS.
10. ALL SHALL BE THWN.
11. ALL CONDUCTORS SHALL BE COPPER RUN IN METALLIC CONDUIT.
12. ALL CONDUCTORS SHALL BE RUN IN CONDUIT METALLIC TYPE). IF PVC SCHEDULE 40 IS
USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN
ACCORDANCE WITH N.E.C. 250-122 MUST 8E INSTALLED AND CONDUIT SIZE INCREASED AS
REQUIRED.
13, ALL MATERIALS SHALL BE U.L. APPROVED.
14. NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED.
15. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
111. ALL NON POWER RELATED WIRING I N CEILING AIR CONDITIONING PLENUM RUNNING
WITHOUT CONDUIT SHALL RE TEFLON COATED CLASSIFIED FOR USE IN PLENUMS.
17. PROVIDE TRAPEZE HANGER AS ASSEMBLE FOR PLENUM COMMUNICATION CABLE WITH
3/8' DIAMETER. THREADED ROD AND CHANNEL ASSEMBLY TO SUPPORT CABLE BUNDLES
EVERY 4 FTO.C. (MAXIMUM CABLES SHALL NOT LIE ON TOP OF CEILING TILE OR
LUMINARIES).
11. LIGHT SWITCHES OPERATING CIRCUIT OTHER THAN 120 V SHALL NOT RE GANGED IN SAME
BOX UNLESS SWITCHES ARE CONNECTED TO SAME CIRCUIT.
19. ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS
PER N.E.C. 250.122.
20. ALL EMPTY CONDUITS TO ME PROVIDED WITH NYLON PULL STRINGS.
21. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
22. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING, CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE
MENTIONED CHANGES AT NO EXTRA COST.
23. CONTACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONG DRAWING REFER TO MANUFACTURER ALL
REQUIREMENT AND INCLUDE ALL RELATED WORK IN HAS CONTACT.
24. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS.
25. RISERS ARE DIAGRAMMATIC ONLY, THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE
INSTALLATION.
26. THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLTION, THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
27. ALL CABLES SHALL ME RUN WITHOUT SPLICES EXCEPT IF OTHERWISE INDICATED.
28. ALL PULL AND JUNCTION BOXES SHAL IE ACCESSIBLE AT ALL TIMES.
29. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
30. ALL WORK SHALL NE DONE IN A NEAT AND WORKMANLIKE MANNER.
31. BRANCH CIRCUIT BREAKERS SHALL BE OF THE BOU N TYPE. PLUG IN CIRCUIT
BREAKERS WILL NOT BE ACCEPTED.
32. SUMMIT DETAILED LAYOUT OF ALL ELECTRICAL ROOMS WITH EQUIPMENT REQUIRING
ELECTRICAL SERVICE, LAYOUT SHALL SHOW PROPOSED LOCATION OF ELECTRICAL
SERVICE ITEMS SUCH AS DISCONNECTS, RELAY, PANELBOARDS, ETC. AND DIMENSIONS
SHOWING CODE CLEARANCES TO ADJACENT SURFACES,
33. ALL ROUGH IN DIMENSIONS ARE TO CENTER LINE OF DEVICE UNLESS OTHERWISE NOTED.
34, ALL PULL BOXES, HAND HOLES AND MAN HOLES TO HAVE COVER PLATE BOLTED TO
FRAME AND BONDED TO THE EQUIPMENT GROUND SYSTEM.
35. CONTRACTOR SHALL INCLUDE IN HIS BID ALL COST RELATED TO THE WIND LOAD
COMPLIANCE, THE CERTIFICATION OF THE EXTERIOR POLE/LUMINARY ASSEMBLIES BY A
STRUCTURAL ENGINEER.
36. ALL CONDUCTOR SPLICES IN EXTERIOR LOCATED JUNCTION / PULL BOXES EXPOSED TO
THE WEATHER TO ME WEATHER SEALED BY USING AN APPROVED METHOD SUCH AS 3M,
SCOTHLOCK CONNECTOR EPDXY SEALING, PACK OR SIMILAR.
37. CONTRACTOR SHALL PROVIDE TEMPORARY PANEL, LIGHTS & OUTLETS THROUGHOUT
THE BUILDING DURING COMPLETE CONSTRUCTION (ALL POWER MUST BE MADE TO SATISFY
CONSULTANT NEEDS FOR ALL EQUIPMENT.)
CI1'Y OF SOUT, !-1 I''S7V+i`.'Ii
BUILDING DEPT.
ELE:CTril(".AL. ST-CT10i,J
APPROVE 3Y: _,_. __. __
DATE:
,
#26000522
ARCHITECTURE INTERIOR DESIGN PLANNING
SEAL
RONEY J. MATEU
AR 0008220
JMM CONSULTING ENGINEERS, LLC
M.E.P.
12651 S DIXIE HIGHWAY, SUITE 209
MIAMI, FLORIDA 33156
M.A. SUAREZ CONSULTING ENGINEERS
STRUCTURAL ENGINEERING
4869 SW 75TH AVENUE
MIAMI, FLORIDA 33155
PISTORIND & ALAM CONSULTING ENG, INC,
CIVIL ENGINEERING
7171 SW 62ND AVENUE, 4TH FLOOR
MIAMI, FLORIDA 33143
OXFORD UNIVERSAL
4311 PONCE DE LEON BLVD.
CORAL GABLES, FLORIDA 33146
5966 SOUTH
DIXIE BUILDING
5966 & 5970
SOUTH DIXIE HIGHWAY
MIAMI, FLORIDA 33133
M A TE U ARCH ITECTURE INC.
THIS DRAWING 15 THE PROPERTY OF MATEU
ARCHITECTURE INC. UNLESS OTHERWISE PROVIDED
FOR BY CONTRACT THE CONTENTS OF THIS
DRAWING ARE CONFIDENTIAL AND SHALL NOT
IE TRANSMITTED TO ANY PARTY EXCEPT AS
AUTHORIZED BY THE ARCHITECT/ENGINEERS OF
RECORD
PHASE
-AT. LT1j"Ififfla i
FILE NAME:
E -204 -DWG
PROJECT NO
MA0605
DRAWN NY:
JMM
CHECKED BY:
JMM
ISSUE DATE.
DECEMBER 10, 2007
diH691U�169
SHEET TITLE
NOTES & DETAILS
SHEET- OF.
E-204 19