Loading...
08-40-116ELEVATOR NOTES 1. PROPERLY FRAMED AND ENCLOSED LEGAL HOISTWAY INCLUDING VENTING AS REQUIRED BY THE GOVERNING CODE AND SAFETY BEAM AS SHOWN. 2. ADEQUATE SUPPORT FOR GUIDE RAIL FASTENINGS NOT TO EXCEED THE VERTICAL SPACING SHOWN ON THE RAIL BRACKET CHART. SEPARATOR BEAMS WHERE REQUIRED. 3. PROVISIONS FOR GUARDING AND PROTECTING THE HOISTWAY DURING CONSTRUCTION TO BE ERECTED, MAINTAINED, AND REMOVED BY OTHERS. 4. ALL CUTTING OR PATCHING TO ACCOMMODATE ELEVATOR INSTALLATION. 5. HOISTWAY WALLS ARE TO BE DESIGNED AND CONSTRUCTEb IN ACCORDANCE WITH THE REQUIRED FIRE RATING INCLUDING WHERE PENETRATED BY ELEVATOR FIXTURE BOXES, AND TO INCLUDE ADEQUATE FASTENINGS TO HOISTWAY ASSEMBLIES. A HORIZONTAL SUPPORT MUST BE PROVIDED 12" (305mm) ABOVE THE CLEAR OPENING AT EACH LANDING TO SUPPORT THE DOOR FRAME ASSEMBLY. THE ENTRANCE WALL AND THE FINISHED FLOOR MUST NOT BE CONSTRUCTED UNTIL THE FRAMES AND SILLS ARE SET. 6. FOR PRECAST OR POURED CONCRETE WALLS, PROVIDE THE ROUGH OPENNING FOR HOISTWAY AS SHOWN ON LAYOUT, AND ANY GROUTING AROUND ENTRANCE FRAMES IF REO -D. 7. SUITABLE MACHINE ROOM WITH LEGAL ACCESS AND MINIMUM HEIGHT OF 7'6" (2216 mm) TO BE PROVIDED. MACHINE ROOM TEMPERATURE MAINTAINED BETWEEN 60' k 100' F (15.5' & 37.1' C). RELATIVE HUMIDITY NOT TO EXCEED 95% NON-CONDESING. FOR HEATING, VENTILATION, AND AIR CONDITIONING REQUIREMENTS OTHER THAN THOSE SHOWN ABOVE REFER TO OTIS CONFIRMATION OF POWER SUPPLY FORM. ) B. A SEPARATE BRANCH CIRCUIT FOR SUITABLE LIGHT FIXTURE(S AND CONVENIENCE OUTLETS, WITH G.F.I., IN THE MACHINE ROOM WITH THE LIGHT SWITCH LOCATED ADJACENT TO THE LOCK JAMB SIDE OF THE MACHINE ROOM DOOR. 9. FOR EACH ELEVATOR, A THREE PHASE ELECTRICAL FEEDER SYSTEM WITH A SEPARATE EQUIPMENT GROUNDING CONDUCTOR AND A SINGLE PHASE 120 VOLT LIGHTING SUPPLY. EACH WITH A FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER, LOCATED IN THE MACHINE ROOM AND WIRED TO EACH CONTROLLER. 10. IN THE PIT, A SEPARATE BRANCH CIRCUIT FOR CONVENIENCE G.F.C.I. OUTLET & LIGHT FIXTURE WITH LIGHT SWITCH ADJACENT TO THE PIT LADDER. 11. ALL ELECTRIC POWER FOR TOOLS, LIGHT, HOIST, ETC., DURING ERECTION AS WELL AS ELECTRIC CURRENT FOR STARTING AND ADJUSTING THE ELEVATOR. 12. DRY PIT REINFORCED TO SUSTAIN VERTICAL FORCES OF UP TO: 15,041 87 LBS/KN AT EACH BUFFER AND 30,9781138 LBS/KN AT THE CYLINDER HEAD. THE ACCUMULATION OF WATER MUST BE PREVENTED. 13. A FIXED VERTICAL STEEL LADDER TO PIT EXTENDING 4'-0" (1219mm) ABOVE THE SILL OF THE BOTTOM ENTRANCE AS LOCATED IN THE PLAN VIEW. LADDER WIDTH AND PROJECTION FROM WALL PER LOCAL CODE. 14. IF PIT FLOOR IS TO BE POURED BEFORE WELL HOLE OR CASING IS INSTALLED, A 30' x 30" (760mm x 760mm) CUTOUT IN PIT FLOOR SHALL BE PROVIDED. CUTOUT AND PATCHING OF FLOOR NOT BY OTIS. WHEN THE WELL HOLE IS NOT THE RESPONSIBILITY OF OTIS, THE DRILLING CONTRACTOR SHALL DRILL A WELL HOLE AND INSTALL CASING WITH PLUG AND END CAP, CLEAR HOLE TO BE OF ADEQUATE DEPTH AND DIAMETER FOR 011S TO INSTALL A DIAMETER ASSEMBLY PERFECTLY PLUMB AT THE LOCATION INDICATED ON THIS DRAWING. 15. ELEVATOR CAB FLOORING MUST NOT EXCEED A THICKNESS OF 5/16" (8mm). 16. ONE (1) DEDICATED OUTSIDE TELEPHONE LINE TO THE ELEVATOR MACHINE ROOM MUST ME FURNISHED. TELEPHONE CONNECTIONS TO EACH CONTROLLER. TELEPHONE INSTRUMENT BY OTHERS. 17. ALL 125 VOLT, 15 OR 20 AMP, SINGLE PHASE DUPLEX RECEPTACLES INSTALLED IN PITS, MACHINE ROOMS OR MACHINERY SPACES, SHALL BE OF THE GROUND -FAULT - CIRCUIT -INTERRUPTER TYPE. 18. SMOKE DETECTORS, LOCATED AS REQUIRED, WITH WIRING FROM THE SENSING DEVICES TO A CONTROLLER DESIGNATED BY OTIS. FOR EACH GROUP OF ELEVATORS, PROVIDE A NORMALLY CLOSED CONTACT REPRESENTING THE SMOKE DETECTOR AT THE DESIGNATED RETURN LANDING, FOR EACH GROUP OF ELEVATORS, PROVIDE A NORMALLY CLOSED CONTACT REPRESENTING ALL SMOKE DETECTORS LOCATED IN LOBBIES, HOISTWAYS, OR MACHINE ROOMS, BUT NOT THE SMOKE DETECTOR AT THE DESIGNATED RETURN LANDING (SEE ABOVE) OR THE SMOKE DETECTORS AS DESCRIBED IN A & B BELOW: A) IF A SMOKE DETECTOR IS LOCATED IN THE HOISTWAY AT OR BELOW THE LOWER OF THE TWO RECALL LANDINGS, IT SHALL BE WIRED TO ACTIVATE THE SAME NORMALLY CLOSED CONTACT AS THE SMOKE DETECTOR LOCATED IN THE LOBBY AT THE LOWER OF THE TWO RECALL LANDINGS. B) IF MACHINE ROOMS ARE LOCATED AT THE DESIGNATED RETURN LANDING, THE SMOKE DETECTOR LOCATED THEREIN SHALL BE WIRED TO ACTIVATE THE SAME NORMALLY CLOSED CONTACT AS THE SMOKE DETECTOR AT THE DESIGNATED LANDING. FOR A SINGLE UNIT, OR GROUP OF ELEVATORS HAVING ONE COMMON MACHINE ROOM AND ONE COMMON HOISTWAY, PROVIDE ONE ADDITIONAL NORMALLY CLOSED CONTACT REPRESENTING ALL MACHINE ROOM AND HOISTWAY SMOKE DETECTORS. IF THE GROUP CONTAINS MORE THAN ONE HOISTWAY, AND HOISTWAY SMOKE DETECTORS ARE INSTALLED, OR IF THE GROUP HAS MORE THAN ONE MACHINE ROOM, PROVIDE ONE ADDITIONAL NORMALLY CLOSED CONTACT FOR EACH ELEVATOR. THE CONTACT IS TO REPRESENT THE SMOKE DETECTOR IN THE MACHINE ROOM FOR THAT PARTICULAR ELEVATOR, AND ANY SMOKE DETECTORS IN THE HOISTWAY CONTAINING THAT PARTICULAR ELEVATOR. C) PROVIDE CLASS "ABC" FIRE EXTINGUISHER IN MACHINE ROOMS. 19. IF SPRINKLERS ARE INSTALLED IN THE HOISTWAY, MACHINE ROOM, OR MACHINERY SPACES, THE LOCAL CODE MAY REQUIRE A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN POWER SUPPLY OF THE AFFECTED ELEVATOR PRIOR TO THE APPLICATION OF WATER (CONFIRM WITH THE LOCAL CODE OFFICIAL). SMOKE DETECTORS SHALL NOT BE USED TO ACTIVATE SPRINKLERS IN HOISTWAYS, MACHINE ROOMS OR MACHINERY SPACES OR TO DISCONNECT THE MAIN LINE POWER SUPPLY. 20. TWO (2 6" X 6" 152mm x 152mm) CUTOUTS ARE REQUIRED (NOT BY OTIS). THE ACTUAL LOCATION OF THE CUTOUTS FOR THE TO AND FROM OIL PIPE AND ELECTRICAL TROUGH WILL VARY DEPENDENT UPON MACHINE ROOM LOCATION AND CONFIGURATION. TWO 6"X6" CUTOUTS — z ELEV MACH R02 0 _ _I Co cV 0 1 _ n 0 N 0 I I r CONCRETE CANOPY, SEE ROOF PLAN AND STRUCTURAL DRAWINGS METAL DOOR ON RAISED CURB, SEE SCHEDULE _ EL. +56'-0" T.O. ROOF SLAB HOIST BEAM, SEE ELEVATOR MANUFACTURER'S SPECIFICATIONS w cn x J H 0 0 N 0 il b ul) no a '-0" T.O. 3rd FL. SLAB EL. +20'-0" T.O. 2nd FL. SLAB EL. +10'-0" _ T.O. INTER. SLAB EL. 0'-0" T.O. GROUND FL. SLAB FOUNDATION, SEE STRUCTURAL DRAWINGS LADDER SUMP PUMP ELEVATOR SHAFT SECTION • •r•r• iir i • • +• i ♦ ^ *26000522 ••• i V f e u O U f ♦ Y • i [) U J Y f « V • � �) t C i " Yl W W I F- .n N m G, r m U Q q m m o N 6 a r r 0 Lu ARCHITECTURE INTERIOR DESIGN PLANNING $EAI ' I �Y—woo ,�T MONEY J. MATED AR 0008220 JMM CONSULTING ENGINEERS, LLC M.E.P. 12651 S DIXIE HIGHWAY, SUITE 209 MIAMI, FLORIDA 33156 M.A. SUAREZ CONSULTING ENGINEERS STRUCTURAL ENGINEERING 4869 SW 75TH AVENUE MIAMI, FLORIDA 33155 PISTORINO it ALAM CONSULTING ENG. INC. CIVIL ENGINEERING 7171 SW 62ND AVENUE, 4TH FLOOR MIAMI, FLORIDA 33143 OXFORD UNIVERSAL 4311 PONCE DE LEON BLVD. CORAL GAILES, FLORIDA 33146 6966 SOUTH DIXIE BUILDING 5966 & 5970 SOUTH DIXIE HIGHWAY MIAMI, FLORIDA 33133 MATED ARCHITECTURE INC. THIS DRAWING IS THE PROPERTY OF MATED ARCHITECTURE ING UNLESS OTHERWISE PROVIDED FOR NY CONTRACT THE CONTENTS OF THIS DRAWING ARE CONFIDENTIAL AND SHALL NOT DE TRANSMITTED TO ANY PARTY EXCEPT AS AUTHORIZED BY THE ARCHITECT/ENGINEERS OF RECORD, PHASE PERMIT DRAWINGS FILE NAME: M:\0605\CD\SHEET\ARCHA-422.DWG FMOJECT NO MA0605 DRAWN BY RAG CHECKED NY: RJM ISSUE DATE: DECEMBER 10, 2007 REVISIONS SHEET TITLE ELEVATOR SHAFT SECTION SHEET A-422 OF. min f� �lSSlEliil�� _ _I Co cV 0 1 _ n 0 N 0 I I r CONCRETE CANOPY, SEE ROOF PLAN AND STRUCTURAL DRAWINGS METAL DOOR ON RAISED CURB, SEE SCHEDULE _ EL. +56'-0" T.O. ROOF SLAB HOIST BEAM, SEE ELEVATOR MANUFACTURER'S SPECIFICATIONS w cn x J H 0 0 N 0 il b ul) no a '-0" T.O. 3rd FL. SLAB EL. +20'-0" T.O. 2nd FL. SLAB EL. +10'-0" _ T.O. INTER. SLAB EL. 0'-0" T.O. GROUND FL. SLAB FOUNDATION, SEE STRUCTURAL DRAWINGS LADDER SUMP PUMP ELEVATOR SHAFT SECTION • •r•r• iir i • • +• i ♦ ^ *26000522 ••• i V f e u O U f ♦ Y • i [) U J Y f « V • � �) t C i " Yl W W I F- .n N m G, r m U Q q m m o N 6 a r r 0 Lu ARCHITECTURE INTERIOR DESIGN PLANNING $EAI ' I �Y—woo ,�T MONEY J. MATED AR 0008220 JMM CONSULTING ENGINEERS, LLC M.E.P. 12651 S DIXIE HIGHWAY, SUITE 209 MIAMI, FLORIDA 33156 M.A. SUAREZ CONSULTING ENGINEERS STRUCTURAL ENGINEERING 4869 SW 75TH AVENUE MIAMI, FLORIDA 33155 PISTORINO it ALAM CONSULTING ENG. INC. CIVIL ENGINEERING 7171 SW 62ND AVENUE, 4TH FLOOR MIAMI, FLORIDA 33143 OXFORD UNIVERSAL 4311 PONCE DE LEON BLVD. CORAL GAILES, FLORIDA 33146 6966 SOUTH DIXIE BUILDING 5966 & 5970 SOUTH DIXIE HIGHWAY MIAMI, FLORIDA 33133 MATED ARCHITECTURE INC. THIS DRAWING IS THE PROPERTY OF MATED ARCHITECTURE ING UNLESS OTHERWISE PROVIDED FOR NY CONTRACT THE CONTENTS OF THIS DRAWING ARE CONFIDENTIAL AND SHALL NOT DE TRANSMITTED TO ANY PARTY EXCEPT AS AUTHORIZED BY THE ARCHITECT/ENGINEERS OF RECORD, PHASE PERMIT DRAWINGS FILE NAME: M:\0605\CD\SHEET\ARCHA-422.DWG FMOJECT NO MA0605 DRAWN BY RAG CHECKED NY: RJM ISSUE DATE: DECEMBER 10, 2007 REVISIONS SHEET TITLE ELEVATOR SHAFT SECTION SHEET A-422 OF.