08-40-116ELEVATOR NOTES
1. PROPERLY FRAMED AND ENCLOSED LEGAL HOISTWAY INCLUDING VENTING AS
REQUIRED BY THE GOVERNING CODE AND SAFETY BEAM AS SHOWN.
2. ADEQUATE SUPPORT FOR GUIDE RAIL FASTENINGS NOT TO EXCEED THE VERTICAL
SPACING SHOWN ON THE RAIL BRACKET CHART. SEPARATOR BEAMS WHERE REQUIRED.
3. PROVISIONS FOR GUARDING AND PROTECTING THE HOISTWAY DURING CONSTRUCTION
TO BE ERECTED, MAINTAINED, AND REMOVED BY OTHERS.
4. ALL CUTTING OR PATCHING TO ACCOMMODATE ELEVATOR INSTALLATION.
5. HOISTWAY WALLS ARE TO BE DESIGNED AND CONSTRUCTEb IN ACCORDANCE WITH
THE REQUIRED FIRE RATING INCLUDING WHERE PENETRATED BY ELEVATOR
FIXTURE BOXES, AND TO INCLUDE ADEQUATE FASTENINGS TO HOISTWAY
ASSEMBLIES. A HORIZONTAL SUPPORT MUST BE PROVIDED 12"
(305mm) ABOVE THE CLEAR OPENING AT EACH LANDING TO SUPPORT THE
DOOR FRAME ASSEMBLY. THE ENTRANCE WALL AND THE FINISHED FLOOR MUST NOT
BE CONSTRUCTED UNTIL THE FRAMES AND SILLS ARE SET.
6. FOR PRECAST OR POURED CONCRETE WALLS, PROVIDE THE ROUGH OPENNING FOR
HOISTWAY AS SHOWN ON LAYOUT, AND ANY GROUTING AROUND ENTRANCE FRAMES IF REO -D.
7. SUITABLE MACHINE ROOM WITH LEGAL ACCESS AND MINIMUM HEIGHT OF 7'6"
(2216 mm) TO BE PROVIDED. MACHINE ROOM TEMPERATURE MAINTAINED BETWEEN 60'
k 100' F (15.5' & 37.1' C). RELATIVE HUMIDITY NOT TO EXCEED 95% NON-CONDESING.
FOR HEATING, VENTILATION, AND AIR CONDITIONING REQUIREMENTS OTHER THAN THOSE SHOWN
ABOVE REFER TO OTIS CONFIRMATION OF POWER SUPPLY FORM. )
B. A SEPARATE BRANCH CIRCUIT FOR SUITABLE LIGHT FIXTURE(S AND CONVENIENCE
OUTLETS, WITH G.F.I., IN THE MACHINE ROOM WITH THE LIGHT SWITCH LOCATED
ADJACENT TO THE LOCK JAMB SIDE OF THE MACHINE ROOM DOOR.
9. FOR EACH ELEVATOR, A THREE PHASE ELECTRICAL FEEDER SYSTEM WITH A SEPARATE
EQUIPMENT GROUNDING CONDUCTOR AND A SINGLE PHASE 120 VOLT LIGHTING
SUPPLY. EACH WITH A FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER, LOCATED
IN THE MACHINE ROOM AND WIRED TO EACH CONTROLLER.
10. IN THE PIT, A SEPARATE BRANCH CIRCUIT FOR CONVENIENCE G.F.C.I. OUTLET &
LIGHT FIXTURE WITH LIGHT SWITCH ADJACENT TO THE PIT LADDER.
11. ALL ELECTRIC POWER FOR TOOLS, LIGHT, HOIST, ETC., DURING ERECTION AS
WELL AS ELECTRIC CURRENT FOR STARTING AND ADJUSTING THE ELEVATOR.
12. DRY PIT REINFORCED TO SUSTAIN VERTICAL FORCES OF UP TO:
15,041 87 LBS/KN AT EACH BUFFER AND
30,9781138 LBS/KN AT THE CYLINDER HEAD.
THE ACCUMULATION OF WATER MUST BE PREVENTED.
13. A FIXED VERTICAL STEEL LADDER TO PIT EXTENDING 4'-0" (1219mm) ABOVE
THE SILL OF THE BOTTOM ENTRANCE AS LOCATED IN THE PLAN VIEW.
LADDER WIDTH AND PROJECTION FROM WALL PER LOCAL CODE.
14. IF PIT FLOOR IS TO BE POURED BEFORE WELL HOLE OR CASING IS INSTALLED,
A 30' x 30" (760mm x 760mm) CUTOUT IN PIT FLOOR SHALL BE PROVIDED.
CUTOUT AND PATCHING OF FLOOR NOT BY OTIS. WHEN THE WELL HOLE IS NOT THE
RESPONSIBILITY OF OTIS, THE DRILLING CONTRACTOR SHALL DRILL A WELL HOLE AND INSTALL
CASING WITH PLUG AND END CAP, CLEAR HOLE TO BE OF ADEQUATE DEPTH AND DIAMETER
FOR 011S TO INSTALL A DIAMETER ASSEMBLY PERFECTLY PLUMB AT THE
LOCATION INDICATED ON THIS DRAWING.
15. ELEVATOR CAB FLOORING MUST NOT EXCEED A THICKNESS OF 5/16" (8mm).
16. ONE (1) DEDICATED OUTSIDE TELEPHONE LINE TO THE ELEVATOR MACHINE ROOM
MUST ME FURNISHED. TELEPHONE CONNECTIONS TO EACH CONTROLLER.
TELEPHONE INSTRUMENT BY OTHERS.
17. ALL 125 VOLT, 15 OR 20 AMP, SINGLE PHASE DUPLEX RECEPTACLES INSTALLED IN
PITS, MACHINE ROOMS OR MACHINERY SPACES, SHALL BE OF THE GROUND -FAULT -
CIRCUIT -INTERRUPTER TYPE.
18. SMOKE DETECTORS, LOCATED AS REQUIRED, WITH WIRING FROM THE SENSING
DEVICES TO A CONTROLLER DESIGNATED BY OTIS. FOR EACH GROUP OF ELEVATORS,
PROVIDE A NORMALLY CLOSED CONTACT REPRESENTING THE SMOKE DETECTOR AT THE
DESIGNATED RETURN LANDING, FOR EACH GROUP OF ELEVATORS, PROVIDE A NORMALLY
CLOSED CONTACT REPRESENTING ALL SMOKE DETECTORS LOCATED IN LOBBIES,
HOISTWAYS, OR MACHINE ROOMS, BUT NOT THE SMOKE DETECTOR AT THE
DESIGNATED RETURN LANDING (SEE ABOVE) OR THE SMOKE DETECTORS AS
DESCRIBED IN A & B BELOW:
A) IF A SMOKE DETECTOR IS LOCATED IN THE HOISTWAY AT OR BELOW THE LOWER OF
THE TWO RECALL LANDINGS, IT SHALL BE WIRED TO ACTIVATE THE SAME NORMALLY
CLOSED CONTACT AS THE SMOKE DETECTOR LOCATED IN THE LOBBY AT THE LOWER
OF THE TWO RECALL LANDINGS.
B) IF MACHINE ROOMS ARE LOCATED AT THE DESIGNATED RETURN LANDING, THE SMOKE
DETECTOR LOCATED THEREIN SHALL BE WIRED TO ACTIVATE THE SAME NORMALLY
CLOSED CONTACT AS THE SMOKE DETECTOR AT THE DESIGNATED LANDING. FOR A
SINGLE UNIT, OR GROUP OF ELEVATORS HAVING ONE COMMON MACHINE ROOM AND
ONE COMMON HOISTWAY, PROVIDE ONE ADDITIONAL NORMALLY CLOSED CONTACT
REPRESENTING ALL MACHINE ROOM AND HOISTWAY SMOKE DETECTORS. IF THE GROUP
CONTAINS MORE THAN ONE HOISTWAY, AND HOISTWAY SMOKE DETECTORS ARE INSTALLED,
OR IF THE GROUP HAS MORE THAN ONE MACHINE ROOM, PROVIDE ONE ADDITIONAL
NORMALLY CLOSED CONTACT FOR EACH ELEVATOR. THE CONTACT IS TO REPRESENT THE
SMOKE DETECTOR IN THE MACHINE ROOM FOR THAT PARTICULAR ELEVATOR, AND ANY
SMOKE DETECTORS IN THE HOISTWAY CONTAINING THAT PARTICULAR ELEVATOR.
C) PROVIDE CLASS "ABC" FIRE EXTINGUISHER IN MACHINE ROOMS.
19. IF SPRINKLERS ARE INSTALLED IN THE HOISTWAY, MACHINE ROOM, OR MACHINERY SPACES,
THE LOCAL CODE MAY REQUIRE A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN POWER
SUPPLY OF THE AFFECTED ELEVATOR PRIOR TO THE APPLICATION OF WATER (CONFIRM
WITH THE LOCAL CODE OFFICIAL). SMOKE DETECTORS SHALL NOT BE USED TO ACTIVATE
SPRINKLERS IN HOISTWAYS, MACHINE ROOMS OR MACHINERY SPACES OR TO DISCONNECT
THE MAIN LINE POWER SUPPLY.
20. TWO (2 6" X 6" 152mm x 152mm) CUTOUTS ARE REQUIRED (NOT BY OTIS).
THE ACTUAL LOCATION OF THE CUTOUTS FOR THE TO AND FROM OIL PIPE AND
ELECTRICAL TROUGH WILL VARY DEPENDENT UPON MACHINE ROOM LOCATION AND
CONFIGURATION.
TWO 6"X6"
CUTOUTS
—
z
ELEV MACH
R02
0
_
_I
Co
cV 0
1
_ n
0
N 0
I I
r
CONCRETE CANOPY, SEE ROOF PLAN
AND STRUCTURAL DRAWINGS
METAL DOOR ON RAISED CURB, SEE
SCHEDULE
_ EL. +56'-0"
T.O. ROOF SLAB
HOIST BEAM, SEE ELEVATOR
MANUFACTURER'S SPECIFICATIONS
w
cn
x
J
H
0 0
N 0
il b ul)
no
a
'-0"
T.O. 3rd FL. SLAB
EL. +20'-0"
T.O. 2nd FL. SLAB
EL. +10'-0" _
T.O. INTER. SLAB
EL. 0'-0"
T.O. GROUND FL. SLAB
FOUNDATION, SEE
STRUCTURAL DRAWINGS
LADDER
SUMP PUMP
ELEVATOR SHAFT SECTION
• •r•r• iir i
• • +• i ♦ ^ *26000522
••• i V f e u O
U
f ♦ Y • i [) U
J
Y f « V • � �)
t
C i
"
Yl W
W I
F- .n
N
m
G,
r m
U Q
q m
m
o N
6
a
r
r
0
Lu
ARCHITECTURE INTERIOR DESIGN PLANNING
$EAI
' I �Y—woo
,�T
MONEY J. MATED
AR 0008220
JMM CONSULTING ENGINEERS, LLC
M.E.P.
12651 S DIXIE HIGHWAY, SUITE 209
MIAMI, FLORIDA 33156
M.A. SUAREZ CONSULTING ENGINEERS
STRUCTURAL ENGINEERING
4869 SW 75TH AVENUE
MIAMI, FLORIDA 33155
PISTORINO it ALAM CONSULTING ENG. INC.
CIVIL ENGINEERING
7171 SW 62ND AVENUE, 4TH FLOOR
MIAMI, FLORIDA 33143
OXFORD UNIVERSAL
4311 PONCE DE LEON BLVD.
CORAL GAILES, FLORIDA 33146
6966 SOUTH
DIXIE BUILDING
5966 & 5970
SOUTH DIXIE HIGHWAY
MIAMI, FLORIDA 33133
MATED ARCHITECTURE INC.
THIS DRAWING IS THE PROPERTY OF MATED
ARCHITECTURE ING UNLESS OTHERWISE PROVIDED
FOR NY CONTRACT THE CONTENTS OF THIS
DRAWING ARE CONFIDENTIAL AND SHALL NOT
DE TRANSMITTED TO ANY PARTY EXCEPT AS
AUTHORIZED BY THE ARCHITECT/ENGINEERS OF
RECORD,
PHASE
PERMIT DRAWINGS
FILE NAME:
M:\0605\CD\SHEET\ARCHA-422.DWG
FMOJECT NO
MA0605
DRAWN BY
RAG
CHECKED NY:
RJM
ISSUE DATE:
DECEMBER 10, 2007
REVISIONS
SHEET TITLE
ELEVATOR SHAFT SECTION
SHEET
A-422
OF.
min
f�
�lSSlEliil��
_
_I
Co
cV 0
1
_ n
0
N 0
I I
r
CONCRETE CANOPY, SEE ROOF PLAN
AND STRUCTURAL DRAWINGS
METAL DOOR ON RAISED CURB, SEE
SCHEDULE
_ EL. +56'-0"
T.O. ROOF SLAB
HOIST BEAM, SEE ELEVATOR
MANUFACTURER'S SPECIFICATIONS
w
cn
x
J
H
0 0
N 0
il b ul)
no
a
'-0"
T.O. 3rd FL. SLAB
EL. +20'-0"
T.O. 2nd FL. SLAB
EL. +10'-0" _
T.O. INTER. SLAB
EL. 0'-0"
T.O. GROUND FL. SLAB
FOUNDATION, SEE
STRUCTURAL DRAWINGS
LADDER
SUMP PUMP
ELEVATOR SHAFT SECTION
• •r•r• iir i
• • +• i ♦ ^ *26000522
••• i V f e u O
U
f ♦ Y • i [) U
J
Y f « V • � �)
t
C i
"
Yl W
W I
F- .n
N
m
G,
r m
U Q
q m
m
o N
6
a
r
r
0
Lu
ARCHITECTURE INTERIOR DESIGN PLANNING
$EAI
' I �Y—woo
,�T
MONEY J. MATED
AR 0008220
JMM CONSULTING ENGINEERS, LLC
M.E.P.
12651 S DIXIE HIGHWAY, SUITE 209
MIAMI, FLORIDA 33156
M.A. SUAREZ CONSULTING ENGINEERS
STRUCTURAL ENGINEERING
4869 SW 75TH AVENUE
MIAMI, FLORIDA 33155
PISTORINO it ALAM CONSULTING ENG. INC.
CIVIL ENGINEERING
7171 SW 62ND AVENUE, 4TH FLOOR
MIAMI, FLORIDA 33143
OXFORD UNIVERSAL
4311 PONCE DE LEON BLVD.
CORAL GAILES, FLORIDA 33146
6966 SOUTH
DIXIE BUILDING
5966 & 5970
SOUTH DIXIE HIGHWAY
MIAMI, FLORIDA 33133
MATED ARCHITECTURE INC.
THIS DRAWING IS THE PROPERTY OF MATED
ARCHITECTURE ING UNLESS OTHERWISE PROVIDED
FOR NY CONTRACT THE CONTENTS OF THIS
DRAWING ARE CONFIDENTIAL AND SHALL NOT
DE TRANSMITTED TO ANY PARTY EXCEPT AS
AUTHORIZED BY THE ARCHITECT/ENGINEERS OF
RECORD,
PHASE
PERMIT DRAWINGS
FILE NAME:
M:\0605\CD\SHEET\ARCHA-422.DWG
FMOJECT NO
MA0605
DRAWN BY
RAG
CHECKED NY:
RJM
ISSUE DATE:
DECEMBER 10, 2007
REVISIONS
SHEET TITLE
ELEVATOR SHAFT SECTION
SHEET
A-422
OF.