11-1105-0182— f10 S.S. SCREWS TO UNIT 2 — e'xti" S.S. TAPCONS o 2"x2'x14 GA IN CONC. 7>, ANGLE 4" LONG (4 TOTAL) CONDENSING UNIT POWER do CONTROL CONNECTIONS 6" MIN. 6' MIN. ° 4" MIN. LIQUID LINE CONCRETE BASE W/ W/O INSULATION 6x6-10/10WWF SEAL ENTRANCE OF REFRIGERANT 6" MIN. 6" 0 SCHEDULE LINES INTO P.V.C. PIPE W/ �40 P.V.C. PIPE IMPERMEABLE, RESILENT MATERIAL INCREASE SIZE AS REQUIRED BY LENGTH AND ROUTING SUCTION LINE W/ 1-1/2" ARMAFLEX INSULATION do VAPOR BARRIER CONDENSING UNIT MOUNTING DETAIL N.T.S. 2 1/2" SQUARE WASHERS 12" OC MAX. #10x1 1/4" SHEET METAL SCREW FIBROUSGLASS DUCT GFM CLOSURE FLANGE '— SCREW, POP REVIT OR SPOT WELD TO EQUIPMENT FLANGE 22 GUAGE SHEET METAL 1 "x3" MECHANICAL ATTACHEMENT DETAIL N.T.S. PREFERRED ALTERNATE ALTERNATE ALTERNATE TAKE —OFF DETAIL TAKE —OFF DETAIL TAKE —OFF DETAIL TAKE —OFF DETAIL BELLMOUTH MINI—BELLMOUTH STANDARD 90' CONNECTION CONNECTION MAIN DUCT RECTANGULAR TO ROUND SIMILAR TO SIMILAR TO BOOT CONNECTION "BUCKLEY" "BUCKLEY" AIR —0LOW "BUCKLEY" MODEL BMD (SEAMLESS) MODEL MBMD (SEAMLESS) MODEL 3300D (CONTINUOUSLY WELDED) _ 6" MIN. VD DUCT SIZE VD HOLE SIZE VD (ONLY WHEN (SEE PLANS) (SEE BELOW—TYP.) OTHERS DO NOT FIT) V.D. OBD (ABOVE 12" IN STANDARD 45' DEPTH) RECTANGULAR NOTE: ALTERNATE FITTINGS SHALL BE USED WHEN DUCT HEIGHT DOES CONNECTION NOT PERMIT THE USE OF THE PREFERRED FULL SIZE BELLMOUTH SUBMIT FITTINGS FOR REVIEW BY ENGINEER PRIOR TO INSTALLATION THIS DETAIL APPLIES TO SINGLE TAKEOFFS TO DIFFUSER AS WELL AS BRANCH TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS IN THE DUCT TAKEOFFS DETAIL HORIZONTAL AS WELL AS VERTICAL DIRECTION. NOTE: SHEET METAL CANNECTIONS MUST BE MADE USING GLASS FABRIC AND MASTIC (GFM) EXCEPTION: WHEN CONSTRUCTION PRESSURE CLASS IS 1" wg (250 Pa) wg OR LESS AND SHEET METAL SURFACE ARE CLEANED CAREFULLY, UL LISTED PRESSURE -SENSITIVE ALUMINUM TAPE MAY BE USED ALL CONNECTION OF FIBROUS GLASS DUCT TO EQUIPMENT AND METAL DUCT MUST BE MECHANICALLY ATTACHED 12" MAX ON CENTER. —SUPPLY AIR DUCT MIN. FLEX —CONNECTION WALL STRUCTURE -" AIR HANDLING UNIT THERMOSTAT REFRIGERANT LINES � CONDENSATE DRAIN WITH TRAP (3- SEAL) NEOPRENE PAD GALVANIZED DRAINPAN AIR HANDLING UNIT WITH FLOAT SWITCH WIRED SUPPORT ( 1"xt"x1 4" TO SHUT DOWN AHU STEEL ANGLE FR E) s" CONDENSATE DRAIN LINE TO OVER FLOOR DRAIN (SEE PLUMBING PLANS FOR LOCATION) TYPICAL VERTICAL AIR UNIT DETAIL NOTE: . 1. PROVIDE MINIMUM 4" SERVICE/ MAINTENANCE AREA AROUND; AIR HANDLING UNIT. 2. PROVIDE FLOAT SWITCH IN DRAINPAN WIRED TO SHUT DOWN AC UNIT IN CASE OF CONDENSATE STOPPAGE. TYPICAL TURNING VANE ON ALL ELBOWS CORNER ANGLE ( I TYPICAL DUCTWORK ELBOW TURNING VANE DETAIL N.T.S. TOILET EXHAUST DUCT (SEE DRAWING FOR SIZE) THERMOFIN) VIBRATION HANGER SPRING TY W/NEOPRENE ISOLATOR 3/8" THREADED RODS LL I.tIUIVU / GRILLE —/ NOTES: 1.- PROVIDE BACKDRAFT DAMPER W/ BIRDSCREEN 2.- FLASH do SEAL WALL AND ROOF CAP 3.- PROVIDE INTERNAL ISOLATION AND SOUND INSULATION 4.- SUPPORT FAN FROM STRUCTURE CABINET EXHAUST FAN DETAIL FLOAT SWITCH TO OVERFLOW SHUT —DOWN EQUIP. AS DRAIN LINE PER FMC. 301.13 ---- _ REMOVABLE CAP 3/4„ A/C UNIT D RAI N PAN DRAIN LINE AUX. OVERFLOW DRAIN LINE DETAIL N.T.S. PERFORATED: VENT CAP ! 12"MIN. UNION SLOPE 1 /8"/ FT. A/C UNIT DRAIN PAN 3/4" MIN. 3"MIN. CONDENSATE DRAIN TRAP DETAIL — — -- N.T.S. EAL JOINT W, rnnvv e_ n� In INSULATE TOP OF ALL AIR TERMINALS DIFFUSER AIR DUCT (SEE PLAN VIEW) SPIN TAP FITTING N.T.S. AIR FLOW METAL ROUND SCOOP FITTING INSULATED FLEX. DUCT SEAL JOINT WITH EPDXY AND DUCT TAPE MOTE: HANG DUCTS ACCORDING TO SMACNA STANDARDS FLEXIBLE DUCT CONNECTION DETAIL N.T.S. SECURE WIRE 10"0 MAX. METHODS OF HANGING m�u ca ct n LLI oar � u � L h 7- 0 M0 r uj 9 0 to 00 M M ui M U" J Z Q W � 0 W ` r- 0 p W e�- r Z (1) O o r= n� Q ti 0 Fine Line Englne®u4ng-Anc. o IW_' w } m Electrical, ;fsc �, fng ; Z Q in 0 Fire Protection,. A i _ ioaa f� < Y 5975 W. SunriseBly erisa, o 13 W Voice 95_- y5(rj 31,g3 ' ` I— = U F raaik/cor4 . Q Q W O C0 U _ 26 &ORCt FRtUGINUR ,`.R.E R� IaTERED EPiG'N RRi92578 WM3.0 YtSTAiE "f ''W P T OIL region1 R:swvx v' 4