11-1105-016J NEW AZC EQUIPMENT SCHEDULE UNIT NUMBER AC-1 I AREA SERVED SEE DWG TOTAL SUPPLY AIR CFM 800 a OUTSIDE AIR CFM - U` EXTERNAL STATIC PRESS. H2O .5 FAN MOTOR HP FLA .5 4.3 ELEC. CHAR. V N 208-1-60 COOL COIL CAP. BTU HR 26.6 TOTAL SENS. HEAT BTU HR 19.9 6 ENT. AIR TEMP. F DB F WB 80.0 67.0 MODEL NUMBER - UNIT MANUFACTURER CARRIER MODEL NUMBER FE5ANB004 WEIGHT LBS. 150 REMARKS: REF. PIPING RS RL 1 1 8--3 8- UNIT NUMBER CU-1 LOCATION SEE PLAN AMBIENT TEMP. F 95 REFRIGERANT R R-410 COMPRESSOR FLA LRA 10.3-52.0 COMP./COND. FAN FLA HP 1 5-1.1 z ELEC. CHAR. V N 208 1 60 Un Z MANUFACTURER CARRIER z MODEL NUMBER 24ANA124AO03 v WEIGHT LBS. 330 REMARKS SEER NOTES 21.0 MCA 18.1 MOCP 35 UNIT MTD. ELEC. HEAT CAP. 5.0 z STEPS OF ELEC. HEAT NO. 1 ELEC. CHAR. V f- 208 1 60 = MODEL NUMBER - NOTE: 1. CONTRACTOR TO PROVIDE AN AUTOMATIC SHUT OFF SWITCH IN CONDENSATE PAN. SWITCH TO SHUT OFF CONDENSING UNIT AND AIR HANDLER AT TIME OF ACTIVATION. VENTILATION FAN SCHEDULE UNIT DESIGNATION EF-1 AREA SERVED BATHROOMS OPERATING WEIGHT LBS. 15 LOCATION CEILING FAN TYPE CENT. TOTAL AIR CFM 75 DRIVE TYPE DIRECT FAN WHEEL TYPE F.C. FAN TIP SPEED RPM MAX - FAN SPEED,RPM 1500 TOTAL STATIC PRESSURE,IN. OF H2O .125 Z FAN MOTOR HP NON OVERLOAD .009 if FAN MOTOR STARTER TYPE - STARTER FURNISHED BY - ELECTRICAL SERVICE AVAILABLE 120 1 60 DESIGN MANUFACTURER COOK MODEL NUMBER GC-140 SERVICE SWITCH NO SMOKE DETECTORS NO W FIRE DAMPER NO o CONSTRUCTION ALUMINUM MUL71BLADE BACKDRAFT DAMPER YES 8 BIRDSCREEN NO SOLID STATE SPEED CONTROL NO 10 MIN. TIME OFF RELAY CONTROL NO FACTORY FABRICATED CURB INU SONES 12.5 NOTE I 1 NOTE: 1. INTERLOCK WITH LIGHT SWITCH 2. PROVIDE DEDICATED SWITCH COOLING LOAD SUMMARY UNIT NO. [SO. FT.] AC-1 FLOOR AREA [SO. FT.] 779 OUTSIDE DRY BULB IT] 91 OUTDOOR WET BULB [F] 78 RELATIVE HUMIDITY [X] 50 INDOOR DRY BULB [T] 75 GRAINS OF WATER [DIFF] 1.73 TOTAL COOLING / O.A. [BTU/HR] 26.0 TOTAL SENSIBLE GAIN [BTU/HR] 19.0 TOTAL LATENT GAIN [BTU/HR] 7.0 TOTAL HEATING / O.A. [BTU/HR] 10.3 GENERAL SPECIFICATIONS 1. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND COMPLETED IN FIRST CLASS WORKMANLIKE MANNER, ANY MATERIALS INSTALLED, WHICH SHALL NOT PRESENT AN ORDERLY AND REASONABLY NEAT OR WORKMANLIKE APPEARANCE, SHALL BE REMOVED AND REPLACED WHEN SO DIRECTED BY THE ARCHITECT/ENGINEER AT THE CONTRACTOR'S EXPENCE. i 2. NEW DUCTWORK SHOWN IS SCHEMATIC. PLAN ROUTING OF DUCTWORK AND COORDINATE LOCATION OF DUCTS AFTER INSPECTION OF EXISTING CONDITIONS AND BEFORE FABRICATION, SLIGHT VARIATION OF ROUTING AND/OR CONSTRUCTION SHOULD BE ANTICIPATED AND IS EXPRESSLY INCLUDED AS PART OF THE WORK WHENEVER REQUIRED, AT NO ADDITIONAL COST TO OWNER. IGNORANCE ON THE PART OF THE CONTRACTOR WILL IN NO WAY EXCUSE HIM OR SHE FROM THE OBLIGATIONS AND RESPONSIBILITIES OF THIS CONTRACT, 3. ANY CONFLICTS OR DISCREPANCIES ON THESE DRAWINGS SHALL BE CALLED TO THE ATTENTION OF THE ARCHITECT/ENGINEER DURING THE BIDDING PERIOD FOR RESOLUTION, OTHERWISE, ALL SUCH CONFLICTS OR DISCREPANCIES SHALL BE RESOLVED AT THE CONTRACTOR'S EXPENSE. 4. ALL CONTROL WIRING SHALL BE PROVIDED BY THE CONTRACTOR. 5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION WITH ALL OTHER TRADES FOR CLEARANCES AND USE OF AVAILABLE SPACE. 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL PERMITS, FEES, INSPECTIONS AND TEST, 7. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR THE INSTALLATION OF A COMPLETE MECHANICAL SYSTEM, READY FOR CONTINUOUS AND SATISFACTORY OPERATION BY THE OWNER, 8. THE ENTIRE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE AND LOCAL CODES, INCLUDING ALL LOCAL RULES AND ORDINANCES. 9. PROVIDE MANUAL DAMPERS WHERE SHOWN ON THE DRAWINGS. DAMPERS SHALL BE MANUFACTURED ACCORDING TO SMACNA 'HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE' FIRST EDITION AND SHALL HAVE LOCKING QUADRANT WITH WING NUT, 10, DUCTWORK MATERIAL SUPPLY AIR DUCTWORK SHALL BE CONSTRUCTED OF FIVE POUNDS DENSITY 1-1/2- THICK GLASSFIBER DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNKS LOW PRESURE DUCT MANUAL. ALL DUCT JOINTS SHALL BE SEALED AND TAPED. 11. ALL EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL, INSTALLED IN ACCORDANCE WITH SMACNA 'HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE, FIRST EDITION. 12. FLEXIBLE DUCTS SHALL BE UL LISTED CLASS 1 AIR DUCT, THERMAFLEX TYPE M-KE OR EQUAL, DUCTS SHALL BE INSTALLED IN ACCORDANCE j WITH SMACNA 'HAVC DUCT CONSTRUCTIONSTANDARDS METAL AND FLEXIBLE' FIRST EDITION. 13. DUCTWORK DIMENSIONS INDICATED, ARE INSIDE CLEAR AIR PASSAGE. ALL EQUIPMENT AND MATERIAL SHALL BE"'WARRENTIED FOR ONE YEAR AFTER DATE OF ACCEPTANCE BY THE OWNER, 14. AIR DISTRIBUTION DEVICES SHALL BE OF ALL ALUMINUM CONSTRUCTION WITH TYPE #25 FINISH. ALL DIFFUSERS,'' REGISTERS AND GRILLS SHALL HAVE OPPOSED BLADE DAMPERS IN THROAT OR NECK, MANUFACTURER SHALL BE METALAIR OR PRE -APPROVED EQUAL, 15. THE INSIDE OF ALL VISIBLE DIFFUSERS SHALL BE PAINTED BLACK. 16. A/C/ CONTRACTOR TO INCLUDE 1 YEAR MAINTENANCE OF THE SYSTEM. A/C SYMBOL LEGEND m DOUBLE LINE SINGLE LINE 20 x 12 DUCT (1ST. DIMENSION, SIDE SHOWN; q n ry 2ND. DIMENSION, SIDE NOT SHOWN) ry ACOUSTICAL LINING -- - (DUCT DIMENSIONS FOR NET FREE AREA) DIRECTION OF FLOW -" ® DUCT SECTION UP OR DOWN (SUPPLY) DUCT SECTION UP OR DOWN (EXHAUST OR RETURN) INCLINE OR PROP R .- DIRECTION FLDOWARROW E0TRANSITIONS � i- S STANDARD BRANCH FOR SUPPLY & RETURN --/ (NO SPLITER)41 SPLITTER DAMPER VD VOLUME DAMPER 1 (MANUAL OPERATION) L AUTOMATIC DAMPERS 1 MOTOR OPERATED) SEC 3 MOD. MOD. AD AP -�, ACCESS DOOR (AD)) AD AP ACCESS PANEL (AP) vrAD �■- FIRE DAMPER AP IN VERTICAL DUCT / IN HORIZONTAL DUCT SMOKE DAMPER & RADIANT DAMPER AD DYNAMIC MOTORIZED DAMPER BACK DRAFT DAMPER F- BDD CEILING DIFFUSER, SQUARE E 3 CEILING DIFFUSER, RECTANGULAR CEILING DIFFUSER, ROUND 0 SMOKE DETECTOR, DUCT MOUNTED A EXHAUST FAN, CEILING MOUNTED E-----I RETURN AIR GRILLE, CEILING MOUNTED ( } THERMOSTAT HUMIDISTAT (H ) 00O2 CENSOR (C ) OEF-X CENTRIFUGAL EXHAUST FAN EF-X ROOF MOUNTED NOTE : THESE ARE STANDARD SYMBOLS AND MAY NOT ALL APPEAR ON PROJECT DRAWINGS AIR DISTRIBUTION SCHEDULE SYM USE TYPE ACCESSORIES NECK SIZE CFM MFR &MODEL NO tOx4 0-100 Q SUPPLY GRILLE O.B.D. 1Ox6 101-200 METAL AIRE 12x8 201-300 H4002-1 16x8 301-450 12x6 0-100 O RETURN GRILLE _ 16x6 101-200 METAL AIRE 20x8 201-400 H4002R-1 2802 401-1200 30x12 1201-1400 Oc RETURN GRILLE - 18x18 0-800 METAL HIRE 22x22 801-1200 RH-1 NOTE: CONTRACTOR TO PROVIDE ROUND TO SQUARE NECK TRANSITON. .�, w s 'o µ_ 0n R� w z 0 C� n ry �nry ®CL C) R w G7 Fine Line Engineering Inc. Electrical, Mechanical,' Plumbing Fire Protect' nru�ihpn Administration 5975 W. S s"%Blvd..Sjnt sunrise, Ft. 33313 Voice: 454 5g� 3 6 !� . 9Sgg 9 4-3343 kiecEin� Ineeis,cem N O 2, 9; 673 �. Al •`. ;p�i�q�p 4, 32578 co Z w O w Q M UJI Z� Q WC) _� O 0 E" t W Q J W 5-3 � V Q w W D ~ LO 0 CD e- o o w C r O li ZU3 o44Qa0 z LU w m ¢ Q m w ~O 0 OUcoa CD q w co o U i W M1.0 V/ < i